316.1 Trapdoors to be closed. Trapdoors and scuttle covers,

other than those that are within a dwelling unit or automatically operated, shall be kept closed at all times except when in use.

Exceptions & meaning →

316.2 Shaftway markings. Vertical shafts shall be identified

as required by this section.

316.2.1 Exterior access to shaftways. Outside openings that can be reached by the fire department and that open directly on a hoistway or shaftway communicating between two or more floors in a building shall be plainly marked with the word “SHAFTWAY” in red letters not less than 6 inches (152 mm) high on a white background. Such warning signs shall be placed so as to be readily discernible from the outside of the building.

316.2.2 Interior access to shaftways. Door or window openings to a hoistway or shaftway from the interior of the building shall be plainly marked with the word “SHAFTWAY” in red letters not less than 6 inches (152 mm) high on a white background. Such warning signs shall be placed so as to be readily discernible.

Exception: Marking shall not be required on shaftway openings that are readily discernible as openings onto a shaftway by the construction or arrangement.

Exceptions & meaning →

316.3 Pitfalls.

The intentional design or alteration of buildings to disable, injure, maim or kill intruders is prohibited. A person shall not install and use firearms, sharp or pointed objects, razor wire, explosives, flammable or combustible liquid containers, or dispensers containing highly toxic, toxic, irritant or other hazardous materials in a manner that could passively or actively disable, injure, maim or kill a fire fighter who forcibly enters a building for the purpose of controlling or extinguishing a fire, rescuing trapped occupants or rendering other emergency assistance.

Exceptions & meaning →

316.4 Obstructions on roofs. Wires, cables, ropes, antennas,

or other suspended obstructions installed on the roof of a building having a roof slope of less than 30 degrees (0.52 rad) shall not create an obstruction that is less than 7 feet (2133 mm) high above the surface of the roof.

Exceptions:

  1. Such obstruction shall be permitted where the wire, cable, rope, antenna or suspended obstruction is encased in a white, 2-inch (51 mm) minimum diameter plastic pipe or an approved equivalent.
  2. Such obstruction shall be permitted where there is a solid obstruction below such that accidentally walking into the wire, cable, rope, antenna or suspended obstruction is not possible.

TABLE 315.7.6(1) SEPARATION DISTANCE BETWEEN WOOD PALLET STACKS AND BUILDINGS

WALL CONSTRUCTION OPENING TYPE WOOD PALLET SEPARATION DISTANCE (feet)
WALL CONSTRUCTION OPENING TYPE ≤ 50 Pallets 51 to 200 Pallets > 200 Pallets
Masonry None 2 2 2
Masonry Fire-rated glazing with open sprin-
klers
2 5 20
Masonry Fire-rated glazing 5 10 20
Masonry Plain glass with open sprinklers 5 10 20
Noncombustible None 5 10 20
Wood with open sprinklers — 5 10 20
Wood None 15 30 90
Any Plain glass 15 30 90

For SI: 1 foot = 304.8 mm.

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.

GENERAL REQUIREMENTS

TABLE 315.7.6(2) SEPARATION DISTANCE BETWEEN PLASTIC PALLET STACKS AND BUILDINGS

WALL CONSTRUCTION OPENING TYPE PLASTIC PALLET SEPARATION DISTANCE (feet)
WALL CONSTRUCTION OPENING TYPE ≤ 50 Pallets 51 to 200 Pallets > 200 Pallets
Masonry None 2 2 2
Masonry Fire-rated glazing with open sprin-
klers
10 20 50
Masonry Fire-rated glazing 15 40 100
Masonry Plain glass with open sprinklers 15 40 100
Noncombustible None 15 40 100
Wood with open sprinklers — 15 40 100
Wood None 30 80 150
Any Plain glass 30 80 150

For SI: 1 foot = 304.8 mm.

TABLE 315.7.6(3) SEPARATION FROM OTHER PALLET PILES AND ON-SITE STORAGE (WOOD PALLETS)

WOOD PALLET SEPARATION DISTANCE (feet)
≤ 50 Pallets 51 to 200 Pallets > 200 Pallets
Between pallet piles 7.5 15 45
Other on-site storage 7.5 15 45

For SI: 1 foot = 304.8 mm.

TABLE 315.7.6(4) SEPARATION FROM OTHER PALLET PILES AND ON-SITE STORAGE (PLASTIC PALLETS)

PLASTIC PALLET SEPARATION DISTANCE (feet)
≤ 50 Pallets 51 to 200 Pallets > 200 Pallets
Between pallet piles 15 40 75
Other on-site storage 15 40 75

For SI: 1 foot = 304.8 mm.

[California Code of Regulations, Title 19, Division 1, §3.05(b)] Fire Department Access and Egress. (Roofs).

(b) Roofs. No person shall install or maintain any security barrier such as barbed wire fencing, razor wire fencing, chain link fencing or any other fencing material, cable, aerial, antenna or other obstruction on the roof of any commercial establishment in such a manner as to obstruct or render egress or access hazardous in the event of fire or other emergency.

Exception: Guy wire, rods and aerial antenna masts may be attached to a roof structure having a slope of less than 30 degrees provided there is full clearance of seven feet or more between the roof and said obstruction. Guy wire or rods required to support aerial or antenna masts may be attached to a roof structure a lateral distance from the mast not in excess of one-sixth the height of the mast.

Exceptions & meaning →

316.5 Security device. Any security device or system that

emits any medium that could obscure a means of egress in any building, structure or premise shall be prohibited.

Exceptions & meaning →

316.6 Structures and outdoor storage underneath high-

voltage transmission lines. Structures and outdoor storage underneath high-voltage transmission lines shall comply with Sections 316.6.1 and 316.6.2, respectively.

316.6.1 Structures. Structures shall not be constructed within the utility easement beneath high-voltage transmission lines.

Exception: Restrooms and unoccupied telecommunication structures of noncombustible construction less than 15 feet (4572 mm) in height.

316.6.2 Outdoor storage. Outdoor storage within the utility easement underneath high-voltage transmission lines shall be limited to noncombustible material. Storage of hazardous materials including, but not limited to, flammable and combustible liquids is prohibited.

Exception: Combustible storage, including vehicles and fuel storage for backup power equipment serving public utility equipment, is allowed, provided that a plan indicating the storage configuration is submitted and approved.

3-14 2022 CALIFORNIA FIRE CODE

Copyright © 2022 by, or licensed to, International Code Council, Inc. (ALL RIGHTS RESERVED); licensed to California Building Standards Commission pursuant to License Agreement. No further reproductions is authorized. Any unauthorized reproduction or distribution is a violation of the federal copyright act and the license agreement, and subject to civil and criminal penalties thereunder.