Earlier editions: 2026-07
Chapter 5 — Buildings›Article I — BUILDING CODE
Cypress Municipal Code § 11.1 Building Code
Cypress Municipal Code · 2026-10 edition · updated 2026-10-05 · Cypress
Cite as: Cypress Municipal Code § 11.1 · Text as of 2026-10-05
11.1.1.1 When fire sprinkler systems are required in buildings of undetermined use…¶
11.1.1.1 When fire sprinkler systems are required in buildings of undetermined use other than warehouses, they shall be designed and installed to have a fire sprinkler density of not less than that required for an Ordinary Hazard Group 2 use, with no reduction(s) in density or design area. Warehouse fire sprinkler systems shall be designed to Figure 16.2.1.3.2(d) curve "G." Use is considered undetermined if a specific tenant/occupant is not identified at the time the sprinkler plan is submitted. Where a subsequent use or occupancy requires a system with greater capability, it shall be the responsibility of the occupant to upgrade the system to the required density for the new use or occupancy.
(iii) Section 11.2.3.1.1.1 is hereby added as follows:
Get a plain-English answer with a citation back to this text.
Ask AI about this code