Chapter 15 — CONSTRUCTION SAFEGUARDS

Section 1512 — WATER SUPPLY FOR FIRE PROTECTION

2025 California Existing Building Code (Title 24, Part 10) · 2025 edition · updated 2026-07-29 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

[F] 1512.1 When required. An approved water supply for fire protection, either temporary or permanent, shall be made available as soon as combustible building material arrives on the site, on commencement of vertical combustible construction, and on installation of a standpipe system in buildings under construction, in accordance with Sections 1512.1 through 1512.5.

Exception: The fire code official is authorized to reduce the fire-flow requirements for isolated buildings or a group of buildings in rural areas or small communities where the development of full fire-flow requirements is impractical.

[F] 1512.2 Combustible building materials. When combustible building materials of the building under construction are delivered to a site, a minimum fire flow of 500 gallons per minute (1893 L/m) shall be provided. The fire hydrant used to provide this fire flow supply shall be within 500 feet (152 m) of the combustible building materials as measured along an approved fire apparatus access lane. Where the site configuration is such that one fire hydrant cannot be located within 500 feet (152 m) of all combustible building materials, additional fire hydrants shall be required to provide coverage in accordance with this section.

[F] 1512.3 Vertical construction of Types III, IV and V construction. Prior to commencement of vertical construction of Type III, IV or V buildings that utilize any combustible building materials, the fire flow required by Sections 1512.3.1 through 1512.3.3 shall be provided, accompanied by fire hydrants in sufficient quantity to deliver the required fire flow and proper coverage.

[F] 1512.3.1 Fire separation up to 30 feet. Where a building of Type III, IV or V construction has a fire separation distance of less than 30 feet (9144 mm) from property lot lines, and an adjacent property has an existing structure or otherwise can be built on, the water supply shall provide either a minimum of 500 gallons per minute (1893 L/m), or the entire fire flow required for the building when constructed, whichever is greater.

[F] 1512.3.2 Fire separation of 30 feet up to 60 feet. Where a building of Type III, IV or V construction has a fire separation distance of 30 feet (9144 mm) up to 60 feet (18 288 mm) from property lot lines, and an adjacent property has an existing structure or otherwise can be constructed upon, the water supply shall provide a minimum of 500 gallons per minute (1893 L/m), or 50 percent of the fire flow required for the building when constructed, whichever is greater.

[F] 1512.3.3 Fire separation of 60 feet or greater. Where a building of Type III, IV or V construction has a fire separation of 60 feet (18 288 mm) or greater from a property lot line, a water supply of 500 gallons per minute (1893 L/m) shall be provided.

[F] 1512.4 Vertical construction, Types I and II construction. If combustible construction materials are delivered to the construction site, water supply in accordance with Section 1509.2 shall be provided. Additional water supply for fire flow is not required prior to commencing vertical construction of Type I and II buildings.

[F] 1512.5 Standpipe supply. Regardless of the presence of combustible building materials, the construction type or the fire separation distance, where a standpipe is required in accordance with Section 1509, a water supply providing a minimum flow of 500 gallons per minute (1893 L/m) shall be provided. The fire hydrant used for this water supply shall be located within 100 feet (30 480 mm) of the fire department connection supplying the standpipe.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

15-8 2025 CALIFORNIA EXISTING BUILDING CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

CALIFORNIA EXISTING BUILDING CODE – MATRIX ADOPTION TABLE

CHAPTER 16 – REFERENCED STANDARDS

(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

Adopting Agency BSC BSC-
CG
SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
Adopting Agency BSC BSC-
CG
SFM 1 2 1/AC AC SS SS/CC 1 1R 2 3 4 5 6 6 6 6 6 6 6 6 6
Adopt Entire Chapter X X
Adopt Entire Chapter as
amended (amended
sections listed below)
X X X X X X X X X X X
Adopt only those sections
that are listed below
Chapter / Section
ASCE/SEI 7—2016 X X X X X
ASCE/SEI 7—2022 X X X X X X X
ASCE/SEI 41—2013 X
ASCE/SEI 41—2023 X X X X X X X X X X
ASTM A615—15 22 X
ICC A117.1—2017
ICC CBC—25 X
NFPA 72—24 X

The state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

16-2 2025 CALIFORNIA EXISTING BUILDING CODE

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Existing Building Code (Title 24, Part 10)
2025 California Existing Building Code (Title 24, Part 10)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
  4. Chapter 3A — PROVISIONS FOR ALL COMPLIANCE METHODS
  5. Chapter 4 — REPAIRS
  6. Chapter 4A — REPAIRS
  7. Chapter 5 — PRESCRIPTIVE COMPLIANCE METHOD
  8. Chapter 5A — PRESCRIPTIVE COMPLIANCE METHOD
  9. Chapter 6 — CLASSIFICATION OF WORK
  10. Chapter 7 — ALTERATIONS—LEVEL 1
  11. Chapter 8 — ALTERATIONS—LEVEL 2
  12. Chapter 9 — ALTERATIONS—LEVEL 3
  13. Chapter 10 — CHANGE OF OCCUPANCY
  14. Chapter 11 — ADDITIONS
  15. Chapter 12 — HISTORIC BUILDINGS
  16. Chapter 13 — PERFORMANCE COMPLIANCE METHODS
  17. Chapter 14 — RELOCATED OR MOVED BUILDINGS
  18. Chapter 15 — CONSTRUCTION SAFEGUARDS
  19. Chapter 16 — REFERENCED STANDARDS
  20. Appendix A — GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING B…
  21. Appendix B — SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS FOR EXIS…
  22. Appendix C — GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUIL…
  23. Appendix D — BOARD OF APPEALS
  24. Appendix E — TEMPORARY EMERGENCY USES
  25. Appendix A — GUIDELINES ON FIRE RATINGS OF ARCHAIC MATERIALS A…

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.