Skip to content

Chapter 7 — WALL COVERING

Section R703

California Residential Code (Title 24, Part 2.5) · 2022 edition · updated 2026-09-12 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

R703.1 General.

Exterior walls shall provide the building with a weather-resistant exterior wall envelope. The exterior wall envelope shall include flashing as described in Section R703.4.

Exception: Log walls designed and constructed in accordance with the provisions of ICC 400.

R703.1.1 Water resistance. The exterior wall envelope shall be designed and constructed in a manner that prevents the accumulation of water within the wall assembly by providing a water-resistant barrier behind the exterior cladding as required by Section R703.2 and a means of draining to the exterior water that penetrates the exterior cladding.

Exceptions:

  1. A weather-resistant exterior wall envelope shall not be required over concrete or masonry walls designed in accordance with Chapter 6 and
TABLE R702.7(1) VAPOR RETARDER MATERIALS AND CLASSES
CLASS ACCEPTABLE MATERIALS
I Sheet polyethylene, nonperforated aluminum foil or other approved materials with a perm rating less than or equal to 0.1.
II Kraft-faced fiberglass batts, vapor retarder paint or other approved materials applied in accordance with the manufacturer’s instal-
lation instructions for a perm rating greater than 0.1 and less than or equal to 1.0.
III Latex paint, enamel paint or other approved materials applied in accordance with the manufacturer’s installation instructions for a
perm rating greater than 1.0 and less than or equal to 10.0.
TABLE R702.7(2) VAPOR RETARDER OPTIONS
CLIMATE ZONE VAPOR RETARDER CLASS VAPOR RETARDER CLASS VAPOR RETARDER CLASS
CLIMATE ZONE CLASS Ia CLASS IIa CLASS III
1, 2 Not Permitted Not Permitted Permitted
3, 4 (except Marine 4) Not Permitted Permittedc Permitted
Marine 4, 5, 6, 7, 8 Permittedb Permittedc See Table R702.7(3)

a. Class I and II vapor retarders with vapor permeance greater than 1 perm when measured by ASTM E96 water method (Procedure B) shall be allowed on the

interior side of any frame wall in all climate zones. b. Use of a Class I interior vapor retarder in frame walls with a Class I vapor retarder on the exterior side shall require an approved design. c. Where a Class II vapor retarder is used in combination with foam plastic insulating sheathing installed as continuous insulation on the exterior side of frame

walls, the continuous insulation shall comply with Table R702.7(4) and the Class II vapor retarder shall have a vapor permeance greater than 1 perm when measured by ASTM E96 water method (Procedure B).

7-8 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

TABLE R702.7(3) CLASS III VAPOR RETARDERS
CLIMATE ZONE CLASS III VAPOR RETARDERS PERMITTED FOR:a, b
Marine 4 Vented cladding over wood structural panels.
Marine 4 Vented cladding over fiberboard.
Marine 4 Vented cladding over gypsum.
Marine 4 Continuous insulation with_R_-value ≥ 2.5 over 2 × 4 wall.
Marine 4 Continuous insulation with_R_-value ≥ 3.75 over 2 × 6 wall.
5 Vented cladding over wood structural panels.
5 Vented cladding over fiberboard.
5 Vented cladding over gypsum.
5 Continuous insulation with_R_-value ≥ 5 over 2 × 4 wall.
5 Continuous insulation with_R_-value ≥ 7.5 over 2 × 6 wall.
6 Vented cladding over fiberboard.
6 Vented cladding over gypsum.
6 Continuous insulation with_R_-value ≥ 7.5 over 2 × 4 wall.
6 Continuous insulation with_R_-value ≥ 11.25 over 2 × 6 wall.
7 Continuous insulation with_R_-value ≥ 10 over 2 × 4 wall.
7 Continuous insulation with_R_-value ≥ 15 over 2 × 6 wall.
8 Continuous insulation with_R_-value ≥ 12.5 over 2 × 4 wall.
Continuous insulation with_R_-value ≥ 20 over 2 × 6 wall.

a. Vented cladding shall include vinyl, polypropylene, or horizontal aluminum siding, brick veneer with a clear airspace as specified in Table R703.8.4(1), and

other approved vented claddings. b. The requirements in this table apply only to insulation used to control moisture in order to permit the use of Class III vapor retarders. The insulation materials

used to satisfy this option also contribute to but do not supersede the thermal envelope requirements of Chapter 11.

TABLE R702.7(4) CONTINUOUS INSULATION WITH CLASS II VAPOR RETARDER
CLIMATE ZONE CLASS II VAPOR RETARDERS PERMITTED FOR:a
3 Continuous insulation with_R_-value ≥ 2.
4, 5 and 6 Continuous insulation with_R_-value ≥ 3 over 2 × 4 wall.
Continuous insulation with_R_-value ≥ 5 over 2 × 6 wall.
7 Continuous insulation with_R_-value ≥ 5 over 2 × 4 wall.
Continuous insulation with_R_-value ≥ 7.5 over 2 × 6 wall.
8 Continuous insulation with_R_-value ≥ 7.5 over 2 × 4 wall.
Continuous insulation with_R_-value ≥ 10 over 2 × 6 wall.

a. The requirements in this table apply only to insulation used to control moisture in order to permit the use of Class II vapor retarders. The insulation materials

used to satisfy this option also contribute to but do not supersede the thermal envelope requirements of Chapter 11.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

TABLE R702.7(5) IECC VS. CALIFORNIA ENERGY CODE CLIMATE ZONE COMPARISON

IECCa CALIFORNIA
ENERGY CODE
DESCRIPTIONb
_6 _ 16 Includes Alpine, Mono Counties
_5 _ 11, 12, 16 Includes Siskiyou, Modoc, Lassen, Plumas, Sierra, Nevada Counties
4 (marine) 1, 2, 16 Includes Del Norte and Humboldt Counties
_4 _ 2, 12, 13, 16 Includes Inyo, Trinity, Lake, El Dorado, Amador, Calaveras, Tuolumne, Mariposa Counties
_3 _ 8, 9, 10,11,12,
13, 14, 15, 16
Includes Shasta, Tehama, Butte, Glenn, Colusa, Yuba, Contra Costa, Sutter, Yolo, Sacramento, Placer,
San Joaquin, Solano, Stanislaus, Merced, Madera, Fresno, Kings, Tulare, Kern, Ventura, Los Angeles,
Orange, San Bernardino, Riverside Counties
3 (marine) 1, 2, 3, 4, 5, 6,
9, 12, 16
Includes Mendocino, Sonoma, Marin, San Francisco, San Mateo, Alameda, Santa Cruz, Monterey,
San Benito, San Luis Obispo, Santa Barbara, Ventura, San Diego Counties
_2 _ 14, 16 Includes Imperial County

a. IECC Climate Zones 1, 7 and 8 do not occur in California, nor do any IECC moist climate zones. b. IECC boundaries are defined by county political boundary lines. California Energy Code boundaries are based on metes and bounds specifications aligned

with climate-affecting geographic features, which often do not coincide with county lines.

R703.1.2 Wind resistance. Wall coverings, backing materials and their attachments shall be capable of resisting wind loads in accordance with Tables R301.2.1(1) and R301.2.1(2). Wind-pressure resistance of the siding, soffit and backing materials shall be determined by ASTM E330 or other applicable standard test methods. Where wind-pressure resistance is determined by design analysis, data from approved design standards and analysis conforming to generally accepted engineering practice shall be used to evaluate the siding, soffit and backing material and its fastening. All applicable failure modes including bending rupture of siding, fastener withdrawal and fastener head pull-through shall be considered in the testing or design analysis. Where the wall covering, soffit and backing material resist wind load as an assembly, use of the design capacity of the assembly shall be permitted.

R703.2 Water-resistive barrier.

Not fewer than one layer of water-resistive barrier shall be applied over studs or sheathing of all exterior walls with flashing as indicated in Section R703.4, in such a manner as to provide a continuous water-resistive barrier behind the exterior wall veneer. The water-resistive barrier material shall be continuous to the top of walls and terminated at penetrations and building appendages in a manner to meet the requirements of the exterior wall envelope as described in Section R703.1. Water-resistive barrier materials shall comply with one of the following:

  1. No. 15 felt complying with ASTM D226, Type 1.

  2. ASTM E2556, Type 1 or 2.

  3. ASTM E331 in accordance with Section R703.1.1.

  4. Other approved materials in accordance with the manufacturer’s installation instructions.

No.15 asphalt felt and water-resistive barriers complying with ASTM E2556 shall be applied horizontally, with the upper layer lapped over the lower layer not less than 2

inches (51 mm), and where joints occur, shall be lapped not less than 6 inches (152 mm).

R703.3 Wall covering nominal thickness and attach-ments.

ments. The nominal thickness and attachment of exterior wall coverings shall be in accordance with Table R703.3(1), the wall covering material requirements of this section, and the wall covering manufacturer’s installation instructions. Cladding attachment over foam sheathing shall comply with the additional requirements and limitations of Sections R703.15 through R703.17. Nominal material thicknesses in Table R703.3(1) are based on a maximum stud spacing of 16 inches (406 mm) on center. Where specified by the siding manufacturer’s instructions and supported by a test report or other documentation, attachment to studs with greater spacing is permitted. Fasteners for exterior wall coverings attached to wood framing shall be in accordance with Section R703.3.3 and Table R703.3(1). Exterior wall coverings shall be attached to cold-formed steel light frame construction in accordance with the cladding manufacturer’s installation instructions, the requirements of Table R703.3(1) using screw fasteners substituted for the nails specified in accordance with Table R703.3(2), or an approved design.

R703.3.1 Soffit installation. Soffits shall comply with Section R704.

R703.3.2 Wind limitations. Where the design wind pressure exceeds 30 psf or where the limits of Table R703.3.2 are exceeded, the attachment of wall coverings and soffits shall be designed to resist the component and cladding loads specified in Table R301.2.1(1) for walls, adjusted for height and exposure in accordance with Table R301.2.1(2). For the determination of wall covering and soffit attachment, component and cladding loads shall be determined using an effective wind area of 10 square feet (0.93 m 2 ).

7-10 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

TABLE R703.3(1) SIDING MINIMUM ATTACHMENT AND MINIMUM THICKNESS

SIDING MATERIAL NOMINAL
THICKNESS
(inches)
JOINT
TREATMENT
TYPE OF SUPPORTS FOR THE SIDING MATERIAL AND FASTENERS
SIDING MATERIAL SIDING MATERIAL NOMINAL
THICKNESS
(inches)
JOINT
TREATMENT
Wood or wood
structural
** panel**
sheathing
into stud
Fiberboard
sheathing
into stud
Gypsum
sheathing
into stud
Foam
plastic
sheathing
into studl
Direct
to studs
Number or
spacing of
fasteners
Anchored veneer:
brick, concrete,
masonry or stone
(see Section R703.8)
Anchored veneer:
brick, concrete,
masonry or stone
(see Section R703.8)
2 Section
R703.8
Section R703.8 Section R703.8 Section R703.8 Section R703.8 Section R703.8 Section R703.8
Adhered veneer: concrete,
stone or masonry
(see Section R703.12)
Adhered veneer: concrete,
stone or masonry
(see Section R703.12)
Section
R703.12
Section R703.12 Section R703.12 Section R703.12 Section R703.12 Section R703.12 Section R703.12
Fiber cement
siding
Panel siding
(see Section
R703.10.1)
5/16 Section
R703.10.1
6d common
(2″ × 0.113″)
6d common
(2″ × 0.113″)
6d common
(2″ × 0.113″)
6d common
(2″ × 0.113″)
4d common
(11/2″ ×
0.099″)
6″ panel edges
12″ inter. sup.
Fiber cement
siding
Lap siding
(see Section
R703.10.2)
5/16 Section
R703.10.2
6d common
(2″ × 0.113″)
6d common
(2″ × 0.113″)
6d common
(2″ × 0.113″)
6d common
(2″ × 0.113″)
6d common
(2″ × 0.113″)
or 11 gage
roofing nail
Note f
Hardboard panel siding
(see Section R703.5)
Hardboard panel siding
(see Section R703.5)
7/16 0.120″ nail
(shank) with
0.225″ head
0.120″ nail
(shank) with
0.225″ head
0.120″ nail
(shank) with
0.225″ head
0.120″ nail
(shank) with
0.225″ head
0.120″ nail
(shank) with
0.225″ head
6″ panel edges
12″ inter. sup.d
Hardboard lap siding
(see Section R703.5)
Hardboard lap siding
(see Section R703.5)
7/16 Note e 0.099″ nail
(shank) with
0.240″ head
0.099″ nail
(shank) with
0.240″ head
0.099″ nail
(shank) with
0.240″ head
0.099″ nail
(shank) with
0.240″ head
0.099″ nail
(shank) with
0.240″ head
Same as stud
spacing 2 per
bearing
Horizontal
aluminuma
Without
insulation
0.019b Lap Siding nail
11/2″ × 0.120″
Siding nail
2″ × 0.120″
Siding nail
2″ × 0.120″
Siding nailh
11/2″ × 0.120″
Not
allowed
Same as stud
spacing
Horizontal
aluminuma
Without
insulation
0.024 Lap Siding nail
11/2″ × 0.120″
Siding nail
2″ × 0.120″
Siding nail
2″ × 0.120″
Siding nailh
11/2″ × 0.120″
Not
allowed
Not
allowed
Horizontal
aluminuma
With insula-
tion
0.019 Lap Siding nail
11/2″ × 0.120″
Siding nail
21/2″ × 0.120″
Siding nail
21/2″ × 0.120″
Siding nailh
11/2″ × 0.120″
Siding nail
11/2″ × 0.120″
Siding nail
11/2″ × 0.120″
Insulated vinyl sidingj Insulated vinyl sidingj 0.035 (vinyl
siding layer
only)
Lap 0.120 nail
(shank) with a
0.313 head or
16-gage
crownh, i
0.120 nail
(shank) with a
0.313 head or
16-gage
crownh
0.120 nail
(shank) with a
0.313 head or
16-gage
crownh
0.120 nail
(shank) with a
0.313 head
Section
R703.11.2
Not
allowed
16 inches on
center or
specified by
manufacturer
instructions, test
report or other
sections of this
code
Particleboard panels Particleboard panels 3/8 6d box nail
(2″ × 0.099″)
6d box nail
(2″ × 0.099″)
6d box nail
(2″ × 0.099″)
6d box nail
(2″ × 0.099″)
Not
allowed
6″ panel edges
12″ inter. sup.
Particleboard panels Particleboard panels 1/2 6d box nail
(2″ × 0.099″)
6d box nail
(2″ × 0.099″)
6d box nail
(2″ × 0.099″)
6d box nail
(2″ × 0.099″)
6d box nail (2″
× 0.099″)
6d box nail (2″
× 0.099″)
Particleboard panels Particleboard panels 5/8 6d box nail
(2″ × 0.099″)
8d box nail
(21/2″ ×
0.113″)
8d box nail
(21/2″ ×
0.113″)
6d box nail
(2″ × 0.099″)
6d box nail (2″
× 0.099″)
6d box nail (2″
× 0.099″)
Polypropylene sidingk Polypropylene sidingk Not
applicable
Lap Section
703.14.1
Section
703.14.1
Section
703.14.1
Section
703.14.1
Not
allowed
As specified by
the manufac-
turer instruc-
tions, test report
or other sections
of this code
Steelc Steelc 29 ga. Lap Siding nail
(13/4″ ×
0.113″) Sta-
ple–13/4
Siding nail
(23/4″ ×
0.113″) Sta-
ple–21/2
Siding nail
(21/2″ ×
0.113″) Sta-
ple–21/4
Siding nail
(13/4″ ×
0.113″) Sta-
ple–13/4
Not
allowed
Same as
stud spacing

(continued)

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

TABLE R703.3(1)—continued SIDING MINIMUM ATTACHMENT AND MINIMUM THICKNESS

SIDING MATERIAL NOMINAL
THICKNESS
(inches)
JOINT
TREATMENT
TYPE OF SUPPORTS FOR THE SIDING MATERIAL AND FASTENERS
SIDING MATERIAL SIDING MATERIAL NOMINAL
THICKNESS
(inches)
JOINT
TREATMENT
Wood or wood
structural
** panel**
sheathing
into stud
Fiberboard
sheathing
into stud
Gypsum
sheathing
into stud
Foam
plastic
sheathing
into studl
Direct
to studs
Number or
spacing of
fasteners
Vinyl siding
(see Section R703.11)
Vinyl siding
(see Section R703.11)
0.035 Lap 0.120″ nail
(shank) with
a 0.313″ head
or 16-gage
staple with
3/8- to1/2-inch
crownh, i
0.120″ nail
(shank) with
a 0.313″ head
or 16-gage
staple with
3/8- to1/2-inch
crownh
0.120″ nail
(shank) with
a 0.313″ head
or 16-gage
staple with
3/8- to1/2-inch
crownh
0.120″ nail
(shank) with
a 0.313 head
Section
R703.11.2
Not
allowed
16 inches on
center or as
specified
by the
manufacturer
instructions or
test report
Wood siding
(see Section
R703.5)
Wood rustic,
drop
3/8 min. Lap 6d box or
siding nail
(2″ × 0.099″)
6d box or
siding nail
(2″ ×0.099″)
6d box or
siding nail
(2″ × 0.099″)
6d box or
siding nail
(2″ × 0.099″)
8d box or
siding nail
(21/2″ × 0.113″)
Staple–2″
Face nailing up
to 6″ widths,
1 nail per bear-
ing; 8″ width
sand over,
2 nails per
bearing
Wood siding
(see Section
R703.5)
Shiplap 19/32 average Lap Lap Lap Lap Lap Lap Lap
Wood siding
(see Section
R703.5)
Bevel 7/16 7/16 7/16 7/16 7/16 7/16 7/16 7/16
Wood siding
(see Section
R703.5)
Butt tip 3/16 Lap Lap Lap Lap Lap Lap Lap
Wood structural panel
ANSI/APA PRP-210
siding (exterior grade)
(see Section R703.5)
Wood structural panel
ANSI/APA PRP-210
siding (exterior grade)
(see Section R703.5)
3/8 –1/2 Note e 2″ × 0.099″
siding nail
21/2″ × 0.113″
siding nail
21/2″ × 0.113″
siding nail
21/2″ × 0.113″
siding nail
2″ × 0.099″
siding nail
6″ panel edges
12″ inter. sup.
Wood structural
panel lap siding
(see Section R703.5)
Wood structural
panel lap siding
(see Section R703.5)
3/8 –1/2 Note e
Note g
2″ × 0.099″
siding nail
21/2″ × 0.113″
siding nail
21/2″ × 0.113″
siding nail
21/2″ × 0.113″
siding nail
2″ × 0.099″
siding nail
8″ along bot-
tom edge

For SI: 1 inch = 25.4 mm. a. Aluminum nails shall be used to attach aluminum siding. b. Aluminum (0.019 inch) shall be unbacked only where the maximum panel width is 10 inches and the maximum flat area is 8 inches. The tolerance for

aluminum siding shall be +0.002 inch of the nominal dimension. c. Shall be of approved type. d. Where used to resist shear forces, the spacing must be 4 inches at panel edges and 8 inches on interior supports. e. Vertical end joints shall occur at studs and shall be covered with a joint cover or shall be caulked. f. Face nailing: one 6d common nail through the overlapping planks at each stud. Concealed nailing: one 11-gage 1 1 /2-inch-long galv. roofing nail through the

top edge of each plank at each stud in accordance with the manufacturer’s installation instructions. g. Vertical joints, if staggered, shall be permitted to be away from studs if applied over wood structural panel sheathing. h. Minimum fastener length must be sufficient to penetrate sheathing other nailable substrate and framing a total of a minimum of 1 1 /4 inches or in accordance

with the manufacturer’s installation instructions. i. Where specified by the manufacturer’s instructions and supported by a test report, fasteners are permitted to penetrate into or fully through nailable sheathing

or other nailable substrate of minimum thickness specified by the instructions or test report, without penetrating into framing. j. Insulated vinyl siding shall comply with ASTM D7793. k. Polypropylene siding shall comply with ASTM D7254. l. Cladding attachment over foam sheathing shall comply with the additional requirements and limitations of Sections R703.15, R703.16 and R703.17.

R703.3.3 Fasteners. Exterior wall coverings and roof overhang soffits shall be securely fastened with aluminum, galvanized, stainless steel or rust-preventative coated nails or staples in accordance with Table R703.3(1) or with other approved corrosion-resistant fasteners in accordance with the wall covering manufacturer’s installation instructions. Nails and staples shall comply with ASTM F1667. Nails shall be T-head, modified round head, or round head with smooth or deformed shanks. Staples shall have a minimum crown width of 7 /16 inch (11.1 mm) outside diameter and be manufactured of minimum 16-gage wire. Where fiberboard, gypsum, or foam plastic sheathing backing is used, nails or staples shall be driven into the studs. Where wood or wood structural panel sheathing is used, fasteners shall be driven into studs unless otherwise permitted to be driven into sheathing in accordance with either the siding manufacturer’s installation instructions or Table R703.3.3.

R703.3.4 Minimum fastener length and penetration. Fasteners shall have the greater of the minimum length specified in Table R703.3(1) or as required to provide a minimum penetration into framing as follows:

  1. Fasteners for horizontal aluminum siding, steel siding, particleboard panel siding, wood structural panel siding in accordance with ANSI/APA-PRP 210, fiber-cement panel siding and fiber-cement lap siding installed over foam plastic sheathing shall penetrate not less than 1 1 /2 inches (38 mm) into framing or shall be in accordance with the manufacturer’s installation instructions.

  2. Fasteners for hardboard panel and lap siding shall penetrate not less than 1 1 /2 inches (38 mm) into framing.

  3. Fasteners for vinyl siding and insulated vinyl siding installed over wood or wood structural panel sheathing shall penetrate not less than 1 1 /4 inches (32 mm) into

7-12 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

sheathing and framing combined. Vinyl siding and insulated vinyl siding shall be permitted to be installed with fasteners penetrating into or through wood or wood structural sheathing of minimum thickness as specified by the manufacturer’s instructions or test report, with or without penetration into the framing. Where the fastener penetrates fully through the sheathing, the end of the fastener shall extend not less than 1 /4 inch (6.4 mm) beyond the opposite face of the sheathing. Fasteners for vinyl siding and insulated vinyl siding installed over foam plastic sheathing shall be in accordance with Section R703.11.2. Fasteners for vinyl siding and insulated vinyl siding installed over fiberboard or gypsum sheathing shall penetrate not less than 1 1 /4 inches (32 mm) into framing.

  1. Fasteners for vertical or horizontal wood siding shall penetrate not less than 1 1 /2 inches (38 mm) into studs, studs and wood sheathing combined, or blocking.

  2. Fasteners for siding material installed over foam plastic sheathing shall have sufficient length to accommodate foam plastic sheathing thickness and to penetrate framing or sheathing and framing combined, as specified in Items 1 through 4.

TABLE R703.3(2) SCREW FASTENER SUBSTITUTION FOR SIDING ATTACHMENT TO COLD-FORMED

TABLE R703.3.2 LIMITS FOR ATTACHMENT PER Table R703.3(1)
MAXIMUM MEAN ROOF HEIGHT MAXIMUM MEAN ROOF HEIGHT MAXIMUM MEAN ROOF HEIGHT MAXIMUM MEAN ROOF HEIGHT
Ultimate Wind Speed
(mph 3-second gust)
Exposure Exposure Exposure
Ultimate Wind Speed
(mph 3-second gust)
B C D
95 NL NL NL
100 NL NL NL
105 NL NL NL
110 NL NL 40′
115 NL 50′ 20′
120 NL 30′ DR
130 60′ 15′ DR
140 35′ DR DR

For SI: 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s. NL = Not Limited by Table R703.3.2, DR = Design Required.

R703.4 Flashing.

Approved corrosion-resistant flashing shall be applied shingle-fashion in a manner to prevent entry of water into the wall cavity or penetration of water to the building structural framing components. Self-adhered membranes used as flashing shall comply with AAMA 711. Fluid-applied membranes used as flashing in exterior walls shall comply with AAMA 714. The flashing shall extend to the surface of the exterior wall finish. Approved corrosionresistant flashings shall be installed at the following locations:

  1. Exterior window and door openings. Flashing at exterior window and door openings shall be installed in accordance with Section R703.4.1.

  2. At the intersection of chimneys or other masonry construction with frame or stucco walls, with projecting lips on both sides under stucco copings.

  3. Under and at the ends of masonry, wood or metal copings and sills.

  4. Continuously above all projecting wood trim.

  5. Where exterior porches, decks or stairs attach to a wall or floor assembly of wood-frame construction.

  6. At wall and roof intersections.

  7. At built-in gutters.

WALL COVERING

STEEL LIGHT FRAME C CONSTRUCTIONa, b, c, d, e
NAIL DIAMETER PER
TABLE R703.3(1)
MINIMUM SCREW
FASTENER SIZE
0.099″ No. 6
0.113″ No. 7
0.120″ No. 8

For SI: 1 inch = 25.4 mm. a. Screws shall comply with ASTM C1513 and shall penetrate a minimum

of three threads through minimum 33 mil (20 gage) cold-formed steel frame construction. b. Screw head diameter shall be not less than the nail head diameter required

by Table R703.3(1). c. Number and spacing of screw fasteners shall comply with Table

R703.3(1). d. Pan head, hex washer head, modified truss head or other screw head types

with a flat attachment surface under the head shall be used for vinyl siding attachment. e. Aluminum siding shall not be fastened directly to cold-formed steel light

frame construction.

TABLE R703.3.3 OPTIONAL SIDING ATTACHMENT SCHEDULE FOR FASTENERS WHERE NO STUD PENETRATION NECESSARY

NUMBER AND TYPE OF FASTENER SPACING OF
FASTENERSb
Ring shank roofing nail (0.120″ min. dia.) 12″ o.c.
Ring shank nail (0.148″ min. dia.) 15″ o.c.
No. 6 screw (0.138″ min. dia.) 12″ o.c.
No. 8 screw (0.164″ min. dia.) 16″ o.c.

For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.479 kPa. a. Fastener length shall be sufficient to penetrate the back side of the wood structural panel sheathing by at least 1 /4 inch. The wood structural panel sheathing

shall be not less than 7 /16 inch in thickness. b. Spacing of fasteners is per 12 inches of siding width. For other siding widths, multiply “Spacing of Fasteners” above by a factor of 12/s, where “s” is the

siding width in inches. Fastener spacing shall never be greater than the manufacturer’s minimum recommendations.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

R703.4.1 Flashing installation at exterior window and door openings. Flashing at exterior window and door openings shall extend to the surface of the exterior wall finish or to a water-resistive barrier complying with Section 703.2 for subsequent drainage. Air sealing shall be installed around all window and door openings on the interior side of the rough opening gap. Mechanically attached flexible flashings shall comply with AAMA 712. Flashing at exterior window and door openings shall be installed in accordance with one or more of the following:

  1. The fenestration manufacturer’s installation and flashing instructions, or for applications not addressed in the fenestration manufacturer’s instructions, in accordance with the flashing manufacturer’s instructions. Where flashing instructions or details are not provided, pan flashing shall be installed at the sill of exterior window and door openings. Pan flashing shall be sealed or sloped in such a manner as to direct water to the surface of the exterior wall finish or to the water-resistive barrier for subsequent drainage. Openings using pan flashing shall incorporate flashing or protection at the head and sides.

  2. In accordance with the flashing design or method of a registered design professional.

  3. In accordance with other approved methods.

R703.5 Wood, hardboard and wood structural panel siding.

siding. Wood, hardboard and wood structural panel siding shall be installed in accordance with this section and Table R703.3(1). Hardboard siding shall comply with ANSI A135.5.

R703.5.1 Vertical wood siding. Wood siding applied vertically shall be nailed to horizontal nailing strips or blocking set not more than 24 inches (610 mm) on center.

R703.5.2 Panel siding. Three-eighths-inch (9.5 mm) wood structural panel siding shall not be applied directly to studs spaced more than 16 inches (406 mm) on center where long dimension is parallel to studs. Wood structural panel siding 7 /16 inch (11.1 mm) or thinner shall not be applied directly to studs spaced more than 24 inches (610 mm) on center. The stud spacing shall not exceed the panel span rating provided by the manufacturer unless the panels are installed with the face grain perpendicular to the studs or over sheathing approved for that stud spacing.

Joints in wood, hardboard or wood structural panel siding shall be made as follows unless otherwise approved. Vertical joints in panel siding shall occur over framing members, unless wood or wood structural panel sheathing is used, and shall be shiplapped or covered with a batten. Horizontal joints in panel siding shall be lapped not less than 1 inch (25 mm) or shall be shiplapped or flashed with Z-flashing and occur over solid blocking, wood or wood structural panel sheathing.

R703.5.3 Horizontal wood siding. Horizontal lap siding shall be installed in accordance with the manufacturer’s recommendations. Where there are no recommendations the siding shall be lapped not less than 1 inch (25 mm), or 1/2 inch (12.7 mm) if rabbeted, and shall have the ends

caulked, covered with a batten or sealed and installed over a strip of flashing.

R703.6 Wood shakes and shingles.

Wood shakes and shingles shall conform to CSSB.

R703.6.1 Application. Wood shakes or shingles shall be applied either single course or double course over nominal 1/2-inch (12.7 mm) wood-based sheathing or to furring strips over 1 /2-inch (12.7 mm) nominal nonwood sheathing. A water-resistive barrier shall be provided over all sheathing, with horizontal overlaps in the membrane of not less than 2 inches (51 mm) and vertical overlaps of not less than 6 inches (152 mm). Where horizontal furring strips are used, they shall be 1 inch by 3 inches or 1 inch by 4 inches (25 mm by 76 mm or 25 mm by 102 mm) and shall be fastened to the studs with minimum 7d or 8d box nails and shall be spaced a distance on center equal to the actual weather exposure of the shakes or shingles, not to exceed the maximum exposure specified in Table R703.6.1. When installing shakes or shingles over a nonpermeable water-resistive barrier, furring strips shall be placed first vertically over the barrier and in addition, horizontal furring strips shall be fastened to the vertical furring strips prior to attaching the shakes or shingles to the horizontal furring strips. The spacing between adjacent shingles to allow for expansion shall be 1 /8 inch (3.2 mm) to 1 /4 inch (6.4 mm) apart, and between adjacent shakes shall be 3 /8 inch (9.5 mm) to 1 /2 inch (12.7 mm) apart. The offset spacing between joints in adjacent courses shall be not less than 1 1 /2 inches (38 mm).

TABLE R703.6.1 MAXIMUM WEATHER EXPOSURE FOR WOOD SHAKES AND SHINGLES ON EXTERIOR WALLS a, b, c

(Dimensions are in inches)

LENGTH EXPOSURE FOR
SINGLE COURSE
EXPOSURE FOR
DOUBLE COURSE
Shinglesa Shinglesa Shinglesa
16 7 12b
18 8 14c
24 101/2 16d
Shakesa Shakesa Shakesa
18 8 14
24 101/2 18

For SI: 1 inch = 25.4 mm. a. Dimensions given are for No. 1 grade. b. A maximum 9-inch exposure is permitted for No. 2 grade. c. A maximum 10-inch exposure is permitted for No. 2 grade. d. A maximum 14-inch exposure is permitted for No. 2 grade.

R703.6.2 Weather exposure. The maximum weather exposure for shakes and shingles shall not exceed that specified in Table R703.6.1.

R703.6.3 Attachment. Wood shakes or shingles shall be installed according to this chapter and the manufacturer’s instructions. Each shake or shingle shall be held in place by two stainless steel Type 304, Type 316 or hot-dipped zinc-coated galvanized corrosion-resistant box nails in accordance with Table R703.6.3(1) or R703.6.3(2). The hot-dipped zinc-coated galvanizing shall be in compliance with ASTM A153, 1.0 ounce per square foot. Alterna

7-14 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

tively, 16-gage stainless steel Type 304 or Type 316 staples with crown widths 7 /16 inch (11 mm) minimum, 3 /4 inch (19 mm) maximum, shall be used and the crown of the staple shall be placed parallel with the butt of the shake or the shingle. In single-course application, the fasteners shall be concealed by the course above and shall be driven approximately 1 inch (25 mm) above the butt line of the succeeding course and 3 /4 inch (19 mm) from the edge. In double-course applications, the exposed shake or shingle shall be face-nailed with two fasteners, driven approximately 2 inches (51 mm) above the butt line and 3 /4 inch (19 mm) from each edge. Fasteners installed within 15 miles (24 km) of saltwater coastal areas shall be stainless steel Type 316. Fasteners for fire-retardant-treated shakes or shingles in accordance with Section R902 or pressureimpregnated-preservative-treated shakes or shingles in accordance with AWPA U1 shall be stainless steel Type 316. The fasteners shall penetrate the sheathing or furring strips by not less than 1 /2 inch (13 mm) and shall not be overdriven. Fasteners for untreated (natural) and treated products shall comply with ASTM F1667.

R703.6.4 Bottom courses. The bottom courses shall be doubled.

WALL COVERING

R703.7 Exterior plaster (stucco).

Installation of exterior plaster shall be in compliance with ASTM C926, ASTM C1063 and the provisions of this code.

R703.7.1 Lath. Lath and lath attachments shall be of corrosion-resistant materials in accordance with ASTM C1063. Expanded metal, welded wire, or woven wire lath shall be attached to wood framing members or furring. Where the exterior plaster is serving as wall bracing in accordance with Table R602.10.4, the lath shall be attached directly to framing. The lath shall be attached with 1 1 /2-inch-long (38 mm), 11-gage nails having a 7 /16inch (11.1 mm) head, or 7 /8-inch-long (22.2 mm), 16gage staples, spaced not more than 7 inches (178 mm) on center along framing members or furring and not more than 24 inches (610 mm) on center between framing members or furring, or as otherwise approved. Additional fastening between wood framing members shall not be prohibited. Lath attachments to cold-formed steel framing or to masonry, stone, or concrete substrates shall be in accordance with ASTM C1063. Where lath is installed directly over foam sheathing, lath connections shall also be in accordance with Section R703.15, R703.16 or R703.17. Where lath is attached to furring

TABLE R703.6.3(1) SINGLE-COURSE SIDEWALL FASTENERS

PRODUCT TYPE NAIL TYPE, MINIMUM LENGTH AND SHANK DIAMETER (inches)
R & R and sanded shingles R & R and sanded shingles
16″ and 18″ shingles 3d box 11/4 × 0.076
24″ shingles 4d box 11/2 × 0.076
Grooved shingles Grooved shingles
16″ and 18″ shingles 3d box 11/4 × 0.076
24″ shingles 4d box 11/2 × 0.076
Split and sawn shakes Split and sawn shakes
18″ straight-split shakes 5d box 13/4 × 0.080
18″ and 24″ handsplit shakes 6d box 2 × 0.099
24″ tapersplit shakes 5d box 13/4 × 0.080
18″ and 24″ tapersawn shakes 6d box 2 × 0.099

For SI: 1 inch = 25.4 mm.

TABLE R703.6.3(2) DOUBLE-COURSE SIDEWALL FASTENERS

PRODUCT TYPE NAIL TYPE, MINIMUM LENGTH AND SHANK DIAMETER (inches)
R & R and sanded shingles R & R and sanded shingles
16″, 8″ and 24″ shingles 5d box 13/4 × 0.08 or 5d casing nails 13/4 × 0.080
Grooved shingles Grooved shingles
16″, 18″ and 24″shingles 5d box 13/4 × 0.080
Split and sawn shakes Split and sawn shakes
18″ straight-split shakes 7d box 21/4 × 0.099 or 8d box 21/2 × 0.113
18″ and 24″ handsplit shakes 7d box 21/4 × 0.099 or 8d box 21/2 × 0.113
24″ tapersplit shakes 7d box 21/4 × 0.099 or 8d box 21/2 × 0.113
18″ and 24″ tapersawn shakes 7d box 21/4 × 0.099 or 8d box 21/2 × 0.113

For SI: 1 inch = 25.4 mm.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

shall be in accordance with Section R703.15, R703.16 or R703.17.

Exception: Lath is not required over masonry, cast-inplace concrete, precast concrete or stone substrates prepared in accordance with ASTM C1063.

703.7.1.1 Furring. Where provided, furring shall consist of wood furring strips not less than 1 inch by 2 inches (25 mm by 51 mm), minimum 3 /4-inch (19 mm) metal channels, or self-furring lath, and shall be installed in accordance with ASTM C1063. Furring shall be spaced not greater than 24 inches (600 mm) on center and, where installed over wood or cold-formed steel framing, shall be fastened into framing members.

R703.7.2 Plaster. Plastering with cement plaster shall be in accordance with ASTM C926. Cement materials shall be in accordance with one of the following:

  1. Masonry cement conforming to ASTM C91, Type M, S or N.

  2. Portland cement conforming to ASTM C150, Type I, II or III.

  3. Blended hydraulic cement conforming to ASTM C595, Type IP, IS (< 70), IL, or IT (S < 70).

  4. Hydraulic cement conforming to ASTM C1157, Type GU, HE, MS, HS or MH.

  5. Plastic (stucco) cement conforming to ASTM C1328.

Plaster shall be not less than three coats where applied over metal lath or wire lath and shall be not less than two coats where applied over masonry, concrete, pressure-preservative-treated wood or decay-resistant wood as specified in Section R317.1 or gypsum backing. If the plaster surface is completely covered by veneer or other facing material or is completely concealed, plaster application need be only two coats, provided the total thickness is as set forth in Table R702.1(1).

On wood-frame construction with an on-grade floor slab system, exterior plaster shall be applied to cover, but not extend below, lath, paper and screed.

The proportion of aggregate to cementitious materials shall be as set forth in Table R702.1(3).

R703.7.2.1 Weep screeds. A minimum 0.019-inch (0.5 mm) (No. 26 galvanized sheet gage), corrosion-resistant weep screed or plastic weep screed, with a minimum vertical attachment flange of 3 1 /2 inches (89 mm), shall be provided at or below the foundation plate line on exterior stud walls in accordance with ASTM C926. The weep screed shall be placed not less than 4 inches (102 mm) above the earth or 2 inches (51 mm) above paved areas and shall be of a type that will allow trapped water to drain to the exterior of the building. The weather-resistant barrier shall lap the attachment flange. The exterior lath shall cover and terminate on the attachment flange of the weep screed. R703.7.3 Water-resistive barriers. Water-resistive barriers shall be installed as required in Section R703.2 and, where applied over wood-based sheathing, shall comply with Section R703.7.3.1 or R703.7.3.2.

R703.7.3.1 Dry climates. In Dry (B) climate zones indicated in Figure N1101.7, water-resistive barriers shall comply with one of the following:

  1. The water-resistive barrier shall be two layers of 10-minute Grade D paper or have a water resistance equal to or greater than two layers of a water-resistive barrier complying with ASTM E2556, Type I. The individual layers shall be installed independently such that each layer provides a separate continuous plane. Flashing installed in accordance with Section R703.4 and intended to drain to the water-resistive barrier shall be directed between the layers.

  2. The water-resistive barrier shall be 60-minute Grade D paper or have a water resistance equal to or greater than one layer of a water-resistive barrier complying with ASTM E2556, Type II. The water-resistive barrier shall be separated from the stucco by a layer of foam plastic insulating sheathing or other non-water-absorbing layer, or a designed drainage space.

R703.7.3.2 Moist or marine climates. In the Moist (A) or Marine (C) climate zones indicated in Figure N1101.7, water-resistive barriers shall comply with one of the following:

  1. In addition to complying with Section R703.7.3.1, a space or drainage material not less than 3 /16 inch (5 mm) in depth shall be added to the exterior side of the water-resistive barrier.

  2. In addition to complying with Section R703.7.3.1, Item 2, drainage on the exterior of the water-resistive barrier shall have a drainage efficiency of not less than 90 percent, as measured in accordance with ASTM E2273 or Annex A2 of ASTM E2925.

R703.7.4 Application. Each coat shall be kept in a moist condition for at least 48 hours prior to application of the next coat.

Exception: Applications installed in accordance with ASTM C926.

R703.7.5 Curing. The finish coat for two-coat cement plaster shall not be applied sooner than seven days after application of the first coat. For three-coat cement plaster, the second coat shall not be applied sooner than 48 hours after application of the first coat. The finish coat for threecoat cement plaster shall not be applied sooner than seven days after application of the second coat.

above paved areas and shall be of a type that will allow

R703.8 Anchored stone and masonry veneer, general.

trapped water to drain to the exterior of the building.

Anchored stone and masonry veneer shall be installed in

The weather-resistant barrier shall lap the attachment

accordance with this chapter, Table R703.3(1) and Figures

flange. The exterior lath shall cover and terminate on

R703.8(1) and R703.8(2). These veneers installed over a

the attachment flange of the weep screed.

backing of wood or cold-formed steel shall be limited to the

R703.7.3 Water-resistive barriers. Water-resistive barri- first story above grade plane and shall not exceed 5 inches ers shall be installed as required in Section R703.2 and, (127 mm) in thickness. See Section R602.10 for wall bracwhere applied over wood-based sheathing, shall comply ing requirements for masonry veneer for wood-framed

  • with Section R703.7.3.1 or R703.7.3.2. construction and Section R603.9.5 for wall bracing require

7-16 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

ments for masonry veneer for cold-formed steel construction.

Exceptions:

  1. For buildings in Seismic Design Categories A, B and C, exterior stone or masonry veneer, as specified in Table R703.8(1), with a backing of wood or steel framing shall be permitted to the height specified in Table R703.8(1) above a noncombustible foundation.

  2. For detached one- or two-family dwellings in Seismic Design Categories D0, D1 and D2, exterior stone or masonry veneer, as specified in Table R703.8(2), with a backing of wood framing shall be permitted to the height specified in Table R703.8(2) above a noncombustible foundation.

WALL COVERING

R703.8.1 Interior veneer support. Veneers used as interior wall finishes shall be permitted to be supported on wood or cold-formed steel floors that are designed to support the loads imposed. R703.8.2 Exterior veneer support. Except in Seismic Design Categories D0, D1 and D2, exterior masonry veneers having an installed weight of 40 pounds per square foot (195 kg/m 2 ) or less shall be permitted to be supported on wood or cold-formed steel construction. Where masonry veneer supported by wood or cold-formed steel construction adjoins masonry veneer supported by the foundation, there shall be a movement joint between the veneer supported by the wood or cold-formed steel construction and the veneer supported by the foundation. The wood or cold-formed steel construction supporting the masonry veneer shall be designed to limit the deflection to 1/600 of the span for the supporting members. The design of

steel construction adjoins masonry veneer supported by the foundation, there shall be a movement joint between the veneer supported by the wood or cold-formed steel construction and the veneer supported by the foundation. The wood or cold-formed steel construction supporting the masonry veneer shall be designed to limit the deflection to 1/600 of the span for the supporting members. The design of

For SI: 1 inch = 25.4 mm. a. See Sections R703.4, R703.8.5 and R703.8.6. b. See Sections R703.2 and R703.8.4. c. See Table R703.8.4(1) and Section R703.8.4.2. d. Figures R703.8(1) and R703.8(2) illustrate typical construction details for a masonry veneer wall. For the actual mandatory requirements of this code, see the

indicated sections of text. Other details of masonry veneer wall construction shall be permitted provided the requirements of the indicated sections of text are met.

FIGURE R703.8(1) TYPICAL MASONRY VENEER WALL DETAILS d

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

the wood or cold-formed steel construction shall consider the weight of the veneer and any other loads.

R703.8.2.1 Support by steel angle. A minimum 6-inch by 4-inch by 5 /16-inch (152 mm by 102 mm by 8 mm) steel angle, with the long leg placed vertically, shall be anchored to double 2-inch by 4-inch (51 mm by 102 mm) wood studs or double 350S162 cold-formed steel studs at a maximum on-center spacing of 16 inches (406 mm). Anchorage of the steel angle at every double stud spacing shall be not less than two 7 /16-inch-diameter (11 mm) by 4-inch (102 mm) lag screws for wood construction or two 7 /16-inch (11.1 mm) bolts with washers for cold-formed steel construction. The steel angle shall have a minimum clearance to underlying construction of 1/16 inch (1.6 mm). Not less than two-thirds the width of the masonry veneer thickness shall bear on the steel

angle. Flashing and weep holes shall be located in the masonry veneer in accordance with Figure R703.8.2.1. The maximum height of masonry veneer above the steel angle support shall be 12 feet 8 inches (3861 mm). The airspace separating the masonry veneer from the wood backing shall be in accordance with Sections R703.8.4 and R703.8.4.2. The method of support for the masonry veneer on wood construction shall be constructed in accordance with Figure R703.8.2.1.

The maximum slope of the roof construction without stops shall be 7:12. Roof construction with slopes greater than 7:12 but not more than 12:12 shall have stops of a minimum 3-inch by 3-inch by 1 /4-inch (76 mm by 76 mm by 6.4 mm) steel plate welded to the angle at 24 inches (610 mm) on center along the angle or as approved by the building official.

For SI: 1 inch = 25.4 mm. a. See Sections R703.4, R703.8.5 and R703.8.6. b. See Sections R703.2 and R703.8.4. c. See Table R703.8.4(1) and Section R703.8.4.2. d. See Section R703.8.3. e. Figures R703.8(1) and R703.8(2) illustrate typical construction details for a masonry veneer wall. For the actual mandatory requirements of this code, see the

indicated sections of text. Other details of masonry veneer wall construction shall be permitted provided that the requirements of the indicated sections of text are met.

FIGURE R703.8(2) TYPICAL MASONRY VENEER WALL DETAILS e

7-18 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

TABLE R703.8(1) STONE OR MASONRY VENEER LIMITATIONS AND REQUIREMENTS, WOOD OR STEEL FRAMING, SEISMIC DESIGN CATEGORIES A, B AND C

SEISMIC
DESIGN
CATEGORY
NUMBER OF
WOOD- OR STEEL-
FRAMED STORIES
MAXIMUM HEIGHT OF VENEER ABOVE
NONCOMBUSTIBLE FOUNDATIONa
(feet)
MAXIMUM NOMINAL
THICKNESS OF VENEER
(inches)
MAXIMUM
WEIGHT OF VENEER
(psf)b
WOOD- OR
STEEL-FRAMED
STORY
A or B Steel: 1 or 2
Wood: 1, 2 or 3
30 5 50 all
C 1 30 5 50 1 only
C 2 30 5 50 top
C 2 30 5 50 bottom
C Wood only: 3 30 5 50 top
C Wood only: 3 30 5 50 middle
C Wood only: 3 30 5 50 bottom

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.479 kPa. a. An additional 8 feet is permitted for gable end walls. See also story height limitations of Section R301.3. b. Maximum weight is installed weight and includes weight of mortar, grout, lath and other materials used for installation. Where veneer is placed on both faces

of a wall, the combined weight shall not exceed that specified in this table.

TABLE R703.8(2) STONE OR MASONRY VENEER LIMITATIONS AND REQUIREMENTS, ONE- AND TWO-FAMILY DETACHED DWELLINGS, SEISMIC DESIGN CATEGORIES D0, D1 AND D2

SEISMIC DESIGN
CATEGORY
NUMBER OF
WOOD-FRAMED
STORIESa
MAXIMUM HEIGHT OF VENEER ABOVE NONCOMBUSTIBLE
FOUNDATION OR FOUNDATION WALL
(feet)
MAXIMUM NOMINAL
THICKNESS OF VENEER
(inches)
MAXIMUM
WEIGHT OF VENEER
(psf)b
D0 1 20c 4 40
D0 2 20c 4 40
D0 3 30d 4 40
D1 1 20c 4 40
D1 2 20c 4 40
D1 3 20c 4 40
D2 1 20c 3 30
D2 2 20c 3 30

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.479 kPa, 1 pound-force = 4.448 N. a. Cripple walls are not permitted in Seismic Design Categories D0, D1 and D2. b. Maximum weight is installed weight and includes weight of mortar, grout and lath, and other materials used for installation. c. The veneer shall not exceed 20 feet in height above a noncombustible foundation, with an additional 8 feet permitted for gable end walls, or 30 feet in height with

, 1 pound-force = 4.448 N. a. Cripple walls are not permitted in Seismic Design Categories D0, D1 and D2. b. Maximum weight is installed weight and includes weight of mortar, grout and lath, and other materials used for installation. c. The veneer shall not exceed 20 feet in height above a noncombustible foundation, with an additional 8 feet permitted for gable end walls, or 30 feet in height with

an additional 8 feet for gable end walls where the lower 10 feet have a backing of concrete or masonry wall. See story height limitations of Section R301.3. d. The veneer shall not exceed 30 feet in height above a noncombustible foundation, with an additional 8 feet permitted for gable end walls. See story height

limitations of Section R301.3.

R703.8.2.2 Support by roof construction. A steel angle shall be placed directly on top of the roof construction. The roof supporting construction for the steel angle shall consist of not fewer than three 2-inch by 6-inch (51 mm by 152 mm) wood members for wood construction or three 550S162 cold-formed steel members for cold-formed steel light frame construction. A wood member abutting the vertical wall stud construction shall be anchored with not fewer than three 5 /8-inch (15.9 mm) diameter by 5-inch (127 mm) lag screws to every wood stud spacing. Each additional wood roof member shall be anchored by the use of two 10d nails at every wood stud spacing. A coldformed steel member abutting the vertical wall stud shall be anchored with not fewer than nine No. 8 screws to every cold-formed steel stud. Each additional cold-formed steel roof member shall be anchored to the adjoining roof member using two No.

8 screws at every stud spacing. Not less than twothirds the width of the masonry veneer thickness shall bear on the steel angle. Flashing and weep holes shall be located in the masonry veneer wythe in accordance with Figure R703.8.2.2. The maximum height of the masonry veneer above the steel angle support shall be 12 feet 8 inches (3861 mm). The airspace separating the masonry veneer from the wood backing shall be in accordance with Sections R703.8.4 and R703.8.4.2. The support for the masonry veneer shall be constructed in accordance with Figure R703.8.2.2.

The maximum slope of the roof construction without stops shall be 7:12. Roof construction with slopes greater than 7:12 but not more than 12:12 shall have stops of a minimum 3-inch by 3-inch by 1 /4-inch (76 mm by 76 mm by 6.4 mm) steel plate welded to the angle at 24 inches (610 mm) on center along the angle or as approved by the building official.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

FIGURE R703.8.2.1 EXTERIOR MASONRY VENEER SUPPORT BY STEEL ANGLES

FIGURE R703.8.2.2 EXTERIOR MASONRY VENEER SUPPORT BY ROOF MEMBERS

7-20 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

R703.8.3 Lintels. Masonry veneer shall not support any vertical load other than the dead load of the veneer above. Veneer above openings shall be supported on lintels of noncombustible materials. The lintels shall have a length of bearing not less than 4 inches (102 mm). Steel lintels shall be shop coated with a rust-inhibitive paint, except for lintels made of corrosion-resistant steel or steel treated with coatings to provide corrosion resistance. Construction of openings shall comply with either Section R703.8.3.1 or 703.8.3.2.

R703.8.3.1 Allowable span. The allowable span shall not exceed the values set forth in Table R703.8.3.1.

R703.8.3.2 Maximum span. The allowable span shall not exceed 18 feet 3 inches (5562 mm) and shall be constructed to comply with Figure R703.8.3.2 and the following:

  1. Provide a minimum length of 18 inches (457 mm) of masonry veneer on each side of opening as shown in Figure R703.8.3.2.

  2. Provide a minimum 5-inch by 3 1 /2-inch by 5 /16inch (127 mm by 89 mm by 7.9 mm) steel angle above the opening and shore for a minimum of 7 days after installation.

  3. Provide double-wire joint reinforcement extending 12 inches (305 mm) beyond each side of the opening. Lap splices of joint reinforcement not less than 12 inches (305 mm). Comply with one of the following:

3.1. Double-wire joint reinforcement shall be 3 /16-inch (4.8 mm) diameter and shall be placed in the first two bed joints above the opening.

3.2. Double-wire joint reinforcement shall be 9 gauge (0.144 inch or 3.66 mm diameter) and shall be placed in the first three bed joints above the opening.

  1. Provide the height of masonry veneer above opening, in accordance with Table R703.8.3.2.
MINIMUM HEIGHT OF MASONRY
VENEER ABOVE OPENING
(inches)
MAXIMUM HEIGHT OF MASONRY
VENEER ABOVE OPENING
(feet)
13 < 5
24 5 to < 12
60 12 to height above support
allowed by Section R703.8

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

R703.8.4.1 Size and spacing. Veneer ties, if strand wire, shall be not less in thickness than No. 9 U.S. gage

[(0.148 inch) (4 mm)] wire and shall have a hook embedded in the mortar joint, or if sheet metal, shall be not less than No. 22 U.S. gage by [(0.0299 inch) (0.76 mm)] 7 /8 inch (22 mm) corrugated. Each tie shall support not more than 2.67 square feet (0.25 m 2 ) of wall area and shall be spaced not more than 32 inches (813 mm) on center horizontally and 24 inches (635 mm) on center vertically.

m)] wire and shall have a hook embedded in the mortar joint, or if sheet metal, shall be not less than No. 22 U.S. gage by [(0.0299 inch) (0.76 mm)] 7 /8 inch (22 mm) corrugated. Each tie shall support not more than 2.67 square feet (0.25 m 2 ) of wall area and shall be spaced not more than 32 inches (813 mm) on center horizontally and 24 inches (635 mm) on center vertically.

Exception: In Seismic Design Category D0, D1 or D2 or townhouses in Seismic Design Category C or in wind areas of more than 30 pounds per square foot pressure (1.44 kPa), each tie shall support not more than 2 square feet (0.2 m 2 ) of wall area.

R703.8.4.1.1 Veneer ties around wall openings. Additional metal ties shall be provided around wall openings greater than 16 inches (406 mm) in either dimension. Metal ties around the perimeter of openings shall be spaced not more than 3 feet (9144 mm) on center and placed within 12 inches (305 mm) of the wall opening.

R703.8.4.2 Grout fill. As an alternative to the airspace required by Table R703.8.4(1), grout shall be permitted to fill the airspace. Where the airspace is filled with grout, a water-resistive barrier is required over studs or sheathing. Where the airspace is filled, replacing the sheathing and water-resistive barrier with a wire mesh and approved water-resistive barrier or an approved water-resistive barrier-backed reinforcement attached directly to the studs is permitted.

WALL COVERING

TABLE R703.8.3.2 HEIGHT OF MASONRY VENEER ABOVE OPENING

TABLE R703.8.3.1 ALLOWABLE SPANS FOR LINTELS SUPPORTING MASONRY VENEER a, b, c, d

SIZE OF STEEL ANGLEa, c, d
(inches)
NO STORY ABOVE ONE STORY ABOVE TWO STORIES ABOVE NO. OF 1/-INCH OR EQUIVALENT
2
REINFORCING BARS IN REINFORCED LINTELb, d
3 × 3 ×1/4 6′-0″ 4′-6″ 3′-0″ 1
4 × 3 ×1/4 8′-0″ 6′-0″ 4′-6″ 1
5 × 31/2 ×5/16 10′-0″ 8′-0″ 6′-0″ 2
6 × 31/2 ×5/16 14′-0″ 9′-6″ 7′-0″ 2
2-6 × 31/2 ×5/16 20′-0″ 12′-0″ 9′-6″ 4

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm. a. Long leg of the angle shall be placed in a vertical position. b. Depth of reinforced lintels shall be not less than 8 inches and all cells of hollow masonry lintels shall be grouted solid. Reinforcing bars shall extend not less

than 8 inches into the support. c. Steel members indicated are adequate typical examples; other steel members meeting structural design requirements shall be permitted to be used. d. Either steel angle or reinforced lintel shall span opening.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.

FIGURE R703.8.3.2 MASONRY VENEER OPENING

R703.8.5 Flashing. Flashing shall be located beneath the first course of masonry above finished ground level above the foundation wall or slab and at other points of support, including structural floors, shelf angles and lintels where masonry veneers are designed in accordance with Section R703.8. See Section R703.4 for additional requirements.

R703.8.6 Weepholes. Weepholes shall be provided in the outside wythe of masonry walls at a maximum spacing of 33 inches (838 mm) on center. Weepholes shall be not less than 3 /16 inch (5 mm) in diameter. Weepholes shall be located immediately above the flashing.

R703.9 Exterior insulation and finish system (EIFS)/EIFS with drainage.

with drainage. Exterior insulation and finish systems (EIFS) shall comply with this chapter and Section R703.9.1. EIFS with drainage shall comply with this chapter and Section R703.9.2.

R703.9.1 Exterior insulation and finish systems (EIFS). EIFS shall comply with the following:

  1. ASTM E2568.

  2. EIFS shall be limited to applications over substrates of concrete or masonry wall assemblies.

  3. Flashing of EIFS shall be provided in accordance with the requirements of Section R703.4.

  4. EIFS shall be installed in accordance with the manufacturer’s instructions.

  5. EIFS shall terminate not less than 6 inches (152 mm) above the finished ground level.

  6. Decorative trim shall not be face-nailed through the EIFS.

TABLE R703.8.4(1) TIE ATTACHMENT AND AIRSPACE REQUIREMENTS

BACKING AND TIE MINIMUM TIE MINIMUM TIE
FASTENERa
AIRSPACEb
Wood stud backing with
corrugated sheet metal
22 U.S. gage
(0.0299 in.) ×7/8 in. wide
8d common nailc
(21/2 in. × 0.131 in.)
Nominal 1 in. between sheathing and veneer Nominal 1 in. between sheathing and veneer
Wood stud backing with
adjustable metal strand wire
W1.7 (No. 9 U.S. gage;
0.148 in. dia.) with hook
embedded in mortar jointd
8d common nailc
(21/2 in. × 0.131 in.)
Minimum nominal 1 in.
between sheathing and veneer
Maximum 45/8 in. between
backing and veneer
Wood stud backing with
adjustable metal strand wire
W2.8 (0.187 in. dia.)
with hook embedded
in mortar jointe, f
8d common nailc
(21/2 in. × 0.131 in.)
Greater than 45/8 in. between
backing and veneer
Maximum 65/8 in. between
backing and veneer
Cold-formed steel stud
backing with adjustable
metal strand wire
W1.7 (No. 9 U.S. gage;
0.148 in. dia.) with hook
embedded in mortar jointd
No. 10 screw extending
through the steel framing
a minimum of three
exposed threads
Minimum nominal 1 in.
between sheathing and veneer
Maximum 45/8 in. between
backing and veneer
Cold-formed steel stud
backing with adjustable
metal strand wire
W2.8 (0.187 in. dia.)
with hook embedded
in mortar jointe, f
No. 10 screw extending
through the steel framing
a minimum of three
exposed threads
Greater than 45/8 in. between
backing and veneer
Maximum 65/8 in. between
backing and veneer

For SI: 1 inch = 25.4 mm. a. All fasteners shall have rust-inhibitive coating suitable for the installation in which they are being used, or be manufactured from material not susceptible to

corrosion. b. An airspace that provides drainage shall be permitted to contain mortar from construction. c. In Seismic Design Category D0, D1 or D2, the minimum tie fastener shall be an 8d ring-shank nail (2 1 /2 in. × 0.131 in.). d. Adjustable tie pintles shall include not fewer than 1 pintle leg of wire size W2.8 (MW18) with a maximum offset of 1 1 /4 inches. e. Adjustable tie pintles shall include not fewer than 2 pintle legs with a maximum offset of 1 1 /4 inches. Distance between inside face of brick and end of pintle

shall be a maximum of 2 inches. f. Adjustable tie backing attachment components shall consist of one of the following: eyes with minimum wire W2.8 (MW18), barrel with minimum 1 /4-inch

outside diameter, or plate with minimum thickness of 0.074 inch and minimum width of 1 1 /4 inches.

7-22 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

REQUIRED BRICK-TIE SPACING (VERTICAL-TIE SPACING/HORIZONTAL-TIE SPACING) (inches/inches) 140 mph V ult Zone 5, Exposure D 12/12 12/12 16/12, 12/16, 12/12 16/12, 12/16, 12/12 16/16, 16/12, 12/16, 12/12
REQUIRED BRICK-TIE SPACING (VERTICAL-TIE SPACING/HORIZONTAL-TIE SPACING) (inches/inches) 140 mphVult Zone 5,
Exposure C
16/12,
12/16,
12/12
16/12,
12/16,
12/12
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
REQUIRED BRICK-TIE SPACING (VERTICAL-TIE SPACING/HORIZONTAL-TIE SPACING) (inches/inches) 140 mphVult Zone 5,
Exposure B
12/12 16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
REQUIRED BRICK-TIE SPACING (VERTICAL-TIE SPACING/HORIZONTAL-TIE SPACING) (inches/inches) 130 mphVult Zone 5,
Exposure D
16/12,
12/16,
12/12
16/12,
12/16,
12/12
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
REQUIRED BRICK-TIE SPACING (VERTICAL-TIE SPACING/HORIZONTAL-TIE SPACING) (inches/inches) 130 mphVult Zone 5,
Exposure C
12/12 16/12,
12/16,
12/12
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
REQUIRED BRICK-TIE SPACING (VERTICAL-TIE SPACING/HORIZONTAL-TIE SPACING) (inches/inches) 130 mphVult Zone 5,
Exposure B
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
REQUIRED BRICK-TIE SPACING (VERTICAL-TIE SPACING/HORIZONTAL-TIE SPACING) (inches/inches) 115 mphVult Zone 5,
Exposure D
12/12 16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
REQUIRED BRICK-TIE SPACING (VERTICAL-TIE SPACING/HORIZONTAL-TIE SPACING) (inches/inches) 115 mphVult Zone 5,
Exposure C
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
REQUIRED BRICK-TIE SPACING (VERTICAL-TIE SPACING/HORIZONTAL-TIE SPACING) (inches/inches) 115 mphVult Zone 5,
Exposure B
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
REQUIRED BRICK-TIE SPACING (VERTICAL-TIE SPACING/HORIZONTAL-TIE SPACING) (inches/inches) 110 mphVult Zone 5,
Exposure D
12/12 16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
REQUIRED BRICK-TIE SPACING (VERTICAL-TIE SPACING/HORIZONTAL-TIE SPACING) (inches/inches) 110 mphVult Zone 5,
Exposure C
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
REQUIRED BRICK-TIE SPACING (VERTICAL-TIE SPACING/HORIZONTAL-TIE SPACING) (inches/inches) 110 mphVult Zone 5,
Exposure B
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
24/16,
16/24,
16/16,
16/12,
12/16,
12/12
SIZE
(DIA. OR SCREW #)
SIZE
(DIA. OR SCREW #)
SIZE
(DIA. OR SCREW #)
0.091 0.148 #6 #8 #10 #14
FASTENER
TYPEd
FASTENER
TYPEd
FASTENER
TYPEd
Ring
Shank
Nails
Ring
Shank
Nails
Screws Screws Screws Screws

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

R703.9.2 Exterior insulation and finish system (EIFS) with drainage. EIFS with drainage shall comply with the following:

  1. ASTM E2568.

  2. EIFS with drainage shall be required over all wall assemblies with the exception of substrates of concrete or masonry wall assemblies.

  3. EIFS with drainage shall have an average minimum drainage efficiency of 90 percent when tested in accordance with ASTM E2273.

  4. The water-resistive barrier shall comply with Section R703.2 or ASTM E2570.

  5. The water-resistive barrier shall be applied between the EIFS and the wall sheathing.

  6. Flashing of EIFS with drainage shall be provided in accordance with the requirements of Section R703.4.

  7. EIFS with drainage shall be installed in accordance with the manufacturer’s instructions.

  8. EIFS with drainage shall terminate not less than 6 inches (152 mm) above the finished ground level.

  9. Decorative trim shall not be face-nailed through the EIFS with drainage.

R703.10 Fiber cement siding.

R703.10.1 Panel siding. Fiber-cement panels shall comply with the requirements of ASTM C1186, Type A, minimum Grade II or ISO 8336, Category A, minimum Class 2. Panels shall be installed with the long dimension either parallel or perpendicular to framing. Vertical and horizontal joints shall occur over framing members and shall be protected with caulking, or with battens or flashing, or be vertical or horizontal shiplap, or otherwise designed to comply with Section R703.1. Panel siding shall be installed with fasteners in accordance with Table R703.3(1) or the approved manufacturer’s instructions.

R703.10.2 Lap siding. Fiber-cement lap siding having a maximum width of 12 inches (305 mm) shall comply with the requirements of ASTM C1186, Type A, minimum Grade II or ISO 8336, Category A, minimum Class 2. Lap siding shall be lapped a minimum of 1 1 /4 inches (32 mm) and lap siding not having tongue-and-groove end joints shall have the ends protected with caulking, covered with an H-section joint cover, located over a strip of flashing, or shall be designed to comply with Section R703.1. Lap siding courses shall be installed with the fastener heads exposed or concealed, in accordance with Table R703.3(1) or approved manufacturer’s instructions.

R703.11 Vinyl siding.

Vinyl siding shall be certified and labeled as conforming to the requirements of ASTM D3679 by an approved quality control agency.

R703.11.1 Installation. Vinyl siding, soffit and accessories shall be installed in accordance with the manufacturer’s instructions.

R703.11.1.1 Fasteners. Unless specified otherwise by the manufacturer’s instructions, fasteners for vinyl

siding shall be 0.120-inch (3 mm) shank diameter nail with a 0.313-inch (8 mm) head or 16-gage staple with a 3/8-inch (9.5 mm) to 1/2-inch (12.7 mm) crown.

R703.11.1.2 Penetration depth. Unless specified otherwise by the manufacturer’s instructions, fasteners shall penetrate into building framing. The total penetration into sheathing, furring framing or other nailable substrate shall be a minimum 1 1 /4 inches (32 mm). Where specified by the manufacturer’s instructions and supported by a test report, fasteners are permitted to penetrate into or fully through nailable sheathing or other nailable substrate of minimum thickness specified by the instructions or test report without penetrating into framing. Where the fastener penetrates fully through the sheathing, the end of the fastener shall extend a minimum of 1 /4 inch (6.4 mm) beyond the opposite face of the sheathing or nailable substrate.

R703.11.1.3 Spacing. Unless specified otherwise by the manufacturer’s instructions, the maximum spacing between fasteners for horizontal siding shall be 16 inches (406 mm), and for vertical siding 12 inches (305 mm) both horizontally and vertically. Where specified by the manufacturer’s instructions and supported by a test report, greater fastener spacing is permitted.

R703.11.2 Installation over foam plastic sheathing. Where vinyl siding or insulated vinyl siding is installed over foam plastic sheathing, the vinyl siding shall comply with Section R703.11 and shall have a wind load design pressure rating in accordance with Table R703.11.2.

Exceptions:

  1. Where the foam plastic sheathing is applied directly over wood structural panels, fiberboard, gypsum sheathing or other approved backing capable of independently resisting the design wind pressure, the vinyl siding shall be installed in accordance with Sections R703.3.3 and R703.11.1.

  2. Where the vinyl siding manufacturer’s product specifications provide an approved wind load design pressure rating for installation over foam plastic sheathing, use of this wind load design pressure rating shall be permitted and the siding shall be installed in accordance with the manufacturer’s installation instructions.

  3. Where the foam plastic sheathing and its attachment have a design wind pressure resistance complying with Sections R316.8 and R301.2.1, the vinyl siding shall be installed in accordance with Sections R703.3.3 and R703.11.1.

R703.12 Adhered masonry veneer installation.

Adhered masonry veneer shall comply with the requirements of Section R703.7.3 and the requirements in Sections 12.1 and 12.3 of TMS 402. Adhered masonry veneer shall be installed in accordance with Section R703.7.1, Article 3.3C of TMS 602 or the manufacturer’s instructions.

7-24 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

TABLE R703.11.2 REQUIRED MINIMUM WIND LOAD DESIGN PRESSURE RATING FOR VINYL SIDING INSTALLED OVER FOAM PLASTIC SHEATHING ALONE

ULTIMATE DESIGN WIND SPEED
(MPH)
ADJUSTED MINIMUM DESIGN WIND PRESSURE (ASD) (PSF)a, b
ULTIMATE DESIGN WIND SPEED
(MPH)
Case 1: With interior gypsum wallboardc Case 1: With interior gypsum wallboardc Case 1: With interior gypsum wallboardc Case 2: Without interior gypsum wallboardc Case 2: Without interior gypsum wallboardc Case 2: Without interior gypsum wallboardc
ULTIMATE DESIGN WIND SPEED
(MPH)
Exposure Exposure Exposure Exposure Exposure Exposure
ULTIMATE DESIGN WIND SPEED
(MPH)
B C D B C D
≤ 95 -30.0 -33.2 -39.4 -33.9 -47.4 -56.2
100 -30.0 -36.8 -43.6 -37.2 -52.5 -62.2
105 -30.0 -40.5 -48.1 -41.4 -57.9 -68.6
110 -31.8 -44.5 -52.8 -45.4 -63.5 -75.3
115 -35.5 -49.7 -59.0 -50.7 -71.0 -84.2
120 -37.4 -52.4 -62.1 -53.4 -74.8 -88.6
130 -44.9 -62.8 -74.5 -64.1 -89.7 -106
> 130 See Note d See Note d See Note d See Note d See Note d See Note d

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square foot = 0.0929 m 2, 1 mile per hour = 0.447 m/s, 1 pound per square foot = 0.0479 kPa. a. Linear interpolation is permitted. b. The table values are based on a maximum 30-foot mean roof height, and effective wind area of 10 square feet Wall Zone 5 (corner), and the ASD design

component and cladding wind pressure from Table R301.2.1(1), adjusted for exposure in accordance with Table R301.2.1(2), multiplied by the following adjustment factors: 1.87 (Case 1) and 2.67 (Case 2). c. Gypsum wallboard, gypsum panel product or equivalent. d. For the indicated wind speed condition and where foam sheathing is the only sheathing on the exterior of a frame wall with vinyl siding, the wall assembly

shall be capable of resisting an impact without puncture at least equivalent to that of a wood frame wall with minimum 7 /16-inch OSB sheathing as tested in accordance with ASTM E1886. The vinyl siding shall comply with an adjusted design wind pressure requirement in accordance with Note b, using an adjustment factor of 2.67.

R703.12.1 Clearances. On exterior stud walls, adhered masonry veneer shall be installed:

  1. Minimum of 4 inches (102 mm) above the earth;
  2. Minimum of 2 inches (51 mm) above paved areas; or
  3. Minimum of 1 /2 inch (12.7 mm) above exterior walking surfaces that are supported by the same foundation that supports the exterior wall. R703.12.2 Flashing at foundation. A corrosion-resistant screed or flashing of a minimum 0.019-inch (0.48 mm) or 26gage galvanized or plastic with a minimum vertical attachment flange of 3 1 /2 inches (89 mm) shall be installed to extend a minimum of 1 inch (25 mm) below the foundation plate line on exterior stud walls in accordance with Section R703.4. R703.12.3 Water-resistive barrier. A water-resistive barrier shall be installed as required by Section R703.2 and shall comply with the requirements of Section R703.7.3. The water-resistive barrier shall lap over the exterior of the attachment flange of the screed or flashing provided in accordance with Section R703.12.2.

R703.13 Insulated vinyl siding.

Insulated vinyl siding shall be certified and labeled as conforming to the requirements of ASTM D7793 by an approved quality control agency.

R703.13.1 Insulated vinyl siding and accessories. Insulated vinyl siding and accessories shall be installed in accordance with the manufacturer’s installation instructions.

R703.14 Polypropylene siding.

Polypropylene siding shall be certified and labeled as conforming to the requirements of ASTM D7254, and those of Section R703.14.2 or Section R703.14.3, by an approved quality control agency.

R703.14.1 Polypropylene siding and accessories. Polypropylene siding and accessories shall be installed in accordance with manufacturer’s installation instructions.

R703.14.1.1 Installation. Polypropylene siding shall be installed over and attached to wood structural panel sheathing with minimum thickness of 7 /16 inch (11.1 mm), or other substrate, composed of wood or woodbased material and fasteners having equivalent withdrawal resistance. R703.14.1.2 Fastener requirements. Unless otherwise specified in the approved manufacturer’s instructions, nails shall be corrosion resistant, with a minimum 0.120-inch (3 mm) shank and minimum 0.313-inch (8 mm) head diameter. Nails shall be a minimum of 1 1 /4 inches (32 mm) long or as necessary to penetrate sheathing or substrate not less than 3 /4 inch (19.1 mm). Where the nail fully penetrates the sheathing or nailable substrate, the end of the fastener shall extend not less than 1 /4 inch (6.4 mm) beyond the opposite face of the sheathing or substrate. Staples are not permitted. R703.14.2 Fire separation. Polypropylene siding shall not be installed on walls with a fire separation distance of less than 5 feet (1524 mm) and walls closer than 10 feet (3048 mm) to a building on another lot.

Exception: Walls perpendicular to the line used to determine the fire separation distance. R703.14.3 Flame spread index. The certification of the flame spread index shall be accompanied by a test report stating that all portions of the test specimen ahead of the flame front remained in position during the test in accordance with ASTM E84 or UL 723.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

R703.15 Cladding attachment over foam sheathing to wood framing.

wood framing. Cladding shall be specified and installed in accordance with Section R703, the cladding manufacturer’s approved instructions, including any limitations for use over foam plastic sheathing, or an approved design. In addition, the cladding or furring attachments through foam sheathing to framing shall meet or exceed the minimum fastening requirements of Section R703.15.1, Section R703.15.2, or an approved design for support of cladding weight.

Exceptions:

  1. Where the cladding manufacturer has provided approved installation instructions for application over foam sheathing, those requirements shall apply.

  2. For exterior insulation and finish systems, refer to Section R703.9.

  3. For anchored masonry or stone veneer installed over foam sheathing, refer to Section R703.8.

R703.15.1 Direct attachment. Where cladding is installed directly over foam sheathing without the use of furring, cladding minimum fastening requirements to support the cladding weight shall be as specified in Table R703.15.1.

R703.15.2 Furred cladding attachment. Where wood furring is used to attach cladding over foam sheathing, furring minimum fastening requirements to support the

cladding weight shall be as specified in Table R703.15.2. Where placed horizontally, wood furring shall be preservative-treated wood in accordance with Section R317.1 or naturally durable wood and fasteners shall be corrosion resistant in accordance Section R317.3.

R703.16 Cladding attachment over foam sheathing to cold-formed steel framing.

cold-formed steel framing. Cladding shall be specified and installed in accordance with Section R703, the cladding manufacturer’s approved instructions, including any limitations for use over foam plastic sheathing, or an approved design. In addition, the cladding or furring attachments through foam sheathing to framing shall meet or exceed the minimum fastening requirements of Section R703.16.1, Section R703.16.2 or an approved design for support of cladding weight.

Exceptions:

  1. Where the cladding manufacturer has provided approved installation instructions for application over foam sheathing, those requirements shall apply.

  2. For exterior insulation and finish systems, refer to Section R703.9.

  3. For anchored masonry or stone veneer installed over foam sheathing, refer to Section R703.8.

TABLE R703.15.1 CLADDING MINIMUM FASTENING REQUIREMENTS FOR DIRECT ATTACHMENT OVER FOAM PLASTIC SHEATHING TO SUPPORT CLADDING WEIGHT a

CLADDING
FASTENER
THROUGH FOAM
SHEATHINGb
CLADDING
FASTENER TYPE
AND MINIMUM SIZEc
CLADDING
FASTENER
VERTICAL
SPACING
(inches)
MAXIMUM THICKNESS OF FOAM SHEATHINGd (inches)
CLADDING
FASTENER
THROUGH FOAM
SHEATHINGb
CLADDING
FASTENER TYPE
AND MINIMUM SIZEc
CLADDING
FASTENER
VERTICAL
SPACING
(inches)
16″ o.c. Fastener Horizontal Spacing 16″ o.c. Fastener Horizontal Spacing 16″ o.c. Fastener Horizontal Spacing 16″ o.c. Fastener Horizontal Spacing 16″ o.c. Fastener Horizontal Spacing 24″ o.c. Fastener Horizontal Spacing 24″ o.c. Fastener Horizontal Spacing 24″ o.c. Fastener Horizontal Spacing 24″ o.c. Fastener Horizontal Spacing 24″ o.c. Fastener Horizontal Spacing
CLADDING
FASTENER
THROUGH FOAM
SHEATHINGb
CLADDING
FASTENER TYPE
AND MINIMUM SIZEc
CLADDING
FASTENER
VERTICAL
SPACING
(inches)
Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight:
CLADDING
FASTENER
THROUGH FOAM
SHEATHINGb
CLADDING
FASTENER TYPE
AND MINIMUM SIZEc
CLADDING
FASTENER
VERTICAL
SPACING
(inches)
3 psf 11 psf 15 psf 18 psf 25 psf 3 psf 11 psf 15 psf 18 psf 25 psf
Wood framing
(minimum 11/4-
inch penetration)
0.113″
diameter nail
6 2.00 1.45 1.00 0.75 DR 2.00 0.85 0.55 DR DR
Wood framing
(minimum 11/4-
inch penetration)
0.113″
diameter nail
8 2.00 1.00 0.65 DR DR 2.00 0.55 DR DR DR
Wood framing
(minimum 11/4-
inch penetration)
0.113″
diameter nail
12 2.00 0.55 DR DR DR 1.85 DR DR DR DR
Wood framing
(minimum 11/4-
inch penetration)
0.120″
diamete rnail
6 3.00 1.70 1.15 0.90 0.55 3.00 1.05 0.65 0.50 DR
Wood framing
(minimum 11/4-
inch penetration)
0.120″
diamete rnail
8 3.00 1.20 0.80 0.60 DR 3.00 0.70 DR DR DR
Wood framing
(minimum 11/4-
inch penetration)
0.120″
diamete rnail
12 3.00 0.70 DR DR DR 2.15 DR DR DR DR
Wood framing
(minimum 11/4-
inch penetration)
0.131″
diameter nail
6 4.00 2.15 1.50 1.20 0.75 4.00 1.35 0.90 0.70 DR
Wood framing
(minimum 11/4-
inch penetration)
0.131″
diameter nail
8 4.00 1.55 1.05 0.80 DR 4.00 0.90 0.55 DR DR
Wood framing
(minimum 11/4-
inch penetration)
0.131″
diameter nail
12 4.00 0.90 0.55 DR DR 2.70 0.50 DR DR DR
Wood framing
(minimum 11/4-
inch penetration)
0.162″
diameter nail
6 4.00 3.55 2.50 2.05 1.40 4.00 2.25 1.55 1.25 0.80
Wood framing
(minimum 11/4-
inch penetration)
0.162″
diameter nail
8 4.00 2.55 1.80 1.45 0.95 4.00 1.60 1.10 0.85 0.50
Wood framing
(minimum 11/4-
inch penetration)
0.162″
diameter nail
12 4.00 1.60 1.10 0.85 0.50 4.00 0.95 0.60 DR DR

For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa. DR = Design Required. o.c. = On Center. a. Wood framing shall be Spruce-pine-fir or any wood species with a specific gravity of 0.42 or greater in accordance with AWC NDS. b. The thickness of wood structural panels complying with the specific gravity requirement of Note a shall be permitted to be included in satisfying the minimum

penetration into framing. For cladding connections to wood structural panels, refer to Table R703.3.3. For brick veneer tie connections to wood structural panels, refer to Table R703.8.4(2). c. Nail fasteners shall comply with ASTM F1667, except nail length shall be permitted to exceed ASTM F1667 standard lengths. d. Foam sheathing shall have a minimum compressive strength of 15 psi in accordance with ASTM C578 or ASTM C1289.

7-26 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

TABLE R703.15.2 FURRING MINIMUM FASTENING REQUIREMENTS FOR APPLICATION OVER FOAM PLASTIC SHEATHING TO SUPPORT CLADDING WEIGHT a, b

FURRING
MATERIAL
FRAMING
MEMBER
FASTENER
TYPE AND
MINIMUM
SIZE
MINIMUM
PENETRATION
INTO WALL
FRAMING
(inches)c
FASTENER
SPACING IN
FURRING
(inches)
MAXIMUM THICKNESS OF FOAM SHEATHINGe (inches)
FURRING
MATERIAL
FRAMING
MEMBER
FASTENER
TYPE AND
MINIMUM
SIZE
MINIMUM
PENETRATION
INTO WALL
FRAMING
(inches)c
FASTENER
SPACING IN
FURRING
(inches)
16″ o.c. Furringf 16″ o.c. Furringf 16″ o.c. Furringf 16″ o.c. Furringf 16″ o.c. Furringf 24″ o.c. Furringf 24″ o.c. Furringf 24″ o.c. Furringf 24″ o.c. Furringf 24″ o.c. Furringf
FURRING
MATERIAL
FRAMING
MEMBER
FASTENER
TYPE AND
MINIMUM
SIZE
MINIMUM
PENETRATION
INTO WALL
FRAMING
(inches)c
FASTENER
SPACING IN
FURRING
(inches)
Siding Weight: Siding Weight: Siding Weight: Siding Weight: Siding Weight: Siding Weight: Siding Weight: Siding Weight: Siding Weight: Siding Weight:
FURRING
MATERIAL
FRAMING
MEMBER
FASTENER
TYPE AND
MINIMUM
SIZE
MINIMUM
PENETRATION
INTO WALL
FRAMING
(inches)c
FASTENER
SPACING IN
FURRING
(inches)
3 psf 11 psf 15 psf 18 psf 25 psf 3 psf 11 psf 15 psf 18 psf 25 psf
Minimum
1× wood
furringd
Minimum
2× wood
stud
0.131″
diameter
nail
11/4 8 4.00 2.45 1.75 1.45 0.95 4.00 1.60 1.10 0.85 DR
Minimum
1× wood
furringd
Minimum
2× wood
stud
0.131″
diameter
nail
11/4 12 4.00 1.60 1.10 0.85 DR 4.00 0.95 0.55 DR DR
Minimum
1× wood
furringd
Minimum
2× wood
stud
0.131″
diameter
nail
11/4 16 4.00 1.10 0.70 DR DR 3.05 0.60 DR DR DR
Minimum
1× wood
furringd
Minimum
2× wood
stud
0.162″
diameter
nail
11/4 8 4.00 4.00 3.05 2.45 1.60 4.00 2.75 1.85 1.45 0.85
Minimum
1× wood
furringd
Minimum
2× wood
stud
0.162″
diameter
nail
11/4 12 4.00 2.75 1.85 1.45 0.85 4.00 1.65 1.05 0.75 DR
Minimum
1× wood
furringd
Minimum
2× wood
stud
0.162″
diameter
nail
11/4 16 4.00 1.90 1.25 0.95 DR 4.00 1.05 0.60 DR DR
Minimum
1× wood
furringd
Minimum
2× wood
stud
No.10
wood
screw
1 12 4.00 2.30 1.60 1.20 0.70 4.00 1.40 0.85 0.60 DR
Minimum
1× wood
furringd
Minimum
2× wood
stud
No.10
wood
screw
1 16 4.00 1.65 1.05 0.75 DR 4.00 0.90 DR DR DR
Minimum
1× wood
furringd
Minimum
2× wood
stud
No.10
wood
screw
1 24 4.00 0.90 DR DR DR 2.85 DR DR DR DR
Minimum
1× wood
furringd
Minimum
2× wood
stud
1/4″ lag
screw
11/2 12 4.00 2.65 1.90 1.50 0.90 4.00 1.65 1.05 0.80 DR
Minimum
1× wood
furringd
Minimum
2× wood
stud
1/4″ lag
screw
11/2 16 4.00 1.95 1.25 0.95 0.50 4.00 1.10 0.65 DR DR
Minimum
1× wood
furringd
Minimum
2× wood
stud
1/4″ lag
screw
11/2 24 4.00 1.10 0.65 DR DR 3.25 0.50 DR DR DR

For SI: 1 inch = 25.4 mm, 1 pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa. DR = Design Required. o.c. = On Center. a. Wood framing and furring shall be Spruce-pine-fir or any wood species with a specific gravity of 0.42 or greater in accordance with AWC NDS. b. Nail fasteners shall comply with ASTM F1667, except nail length shall be permitted to exceed ASTM F1667 standard lengths. c. The thickness of wood structural panels complying with the specific gravity requirements of Note a shall be permitted to be included in satisfying the

minimum required penetration into framing. d. Where the required cladding fastener penetration into wood material exceeds 3 /4 inch and is not more than 1 1 /2 inches, a minimum 2× wood furring or an

approved design shall be used. e. Foam sheathing shall have a minimum compressive strength of 15 psi in accordance with ASTM C578 or ASTM C1289. f. Furring shall be spaced not more than 24 inches on center, in a vertical or horizontal orientation. In a vertical orientation, furring shall be located over wall

studs and attached with the required fastener spacing. In a horizontal orientation, the indicated 8-inch and 12-inch fastener spacing in furring shall be achieved by use of two fasteners into studs at 16 inches and 24 inches on center, respectively.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

WALL COVERING

TABLE R703.16.1 CLADDING MINIMUM FASTENING REQUIREMENTS FOR DIRECT ATTACHMENT OVER FOAM PLASTIC SHEATHING TO SUPPORT CLADDING WEIGHT a, b

CLADDING
FASTENER THROUGH FOAM
SHEATHING INTO:
CLADDING
FASTENER TYPE
AND MINIMUM SIZEc
CLADDING
FASTENER
VERTICAL
SPACING
(inches)
MAXIMUM THICKNESS OF FOAM SHEATHINGd (inches)
CLADDING
FASTENER THROUGH FOAM
SHEATHING INTO:
CLADDING
FASTENER TYPE
AND MINIMUM SIZEc
CLADDING
FASTENER
VERTICAL
SPACING
(inches)
16″ o.c. Fastener Horizontal Spacing 16″ o.c. Fastener Horizontal Spacing 16″ o.c. Fastener Horizontal Spacing 16″ o.c. Fastener Horizontal Spacing 16″ o.c. Fastener Horizontal Spacing 24″ o.c. Fastener Horizontal Spacing 24″ o.c. Fastener Horizontal Spacing 24″ o.c. Fastener Horizontal Spacing 24″ o.c. Fastener Horizontal Spacing 24″ o.c. Fastener Horizontal Spacing
CLADDING
FASTENER THROUGH FOAM
SHEATHING INTO:
CLADDING
FASTENER TYPE
AND MINIMUM SIZEc
CLADDING
FASTENER
VERTICAL
SPACING
(inches)
Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight:
CLADDING
FASTENER THROUGH FOAM
SHEATHING INTO:
CLADDING
FASTENER TYPE
AND MINIMUM SIZEc
CLADDING
FASTENER
VERTICAL
SPACING
(inches)
3 psf 11 psf 15 psf 18 psf 25 psf 3 psf 11 psf 15 psf 18 psf 25 psf
Steel framing
(minimum penetration of
steel thickness + 3 threads)
No. 8 screw into
33-mil steel or
thicker
6 3.00 2.95 2.50 2.20 1.45 3.00 2.35 1.75 1.25 DR
Steel framing
(minimum penetration of
steel thickness + 3 threads)
No. 8 screw into
33-mil steel or
thicker
8 3.00 2.55 2.00 1.60 0.60 3.00 1.80 0.90 DR DR
Steel framing
(minimum penetration of
steel thickness + 3 threads)
No. 8 screw into
33-mil steel or
thicker
12 3.00 1.80 0.95 DR DR 3.00 0.65 DR DR DR
Steel framing
(minimum penetration of
steel thickness + 3 threads)
No. 10 screw into
33-mil steel
6 4.00 3.50 3.05 2.70 1.95 4.00 2.90 2.20 1.70 0.55
Steel framing
(minimum penetration of
steel thickness + 3 threads)
No. 10 screw into
33-mil steel
8 4.00 3.10 2.50 2.05 1.00 4.00 2.25 1.35 0.70 DR
Steel framing
(minimum penetration of
steel thickness + 3 threads)
No. 10 screw into
33-mil steel
12 4.00 2.25 1.35 0.70 DR 3.70 1.05 DR DR DR
Steel framing
(minimum penetration of
steel thickness + 3 threads)
No. 10 screw into
43-mil steel or
thicker
6 4.00 4.00 4.00 4.00 3.60 4.00 4.00 3.80 3.45 2.70
Steel framing
(minimum penetration of
steel thickness + 3 threads)
No. 10 screw into
43-mil steel or
thicker
8 4.00 4.00 4.00 3.70 3.00 4.00 3.85 3.25 2.80 1.80
Steel framing
(minimum penetration of
steel thickness + 3 threads)
No. 10 screw into
43-mil steel or
thicker
12 4.00 3.85 3.25 2.80 1.80 4.00 3.05 2.15 1.50 DR

For SI: 1 inch = 25.4 mm, 1 mil = 0.0254 mm, 1 pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa. DR = Design Required. o.c. = On Center. a. Steel framing shall be minimum 33-ksi steel for 33-mil and 43-mil steel, and 50-ksi steel for 54-mil steel or thicker. b. Where cladding is attached to wood structural panel sheathing only, fastening requirements shall be in accordance with Table R703.3.3. c. Screws shall comply with the requirements of ASTM C1513. d. Foam sheathing shall have a minimum compressive strength of 15 psi in accordance with ASTM C578 or ASTM C1289.

TABLE R703.16.2 FURRING MINIMUM FASTENING REQUIREMENTS FOR APPLICATION OVER FOAM PLASTIC SHEATHING TO SUPPORT CLADDING WEIGHT a

FURRING
MATERIAL
FRAMING
MEMBER
FASTENER
TYPE AND
MINIMUM
SIZEb
MINIMUM
PENETRATION
INTO WALL
FRAMING
(inches)
FASTENER
SPACING IN
FURRING
(inches)
MAXIMUM THICKNESS OF FOAM SHEATHINGd (inches)
FURRING
MATERIAL
FRAMING
MEMBER
FASTENER
TYPE AND
MINIMUM
SIZEb
MINIMUM
PENETRATION
INTO WALL
FRAMING
(inches)
FASTENER
SPACING IN
FURRING
(inches)
16″ o.c. Furringe 16″ o.c. Furringe 16″ o.c. Furringe 16″ o.c. Furringe 16″ o.c. Furringe 24″ o.c. Furringe 24″ o.c. Furringe 24″ o.c. Furringe 24″ o.c. Furringe 24″ o.c. Furringe
FURRING
MATERIAL
FRAMING
MEMBER
FASTENER
TYPE AND
MINIMUM
SIZEb
MINIMUM
PENETRATION
INTO WALL
FRAMING
(inches)
FASTENER
SPACING IN
FURRING
(inches)
Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight: Cladding Weight:
FURRING
MATERIAL
FRAMING
MEMBER
FASTENER
TYPE AND
MINIMUM
SIZEb
MINIMUM
PENETRATION
INTO WALL
FRAMING
(inches)
FASTENER
SPACING IN
FURRING
(inches)
3 psf 11 psf 15 psf 18 psf 25 psf 3 psf 11 psf 15 psf 18 psf 25 psf
Minimum
33-mil steel
furring or
minimum
1× wood
furringc
33-mil
steel stud
No. 8
screw
Steel thickness
+ 3 threads
12 3.00 1.80 0.95 DR DR 3.00 0.65 DR DR DR
Minimum
33-mil steel
furring or
minimum
1× wood
furringc
33-mil
steel stud
No. 8
screw
Steel thickness
+ 3 threads
16 3.00 1.00 DR DR DR 2.85 DR DR DR DR
Minimum
33-mil steel
furring or
minimum
1× wood
furringc
33-mil
steel stud
No. 8
screw
Steel thickness
+ 3 threads
24 2.85 DR DR DR DR 2.20 DR DR DR DR
Minimum
33-mil steel
furring or
minimum
1× wood
furringc
33-mil
steel stud
No. 10
screw
Steel thickness
+ 3 threads
12 4.00 2.25 1.35 0.70 DR 3.70 1.05 DR DR DR
Minimum
33-mil steel
furring or
minimum
1× wood
furringc
33-mil
steel stud
No. 10
screw
Steel thickness
+ 3 threads
16 3.85 1.45 DR DR DR 3.40 DR DR DR DR
Minimum
33-mil steel
furring or
minimum
1× wood
furringc
33-mil
steel stud
No. 10
screw
Steel thickness
+ 3 threads
24 3.40 DR DR DR DR 2.70 DR DR DR DR
Minimum
33-mil steel
furring or
minimum
1× wood
furringc
43-mil
or thicker
steel stud
No. 8
Screw
Steel thickness
+ 3 threads
12 3.00 1.80 0.95 DR DR 3.00 0.65 DR DR DR
Minimum
33-mil steel
furring or
minimum
1× wood
furringc
43-mil
or thicker
steel stud
No. 8
Screw
Steel thickness
+ 3 threads
16 3.00 1.00 DR DR DR 2.85 DR DR DR DR
Minimum
33-mil steel
furring or
minimum
1× wood
furringc
43-mil
or thicker
steel stud
No. 8
Screw
Steel thickness
+ 3 threads
24 2.85 DR DR DR DR 2.20 DR DR DR DR
Minimum
33-mil steel
furring or
minimum
1× wood
furringc
43-mil
or thicker
steel stud
No. 10
screw
Steel thickness
+ 3 threads
12 4.00 3.85 3.25 2.80 1.80 4.00 3.05 2.15 1.50 DR
Minimum
33-mil steel
furring or
minimum
1× wood
furringc
43-mil
or thicker
steel stud
No. 10
screw
Steel thickness
+ 3 threads
16 4.00 3.30 2.55 1.95 0.60 4.00 2.25 1.05 DR DR
Minimum
33-mil steel
furring or
minimum
1× wood
furringc
43-mil
or thicker
steel stud
No. 10
screw
Steel thickness
+ 3 threads
24 4.00 2.25 1.05 DR DR 4.00 0.65 DR DR DR

For SI: 1 inch = 25.4 mm, 1 mil = 0.0254 mm, 1 pound per square foot = 0.0479 kPa, 1 pound per square inch = 6.895 kPa. DR = Design Required. o.c. = On Center. a. Wood furring shall be Spruce-pine-fir or any softwood species with a specific gravity of 0.42 or greater. Steel furring shall be minimum 33-ksi steel. Steel

studs shall be minimum 33-ksi steel for 33-mil and 43-mil thickness, and 50-ksi steel for 54-mil steel or thicker. b. Screws shall comply with the requirements of ASTM C1513. c. Where the required cladding fastener penetration into wood material exceeds 3 /4 inch and is not more than 1 1 /2 inches, a minimum 2-inch nominal wood furring

or an approved design shall be used. d. Foam sheathing shall have a minimum compressive strength of 15 psi in accordance with ASTM C578 or ASTM C1289. e. Furring shall be spaced not more than 24 inches (610 mm) on center, in a vertical or horizontal orientation. In a vertical orientation, furring shall be located

over wall studs and attached with the required fastener spacing. In a horizontal orientation, the indicated 8-inch and 12-inch fastener spacing in furring shall be achieved by use of two fasteners into studs at 16 inches and 24 inches on center, respectively.

7-28 2022 CALIFORNIA RESIDENTIAL CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

R703.16.1 Direct attachment. Where cladding is installed directly over foam sheathing without the use of furring, cladding minimum fastening requirements to support the cladding weight shall be as specified in Table R703.16.1. R703.16.2 Furred cladding attachment. Where steel or wood furring is used to attach cladding over foam sheathing, furring minimum fastening requirements to support the cladding weight shall be as specified in Table R703.16.2. Where placed horizontally, wood furring shall be preservative-treated wood in accordance with Section R317.1 or naturally durable wood and fasteners shall be corrosion resistant in accordance with Section R317.3. Steel furring shall have a minimum G60 galvanized coating.

R703.17 Cladding attachment over foam sheathing to masonry or concrete wall construction.

masonry or concrete wall construction. Cladding shall be specified and installed in accordance with Section 703.3 and the cladding manufacturer’s instructions or an approved design. Foam sheathing shall be attached to masonry or concrete construction in accordance with the insulation manufacturer’s installation instructions or an approved design. Furring and furring attachments through foam sheathing into concrete or masonry substrate shall be designed to resist design loads determined in accordance with Section R301, including support of cladding weight as applicable. Fasteners used to attach cladding or furring through foam sheathing to masonry or concrete substrates shall be approved for application into masonry or concrete material and shall be installed in accordance with the fastener manufacturer’s instructions.

Exceptions:

  1. Where the cladding manufacturer has provided approved installation instructions for application over foam sheathing and connection to a masonry or concrete substrate, those requirements shall apply.

  2. For exterior insulation and finish systems, refer to Section R703.9.

  3. For anchored masonry or stone veneer installed over foam sheathing, refer to Section R703.8.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — California Residential Code (Title 24, Part 2.5)

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.