Chapter 34 — TIRE REBUILDING AND TIRE STORAGE
Section 3403
California Fire Code (Title 24, Part 9) · 2022 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
3403.1 Construction. Tire rebuilding plants shall comply¶
with the requirements of the California Building Code, as to construction, separation from other buildings or other portions of the same building, and protection.
3403.2 Location. Buffing operations shall be located in a¶
room separated from the remainder of the building housing the tire rebuilding or tire recapping operations by a 1-hour fire barrier.
Exception: Buffing operations are not required to be separated where all of the following conditions are met:
Buffing operations are equipped with an approved continuous automatic water-spray system directed at the point of cutting action.
Buffing machines are connected to particle-collecting systems providing a minimum air movement of 1,500 cubic feet per minute (cfm) (0.71 m 3 /s) in volume and 4,500 feet per minute (fpm) (23 m/s) in-line velocity.
The collecting system shall discharge the rubber particles to an approved outdoor noncombustible or fire-resistant container that is emptied at frequent intervals to prevent overflow.
3403.3 Cleaning. The buffing area shall be cleaned at¶
frequent intervals to prevent the accumulation of rubber particles.
3403.4 Spray rooms and booths. Each spray room or spray¶
booth where flammable or combustible solvents are applied, shall comply with Chapter 24.