Chapter 32 — HIGH-PILED COMBUSTIBLE STORAGE
3204 Designation of High-Piled Storage Areas — 2025 California Fire Code
California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Fire Code (Title 24, Part 9) § 3204 · Effective January 1, 2026 · Official source: Building Standards Commission
3204.1 General.¶
High-piled storage areas, and portions of high-piled storage areas intended for storage of a different commodity class than adjacent areas, shall be designed and specifically designated to contain Class I, Class II, Class III, Class IV or high-hazard commodities. The designation of a high-piled storage area, or portion thereof intended for storage of a different commodity class, shall be based on the highest hazard commodity class stored except as provided in Section 3204.2.
3204.2 Designation based on engineering analysis.¶
The designation of a high-piled combustible storage area, or portion thereof, is allowed to be based on a lower hazard class than that of the highest class of commodity stored where a limited quantity of the higher hazard commodity has been demonstrated by engineering analysis to be adequately protected by the automatic sprinkler system provided. The engineering analysis shall consider the ability of the automatic sprinkler system to deliver the higher density required by the higher hazard commodity. The higher density shall be based on the actual storage height of the pile or rack and the minimum allowable design area for sprinkler operation as set forth in the density/area figures provided in NFPA 13. The contiguous area occupied by the higher hazard commodity shall not exceed 120 square feet (11 m [2] ) and additional areas of higher hazard commodity shall be separated from other such areas by 25 feet (7620 mm) or more. The automatic sprinkler system shall be capable of delivering the higher density over a minimum area of 900 square feet (84 m [2] ) for wet pipe systems and 1,200 square feet (111 m [2] ) for dry pipe systems. The shape of the design area shall be in accordance with Section 903.
HIGH-PILED COMBUSTIBLE STORAGE