Chapter 12-3 — RELEASING SYSTEMS FOR SECURITY BARS IN DWELLINGS
Section 12-3-9 — ENDURANCE TEST
2025 California Referenced Standards Code (Title 24, Part 12) · 2025 edition · updated 2026-07-29 · California
12-3-9.1 A sample of the security bar releasing system shall function as intended during 250 cycles of operation without failure or excessive wear of the parts, including serving or fraying of individual cable wires. Following the cycling, the system shall be subjected to the Operation Test.
12-3-9.2 The system shall be operated and reset as described in the manufacturer's operating instructions. As part of the cycling, it is only necessary to unlatch, disengage and reset the system, and not open the security bars to the full open position. The cycling rate shall not exceed 30 cycles per minute.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Referenced Standards Code (Title 24, Part 12)
- Chapter 12-1 — ADMINISTRATION
-
▸ Chapter 12-3 — RELEASING SYSTEMS FOR SECURITY BARS IN DWELLINGS
Overview- Section 12-3-1 — SCOPE
- Section 12-3-2 — GENERAL
- Section 12-3-3 — ASSEMBLY
- Section 12-3-4 — MATERIALS
- Section 12-3-5 — TEST SETUP AND SAMPLE PREPARATION
- Section 12-3-6 — SECURE ATTACHMENT TEST
- Section 12-3-7 — OPERATION TEST
- Section 12-3-8 — MANUAL ACTUATION TEST
- Section 12-3-9 — ENDURANCE TEST
- Section 12-3-10 — ENVIRONMENTAL EXPOSURE TEST
- Section 12-3-11 — ABUSE TEST
- Section 12-3-12 — MARKINGS
- Section 12-3-13 — INSTRUCTION MANUAL
- Chapter 12-4A — LABORATORY ANIMAL QUARTERS STANDARDS
- Chapter 12-7A — MATERIALS AND CONSTRUCTION METHODS
- Chapter 12-11A and 11B — BUILDING AND FACILITY ACCESS SPECIFIC…
- Chapter 12-13 — STANDARDS FOR INSULATING MATERIAL
- Chapter 12-31C — RADIATION SHIELDING STANDARDS
- Chapter 12-71 — AIR FILTERS