Chapter 8 — INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS
Section 803
California Fire Code (Title 24, Part 9) · 2022 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
INTERIOR WALL AND CEILING FINISH IN EXISTING BUILDINGS
803.1 General. The provisions of this section shall limit the¶
allowable fire performance and smoke development of interior wall and ceiling finishes in existing buildings based on
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS
location and occupancy classification. Interior wall and ceiling finishes shall be classified in accordance with Section 803 of the California Building Code . Such materials shall be classified in accordance with NFPA 286, as indicated in Section 803.1.1, or in accordance with ASTM E84 or UL 723, as indicated in Section 803.1.2.
Materials tested in accordance with Section 803.1.1 shall not be required to be tested in accordance with Section 803.1.2.
803.1.1 Interior wall and ceiling finish materials tested in accordance with NFPA 286. Interior wall and ceiling finish materials shall be classified in accordance with NFPA 286 and tested in accordance with Section 803.1.1.1. Materials complying with Section 803.1.1.1 shall be considered to comply with the requirements of Class A specified in Section 803.1.2.
803.1.1.1 Acceptance criteria for NFPA 286. The interior finish shall comply with the following:
During the 40 kW exposure, flames shall not spread to the ceiling.
The flame shall not spread to the outer extremity of the sample on any wall or ceiling.
Flashover, as defined in NFPA 286, shall not occur.
The peak heat release rate throughout the test shall not exceed 800 kW.
The total smoke released throughout the test shall not exceed 1,000 m 2 .
803.1.2 Interior wall and ceiling finish materials tested in accordance with ASTM E84 or UL 723. Interior wall and ceiling finishes shall be classified in accordance with ASTM E84 or UL 723. Such interior finish materials shall be grouped in the following classes in accordance with their flame spread and smoke-developed indices:
Class A: Flame spread index 0–25; smoke-developed index 0–450. Class B: Flame spread index 26–75; smoke-developed index 0–450. Class C: Flame spread index 76–200; smoke-developed index 0–450. Exception: Materials tested in accordance with Section 803.1.1 and as indicated in Sections 803.1.3 through 803.15. 803.1.3 Interior wall and ceiling finish materials with specific requirements. The materials indicated in Sections 803.4 through 803.15 shall be tested as indicated in the corresponding sections.
803.2 Stability. Interior finish materials regulated by this¶
chapter shall be applied or otherwise fastened in such a manner that such materials will not readily become detached where subjected to room temperatures of 200°F (93°C) for not less than 30 minutes.
803.3 Interior finish requirements based on occupancy.¶
Interior wall and ceiling finish shall have a flame spread index not greater than that specified in Table 803.3 for the group and location designated. Interior wall and ceiling finish
materials tested in accordance with NFPA 286, and meeting the acceptance criteria of Section 803.1.1.1, shall be used where a Class A classification in accordance with ASTM E84 or UL 723 is required.
803.4 Fire-retardant coatings. The required flame spread or¶
smoke-developed index of surfaces in existing buildings shall be allowed to be achieved by application of approved fireretardant coatings, paints or solutions to surfaces having a flame spread index exceeding that allowed. Such applications shall comply with NFPA 703 and the required fire-retardant properties shall be maintained or renewed in accordance with the manufacturer’s instructions. The fire-retardant paint, coating or solution shall have been assessed by testing over the same substrate to be used in the application.
803.5 Textile wall coverings. Where used as interior wall¶
finish materials, textile wall coverings, including materials having a woven, nonwoven, napped, tufted, looped or similar surface, shall be tested in the manner intended for use, using the product mounting system, including adhesive, and shall comply with the requirements of Section 803.1.1, 803.5.1 or 803.5.2.
[California Code of Regulations, Title 19, Division 1, §3.21(a) and (b)] Interior Finish of Decorative Material.
(a) Unframed Rigid Combustible Decorative Material. Rigid combustible decorative material and assemblies of materials not more than 1 /4 inch in thickness used for fold- ing doors, room dividers, decorative screens and similar applications, which do not create concealed spaces and which are installed with exposed edges, shall be flame resistant in accordance with the following:
(1) Test specimen shall be 12 inches wide and 24 inches long. Four specimens shall be tested, two in each direc- tion of the material.
(2) The specimen shall be suspended vertically with its lower edge 2 inches above the top of a 3 /8 inch diameter Bunsen Burner. The test shall be performed in a draft- free area.
(3) The flames from the burner shall be 4 inches long and shall be adjusted with sufficient air supply to elimi- nate any yellow flame tips but without any distinct inner blue cone.
(4) The specimen shall be exposed to the flame at each corner and at not less than one other point along the lower edge. Each exposure shall be of sufficient dura- tion to determine if the material will ignite and continue to burn, but shall be not less than 20 seconds.
(5) The criteria for acceptance shall be as follows:
(A) There shall be not more than intermittent flaming appreciably beyond the area exposed to the test flame.
(B) No flame shall reach the top of the specimen.
(C) On removing the test flame there shall be not more than one second of after flaming except there may be nonprogressive flaming of short duration in areas of accumulated char which were directly exposed to the test flame.
8-4 2022 CALIFORNIA FIRE CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS
TABLE 803.3 INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCY k
| GROUP | SPRINKLEREDl | NONSPRINKLERED | ||||
|---|---|---|---|---|---|---|
| GROUP | Interior exit stairways and ramps and exit passagewaysa, b |
Corridors and enclosure for exit access stairways and ramps |
Rooms and enclosed spacesc |
Interior exit stairways and ramps and exit passagewaysa, b |
Corridors and enclosure for exit access stairways and ramps |
Rooms and enclosed spacesc |
| A-1 and A-2 | B | B | C | A | Ad | Be |
| A-3f, A-4, A-5 | B | B | C | A | Ad | C |
| B, E, M, R-1, R-4 | B | Cm | C | A | Bm | C |
| F | C | C | C | B | C | C |
| H,L | B | B | Cg | A | A | B |
| I-2,I-2.1 | B | B | Bh, i | A | A | B |
| I-3 | A | Aj | C | A | A | B |
| I-4 | B | B | Bh, i | A | A | B |
| R-2 | C | C | C | B | B | C |
| R-2.1 | B | C | C | A | B | B |
| R-3,R-3.1 | C | C | C | C | C | C |
| S | C | C | C | B | B | C |
| U | No Restrictions | No Restrictions | No Restrictions | No Restrictions | No Restrictions | No Restrictions |
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929 m 2 . NP=Not Permitted [SFM ] a. Class C interior finish materials shall be allowed for wainscoting or paneling of not more than 1,000 square feet of applied surface area in the grade lobby
where applied directly to a noncombustible base or over furring strips applied to a noncombustible base and fireblocked as required by Section 803.11 of the California Building Code . b. In other than Group I-2 and I-2.1 occupancies in buildings less than three stories above grade plane of other than Group I-3, Class B interior finish for
nonsprinklered buildings and Class C interior finish for sprinklered buildings shall be permitted in interior exit stairways and ramps. b.In exit enclosures of buildings less than three stories in height of other than Group I-3, Class B interior finish for nonsprinklered buildings and Class C for
sprinklered buildings shall be permitted. c. Requirements for rooms and enclosed spaces shall be based on spaces enclosed by partitions. Where a fire-resistance rating is required for structural elements,
the enclosing partitions shall extend from the floor to the ceiling. Partitions that do not comply with this shall be considered as enclosing spaces and the rooms or spaces on both sides shall be considered as one. In determining the applicable requirements for rooms and enclosed spaces, the specific occupancy thereof shall be the governing factor, regardless of the group classification of the building or structure. d.Lobby areas in Group A-1, A-2 and A-3 occupancies shall be not less than Class B materials. e. Class C interior finish materials shall be allowed in Group A occupancies with an occupant load of 300 persons or less. f. In places of religious worship, wood used for ornamental purposes, trusses, paneling or chancel furnishing shall be allowed. g.Class B material is required where the building exceeds two stories. h.Class C interior finish materials shall be allowed in administrative spaces. i. Class C interior finish materials shall be allowed in rooms with a capacity of four persons or less. j. Class B materials shall be allowed as wainscoting extending not more than 48 inches above the finished floor in corridors. k.Finish materials as provided for in other sections of this code. l. Applies where the vertical exits, exit passageways, corridors or rooms and spaces are protected by an approved automatic sprinkler system installed in
accordance with Section 903.3.1.1 or 903.3.1.2. m.Corridors in ambulatory care facilities shall have a Class B or better interior finish material.
(b) Framed Rigid Combustible Decorative Material. Rigid combustible decorative material and assemblies of materi- als not more than 1 /4 inch in thickness used for folding doors, room dividers, decorative screens and similar applications, and which are installed with all edges protected, shall conform to the following:
(1) All exposed edges shall be protected with frames of metal or other noncombustible material, or solid wood of minimum 1 /4 inch dimension.
(2) The total square foot area of the material shall not exceed ten percent of that of the floor area of the room in which the material is installed.
(3) When tested as follows, no flames shall reach the top edge of the specimen.
The test shall be conducted in a draft free area, on a speci- men of the material 12 inches by 12 inches suspended at a 45 degree angle from the horizontal with the upper and lower edges in a horizontal plane. The test flame shall be 3 inches long from a Bunsen Burner of approximately 1 /2 inch inside diameter with the air supply completely shut off. The burner shall be so positioned so that its top is 1 inch vertically below a point on the lower surface of the test specimen, 1 inch up from its lower horizontal edge, and mid-way between the inclined edges. The exposure to the test flame and the dura- tion of test shall be for a period of 2 minutes.
803.5.1 Room corner test for textile wall coverings and expanded vinyl wall coverings. Textile wall coverings and expanded vinyl wall coverings shall meet the criteria of Section 803.5.1.1 when tested in the manner intended
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS
for use in accordance with the Method B protocol of NFPA 265 using the product mounting system, including adhesive. Test specimen preparation and mounting shall be in accordance with ASTM E2404.
803.5.1.1 Acceptance criteria for NFPA 265 Method B test protocol. Where testing to NFPA 265, the interior finish shall comply with the following:
During the 40-kW exposure, flames shall not spread to the ceiling.
The flame shall not spread to the outer extremities of the samples on the 8-foot by 12-foot (203 by 305 mm) walls.
Flashover, as defined in NFPA 265, shall not occur.
For newly introduced wall coverings, the total smoke released throughout the test shall not exceed 1,000 m 2 .
803.5.1.2 Unframed rigid combustible decorative material. Rigid combustible decorative material and assemblies of materials not more than 1 /4 inch in thick- ness used for folding doors, room dividers, decorative screens and similar applications, which do not create concealed spaces and which are installed with exposed edges, shall be flame resistant in accordance with SFM Standard 12-7-5 contained in Title 24, Part 12, Califor- nia Referenced Standards Code.
803.5.1.3 Framed rigid combustible decorative mate- rial. Rigid combustible decorative material and assemblies of materials not more than 1 /4 inch in thick- ness used for folding doors, room dividers, decorative screens and similar applications, and which are installed with all edges protected, shall conform to SFM Standard 12-7-5 contained in Title 24, Part 12, California Referenced Standards Code.
803.5.2 Acceptance criteria for wall and ceiling cover- ings. Textile wall and ceiling coverings shall have a Class A flame spread index in accordance with ASTM E84 or UL 723, and be protected by an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2. Test specimen preparation and mounting shall be in accordance with ASTM E2404.
803.6 Textile ceiling coverings.¶
Where used as interior ceiling finish materials, textile ceiling coverings, including materials having a woven, nonwoven, napped, tufted, looped or similar surface and carpet or similar textile materials, shall be tested in the manner intended for use, using the product mounting system, including adhesive, and shall comply with the requirements of Section 803.1.1 or 803.5.2.
803.7 Expanded vinyl wall coverings.¶
Where used as interior wall finish materials, expanded vinyl wall coverings shall be tested in the manner intended for use, using the product mounting system, including adhesive, and shall comply with the requirements of Section 803.1.1, 803.5.1 or 803.5.2.
803.8 Expanded vinyl ceiling coverings. Where used as¶
interior ceiling finish materials, expanded vinyl ceiling coverings shall be tested in the manner intended for use, using the
product mounting system, including adhesive, and shall comply with the requirements of Section 803.1.1 or 803.5.2.
[BF] 803.9 High-density polyethylene (HDPE) and poly- propylene (PP). Where high-density polyethylene or polypropylene is used as an interior finish, it shall comply with Section 803.1.1.
[BF] 803.10 Site-fabricated stretch systems. Where used as newly installed interior wall or interior ceiling finish materials, site-fabricated stretch systems containing all three components described in the definition in Chapter 2 shall be tested in the manner intended for use, and shall comply with the requirements of Section 803.1.1 or 803.1.2. If the materials are tested in accordance with ASTM E84 or UL 723, specimen preparation and mounting shall be in accordance with ASTM E2573.
803.11 Foam plastic materials. Foam plastic materials shall¶
not be used as interior wall and ceiling finish unless specifically allowed by Section 803.11.1 or 803.11.2. Foam plastic materials shall not be used as interior trim unless specifically allowed by Section 804.2.
803.11.1 Foam plastic combustibility characteristics. Foam plastic materials shall be allowed on the basis of fire tests that substantiate their combustibility characteristics for the use intended under actual fire conditions, as indicated in Section 2603.9 of the California Building Code . This section shall apply both to exposed foam plastics and to foam plastics used in conjunction with a textile or vinyl facing or cover.
803.11.2 Thermal barrier for foam plastics. Foam plastic material shall be allowed if it is separated from the interior of the building by a thermal barrier in accordance with Section 2603.4 of the California Building Code.
803.12 Facings or wood veneers intended to be applied on¶
site over a wood substrate. Facings or veneers intended to be applied on site over a wood substrate shall comply with one of the following:
The facing or veneer shall meet the criteria of Section 803.1.1 when tested in accordance with NFPA 286 using the product mounting system, including adhesive, described in Section 5.8.9 of NFPA 286.
The facing or veneer shall have a Class A, B or C flame spread index and smoke-developed index based on the requirements of Table 803.3, in accordance with ASTM E84 or UL 723. Test specimen preparation and mounting shall be in accordance with ASTM E2404.
803.13 Laminated products factory produced with an¶
attached wood substrate. Laminated products factory produced with an attached wood substrate shall comply with one of the following:
The laminated product shall meet the criteria of Section 803.1.1 when tested in accordance with NFPA 286 using the product mounting system, including adhesive, of actual use.
The laminated product shall have a Class A, B or C flame spread index and smoke-developed index based on the requirements of Table 803.3, in accordance with
8-6 2022 CALIFORNIA FIRE CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
ASTM E84 or UL 723. Test specimen preparation and mounting shall be in accordance with ASTM E2579.
803.14 Thickness exemption. Materials having a thickness¶
less than 0.036 inch (0.9 mm) applied directly to the surface of walls or ceilings shall not be required to be tested.
803.15 Heavy timber exemption.¶
Exposed portions of building elements complying with the requirements of Type IV construction in accordance with the California Building Code shall not be subject to interior finish requirements.
Get a plain-English answer with a citation back to this text.
Ask AI about this code