Section 3006
California Fire Code (Title 24, Part 9) · 2022 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
3006.1 Required protection. Class A and B ovens that¶
contain, or are utilized for the processing of, combustible materials shall be protected by an approved automatic fireextinguishing system complying with Chapter 9.
Exceptions:
Small tabletop ovens used in laboratory facilities.
Nonwalk-in ovens that are less than 4 feet (1219 mm) in length and width.
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
INDUSTRIAL OVENS
3006.2 Fixed fire-extinguishing systems.¶
Fixed fire-extinguishing systems shall be provided for Class C or D ovens to protect against such hazards as overheating, spillage of molten salts or metals, quench tanks, ignition of hydraulic oil and escape of fuel. It shall be the user’s responsibility to consult with the fire code official concerning the necessary requirements for such protection.
3006.3 Fire extinguishers. Portable fire extinguishers¶
complying with Section 906 shall be provided not closer than 15 feet (4572 mm) or not more than 50 feet (15 240 mm) or in accordance with NFPA 10. This shall apply to the oven and related equipment.