Earlier editions: 2026-07
Chapter 5 — Buildings›Article I — BUILDING CODE
Cypress Municipal Code § 11.2 Building Code
Cypress Municipal Code · 2026-10 edition · updated 2026-10-05 · Cypress
Cite as: Cypress Municipal Code § 11.2 · Text as of 2026-10-05
11.2.3.1.1.1 The available water supply for fire sprinkler system design shall be…¶
Subtract the project site elevation from the low water level for the appropriate pressure zone and multiply the result by 0.433.
Use a maximum of 40 psi, if available.
Utilize the OCFA water-flow test form/directions to document a flow test conducted by the local water agency or an approved third party licensed in the State of California.
(5) NFPA 13D 2025 Edition, Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes is hereby amended as follows:
(i) Section 7.1.2 is hereby revised as follows: