Section 2106
California Fire Code (Title 24, Part 9) · 2022 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
2106.1 General. Spotting and pretreating operations and¶
equipment shall comply with the provisions of Sections 2106.2 through 2106.5.
2106.2 Class I solvents. The maximum quantity of Class I¶
solvents permitted at any work station shall be 1 gallon (4 L). Spotting or prespotting shall be permitted to be conducted
21-4 2022 CALIFORNIA FIRE CODE
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
with Class I solvents where they are stored in and dispensed from approved safety cans or in sealed DOT-approved metal shipping containers of not more than 1-gallon (4 L) capacity.
2106.2.1 Spotting and prespotting. Spotting and prespotting shall be permitted to be conducted with Class I solvents where dispensed from plastic containers of not more than 1 pint (0.5 L) capacity.
2106.3 Class II and III solvents. Scouring, brushing, and¶
spotting and pretreating shall be permitted to be conducted with Class II or III solvents. The maximum quantity of Class II or III solvents permitted at any work station shall be 1 gallon (4 L). In other than Group H-2 occupancy, the aggregate quantities of solvents shall not exceed the maximum allowable quantity per control area for use-open system.
2106.3.1 Spotting tables. Scouring, brushing or spotting tables on which articles are soaked in solvent shall have a liquid-tight top with a curb on all sides not less than 1 inch (25 mm) high. The top of the table shall be pitched to ensure thorough draining to a 1 1 /2-inch (38 mm) drain connected to an approved container.
2106.3.2 Special handling. Where approved, articles that cannot be washed in the usual washing machines are allowed to be cleaned in scrubbing tubs. Scrubbing tubs shall comply with the following:
Only Class II or III liquids shall be used.
The total amount of solvent used in such open containers shall not exceed 3 gallons (11 L).
Scrubbing tubs shall be secured to the floor.
Scrubbing tubs shall be provided with permanent 1 1 /2-inch (38 mm) drains. Such drain shall be provided with a trap and shall be connected to an approved container.
2106.3.3 Ventilation. Scrubbing tubs, scouring, brushing or spotting operations shall be located such that solvent vapors are captured and exhausted by the ventilating system.
2106.3.4 Bonding and grounding. Metal scouring, brushing and spotting tables and scrubbing tubs shall be permanently and effectively bonded and grounded.
2106.4 Type IV systems. Flammable and combustible¶
liquids used for spotting operations shall be stored in approved safety cans or in sealed DOTn-approved shipping containers of not more than 1 gallon (4 L) in capacity. Aggregate amounts shall not exceed 10 gallons (38 L).
2106.5 Type V systems.¶
Spotting operations using flammable or combustible liquids are prohibited in Type V dry cleaning systems.
Get a plain-English answer with a citation back to this text.
Ask AI about this code