Section 1017
California Fire Code (Title 24, Part 9) · 2022 edition · updated 2026-09-10 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
EXIT ACCESS TRAVEL DISTANCE
[BE] 1017.1 General. Travel distance within the exit access portion of the means of egress system shall be in accordance with this section.
MEANS OF EGRESS
[BE] 1017.2 Limitations. Exit access travel distance shall not exceed the values given in Table 1017.2.
[BE] TABLE 1017.2 EXIT ACCESS TRAVEL DISTANCE a
| OCCUPANCY | WITHOUT SPRINKLER SYSTEM (feet) |
WITH SPRINKLER SYSTEM (feet) |
|---|---|---|
| A, E, F-1, M, R, S-1 | 200 | 250b, e |
| R-2.1 | Not Permitted | 250c |
| B | 200 | 300c |
| F-2, S-2, U | 300 | 400c |
| H-1 | Not Permitted | 75d |
| H-2 | Not Permitted | 100d |
| H-3 | Not Permitted | 150d |
| H-4 | Not Permitted | 175d |
| H-5 | Not Permitted | 200c |
| I-2,_I-2.1,_I-3f, I-4 | Not Permitted | 200c |
| L | Not Permitted | 200c |
For SI: 1 foot = 304.8 mm. a. See the following sections for modifications to exit access travel distance
requirements:
Section 402.8 of the California Building Code : For the distance
limitation in malls. Section 407.4 of the California Building Code : For the distance
limitation in Group I-2. Section 408.3.10 of the California Building Code: For increased
limitation in Group I-3. Sections 408.6.1 and 408.8.1 of the California Building Code : For the
distance limitations in Group I-3. Section 411.2 of the California Building Code : For the distance
limitation in special amusement areas. Section 412.6 of the California Building Code : For the distance
limitations in aircraft manufacturing facilities. Section 1006.2.2.2: For the distance limitation in refrigeration
machinery rooms. Section 1006.2.2.3: For the distance limitation in refrigerated rooms
and spaces. Section 1006.3.4: For buildings with one exit. Section 1017.2.2: For increased distance limitation in Groups F-1 and
S-1. Section 1030.7: For increased limitation in assembly seating. Section 3103.4 of the California Building Code : For temporary structures. Section 3104.9 of the California Building Code : For pedestrian
walkways. b. Buildings equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1 or 903.3.1.2. See Section 903 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.2. c. Buildings equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1. d. Group H occupancies equipped throughout with an automatic sprinkler
system in accordance with Section 903.2.5.1. e. Group R-3 and R-4 buildings equipped throughout with an automatic
sprinkler system in accordance with Section 903.3.1.3. See Section 903.2.8 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.3. f. Not permitted in nonsprinklered Group I-3 occupancies.
[BE] 1017.2.1 Exterior egress balcony increase. Exit access travel distances specified in Table 1017.2 shall be increased up to an additional 100 feet (30 480 mm) provided that the last portion of the exit access leading to the exit occurs on an exterior egress balcony constructed in
Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.
MEANS OF EGRESS
accordance with Section 1021. The length of such balcony shall be not less than the amount of the increase taken.
[BE] 1017.2.2 Groups F-1 and S-1 increase. The maximum exit access travel distance shall be 400 feet (122 m) in Group F-1 or S-1 occupancies where all of the following conditions are met:
The portion of the building classified as Group F-1 or S-1 is limited to one story in height.
The minimum height from the finished floor to the bottom of the ceiling or roof slab or deck is 24 feet (7315 mm).
The building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
[BE] 1017.3 Measurement. Exit access travel distance shall be measured from the most remote point of each room, area or space along the natural and unobstructed path of horizontal and vertical egress travel to the entrance to an exit. Where more than one exit is required, exit access travel distance shall be measured to the nearest exit.
Exceptions:
In open parking garages, exit access travel distance is permitted to be measured to the closest riser of an exit access stairway or the closest slope of an exit access ramp.
In smoke-protected seating and open-air assembly seating, exit access travel distance shall be measured in accordance with Section 1030.7.
[BE] 1017.3.1 Exit access stairways and ramps. Travel distance on exit access stairways or ramps shall be included in the exit access travel distance measurement. The measurement along stairways shall be made on a plane parallel and tangent to the stair tread nosings in the center of the stair and landings. The measurement along ramps shall be made on the walking surface in the center of the ramp and landings. 1017.3.2 Atriums. Exit access travel distance for areas open to an atrium shall comply with the requirements of Sections 1017.3.2.1 through 1017.3.2.3.
1017.3.2.1 Egress not through the atrium. Where required access to the exits is not through the atrium, exit access travel distance shall comply with Section 1017.2. 1017.3.2.2 Exit access travel distance at the level of exit discharge. Where the path of egress travel is through an atrium space, exit access travel distance at the level of exit discharge shall be determined in accordance with Section 1017.2. 1017.3.2.3 Exit access travel distance at other than the level of exit discharge. Where the path of egress travel is not at the level of exit discharge from the atrium, that portion of the total permitted exit access travel distance that occurs within the atrium shall be not greater than 200 feet (60 960 mm).
Get a plain-English answer with a citation back to this text.
Ask AI about this code