Appendix K — CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY CARE FACILITIES
K104 Means of Egress Requirements for Existing Ambulatory Care Facilities — 2025 California Fire Code
California Fire Code (Title 24, Part 9) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Fire Code (Title 24, Part 9) § K104 · Effective January 1, 2026 · Official source: Building Standards Commission
K104.1 Size of doors.¶
The required capacity of each door opening shall be sufficient for the occupant load thereof and shall provide a minimum clear opening width of 28 inches (711 mm). Where this section requires a minimum clear opening width of 28 inches (711 mm) and a door opening includes two door leaves without a mullion, one leaf shall provide a minimum clear opening width of 28 inches (711 mm). In ambulatory care facilities, doors serving as means of egress from patient treatment rooms shall provide a minimum clear opening width of 32 inches (813 mm). The maximum width of a swinging door leaf shall be 48 inches (1219 mm) nominal. The minimum clear opening height of doors shall be 80 inches (2032 mm).
Exceptions:
- Door openings to storage closets less than 10 square feet (0.93 m [2] ) in area shall not be limited by the minimum clear opening width.
- The width of door leaves in revolving doors that comply with Section 1010.3.1 shall not be limited.
- The maximum width of door leaves in revolving doors that comply with Section 1010.3.2 shall not be limited.
- Exit access doors serving a room not larger than 70 square feet (6.5 m [2] ) shall have a door leaf width of not less than 24 inches (610 mm).
- Door closers and door stops shall be permitted to be 78 inches (1980 mm) minimum above the floor.
K104.2 Corridor and aisle width.¶
Corridor width shall be as determined in Section 1005.1 and this section. The minimum width of corridors and aisles that serve gurney traffic in areas where patients receive care that causes them to be incapable of self-preservation shall be not less than 72 inches (1829 mm).
APPENDIX K—CONSTRUCTION REQUIREMENTS FOR EXISTING AMBULATORY CARE FACILITIES
K104.3 Existing elevators.¶
Existing elevators, escalators, dumbwaiters and moving walks shall comply with the requirements of Sections K104.3.1 and K104.3.2.
K104.3.1 Elevators, escalators, dumbwaiters and moving walks. Existing elevators, escalators, dumbwaiters and moving walks in ambulatory care facilities required to be separated by Section 422 of the California Building Code shall comply with Cali- fornia Code of Regulations, Title 8, Division 1, Chapter 4, Subchapter 6, Elevator Safety Orders.
K104.3.2 Elevator emergency operation. Existing elevators with a travel distance of 25 feet (7620 mm) or more above or below the main floor or other level of a building and intended to serve the needs of emergency personnel for firefighting or rescue purposes shall be provided with emergency operation in accordance with California Code of Regulations, Title 8, Division 1, Chapter 4, Subchapter 6, Elevator Safety Orders.