Chapter 10 — CHIMNEYS AND FIREPLACES
Section R1005
California Residential Code (Title 24, Part 2.5) · 2022 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
R1005.1 Listing.¶
Factory-built chimneys shall be listed and labeled and shall be installed and terminated in accordance with the manufacturer’s installation instructions.
R1005.2 Decorative shrouds.¶
Decorative shrouds shall not be installed at the termination of factory-built chimneys except where the shrouds are listed and labeled for use with the specific factory-built chimney system and installed in accordance with the manufacturer’s installation instructions.
R1005.3 Solid-fuel appliances.¶
Factory-built chimneys installed in dwelling units with solid-fuel-burning appliances shall comply with the Type HT requirements of UL 103 and shall be marked “Type HT” and “Residential Type and Building Heating Appliance Chimney.”
Exception: Chimneys for use with open combustion chamber fireplaces shall comply with the requirements of UL 103 and shall be marked “Residential Type and Building Heating Appliance Chimney.”
Chimneys for use with open combustion chamber appliances installed in buildings other than dwelling units shall comply with the requirements of UL 103 and shall be
FIGURE R1003.20 CHIMNEY CRICKET
10-12 2022 CALIFORNIA RESIDENTIAL CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
marked “Building Heating Appliance Chimney” or “Residential Type and Building Heating Appliance Chimney.”
R1005.4 Factory-built fireplaces.¶
Chimneys for use with factory-built fireplaces shall comply with the requirements of UL 127.
R1005.5 Support.¶
Where factory-built chimneys are supported by structural members, such as joists and rafters, those members shall be designed to support the additional load.
R1005.6 Medium-heat appliances.¶
Factory-built chimneys for medium-heat appliances producing flue gases having a temperature above 1,000°F (538°C), measured at the entrance to the chimney, shall comply with UL 959.
R1005.7 Factory-built chimney offsets.¶
Where a factorybuilt chimney assembly incorporates offsets, no part of the chimney shall be at an angle of more than 30 degrees (0.52 rad) from vertical at any point in the assembly and the chimney assembly shall not include more than four elbows.
R1005.8 Insulation shield.¶
Where factory-built chimneys pass through insulated assemblies, an insulation shield constructed of steel having a thickness of not less than 0.0187 inch (0.4712 mm) (No. 26 gage) shall be installed to provide clearance between the chimney and the insulation material. The clearance shall be not less than the clearance to combustibles specified by the chimney manufacturer’s installation instructions. Where chimneys pass through attic space, the shield shall terminate not less than 2 inches (51 mm) above the insulation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed chimney system shall be installed in accordance with the manufacturer’s installation instructions.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Residential Code (Title 24, Part 2.5)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Appendix AF — RADON CONTROL
- Appendix AI — PRIVATE SEWAGE
- Appendix AJ — EXISTING
- Appendix AK — SOUND
- Appendix AO — AUTOMATIC
- Appendix AR — LIGHT STRAW-CLAY
- Appendix AS — STRAWBALE
- Appendix AU — COB CONSTRUCTION
- Appendix AV — BOARD
- Appendix AW — 3D-PRINTED BUILDING
- Chapter 1 — SCOPE AND APPLICATION
- Chapter 3 — BUILDING PLANNING
- Chapter 4 — FOUNDATIONS
- Chapter 5 — FLOORS
- Chapter 6 — WALL CONSTRUCTION
- Chapter 7 — WALL COVERING
- Chapter 8 — ROOF-CEILING CONSTRUCTION
- Chapter 9 — ROOF ASSEMBLIES
▸Chapter 10 — CHIMNEYS AND FIREPLACES
- Chapter 44 — REFERENCED STANDARDS
- Appendix AH — PATIO COVERS
- Appendix AL — PERMIT FEES
- Appendix AQ — TINY HOUSES
- Appendix AT — SOLAR-READY PROVISIONS—DETACHED ONE- AND
- Appendix AX — SWIMMING POOL SAFETY ACT
- Appendix AY — AREAS PROTECTED BY THE FACILITIES
- Appendix AZ — EMERGENCY HOUSING