Section 1502 — OWNER’S RESPONSIBILITY FOR FIRE PROTECTION

2025 California Existing Building Code (Title 24, Part 10) · 2025 edition · updated 2026-07-29 · California

Italicized text is a California amendment to the model code, as printed in the official publication.

[F] 1502.1 Site safety plan. The owner or owner’s authorized agent shall be responsible for the development, implementation and maintenance of an approved, written site safety plan establishing a fire prevention program at the project site applicable throughout all phases of the construction, repair, alteration or demolition work. The plan shall be submitted and approved before a building permit is issued, Any changes to the plan shall address the requirements of this chapter and other applicable portions of the California Fire Code, the duties of staff and staff training requirements. The plan shall be submitted for approval in accordance with the California Fire Code .

[F] 1502.1.1 Components of site safety plans. Site safety plans shall include the following as applicable:

  1. Name and contact information of site safety director.

  2. Documentation of the training of the site safety director and fire watch personnel.

  3. Procedures for reporting emergencies.

  4. Fire department vehicle access routes.

  5. Location of fire protection equipment, including portable fire extinguishers, standpipes, fire department connections and fire hydrants.

  6. Smoking and cooking policies, designated areas to be used where approved and signage locations in accordance with the California Fire Code .

  7. Location and safety considerations for temporary heating equipment.

  8. Hot work permit plan.

  9. Plans for control of combustible waste material.

  10. Locations and methods for storage and use of flammable and combustible liquids and other hazardous materials.

  11. Provisions for site security and, where required, for a fire watch.

  12. Changes that affect this plan.

  13. Other site-specific information required by the California Fire Code .

[F] 1502.2 Site safety director. The owner shall designate a person to be the site safety director. The site safety director shall be responsible for ensuring compliance with the site safety plan. The site safety director shall have the authority to enforce the provisions of this chapter and other provisions as necessary to secure the intent of this chapter. Where guard service is provided in accordance with the California Fire Code, the site safety director shall be responsible for the guard service.

[F] 1502.3 Daily fire safety inspection. The site safety director shall be responsible for completion of a daily fire safety inspection at the project site. Each day, all building and outdoor areas shall be inspected to ensure compliance with the inspection list in this

on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

CONSTRUCTION SAFEGUARDS

section. The results of each inspection shall be documented and maintained on-site until a certificate of occupancy has been issued. Documentation shall be immediately available on-site for inspection and review.

  1. Any contractors entering the site to perform hot work each day have been instructed in the hot work safety requirements in the California Fire Code, and hot work is performed only in areas approved by the site safety director.

  2. Temporary heating equipment is maintained away from combustible materials in accordance with the equipment manufacturer’s instructions.

  3. Combustible debris, rubbish and waste material is removed from the building in areas where work is not being performed.

  4. Temporary wiring does not have exposed conductors.

  5. Flammable liquids and other hazardous materials are stored in locations that have been approved by the site safety director when not involved in work that is being performed.

  6. Fire apparatus access roads required by the California Fire Code are maintained clear of obstructions that reduce the width of the usable roadway to less than 20 feet (6096 mm).

  7. Fire hydrants are clearly visible from access roads and are not obstructed.

  8. The location of fire department connections to standpipe and in-service sprinkler systems are clearly identifiable from the access road and such connections are not obstructed.

  9. Standpipe systems are in service and continuous to the highest work floor, as specified in Section 1509.

  10. Portable fire extinguishers are available in locations required by Section 1507 and for roofing operations in accordance with the California Fire Code .

  11. Where a fire watch is required, fire watch records complying with the California Fire Code are up-to-date.

[F] 1502.3.1 Violations. Failure to properly conduct, document and maintain documentation required by this section shall constitute an unlawful act in accordance with Section 113.1 and shall result in the issuance of a notice of violation to the site safety director in accordance with Section 113.2. Upon the third offense, the code official is authorized to issue a stop work order in accordance with Section 114, and work shall not resume until satisfactory assurances of future compliance have been presented to and approved by the code official.

Get a plain-English answer with a citation back to this text.

Ask AI about this code
Contents — 2025 California Existing Building Code (Title 24, Part 10)
2025 California Existing Building Code (Title 24, Part 10)
  1. Chapter 1 — ADMINISTRATION
  2. Chapter 2 — DEFINITIONS
  3. Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
  4. Chapter 3A — PROVISIONS FOR ALL COMPLIANCE METHODS
  5. Chapter 4 — REPAIRS
  6. Chapter 4A — REPAIRS
  7. Chapter 5 — PRESCRIPTIVE COMPLIANCE METHOD
  8. Chapter 5A — PRESCRIPTIVE COMPLIANCE METHOD
  9. Chapter 6 — CLASSIFICATION OF WORK
  10. Chapter 7 — ALTERATIONS—LEVEL 1
  11. Chapter 8 — ALTERATIONS—LEVEL 2
  12. Chapter 9 — ALTERATIONS—LEVEL 3
  13. Chapter 10 — CHANGE OF OCCUPANCY
  14. Chapter 11 — ADDITIONS
  15. Chapter 12 — HISTORIC BUILDINGS
  16. Chapter 13 — PERFORMANCE COMPLIANCE METHODS
  17. Chapter 14 — RELOCATED OR MOVED BUILDINGS
  18. Chapter 15 — CONSTRUCTION SAFEGUARDS
  19. Chapter 16 — REFERENCED STANDARDS
  20. Appendix A — GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING B…
  21. Appendix B — SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS FOR EXIS…
  22. Appendix C — GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUIL…
  23. Appendix D — BOARD OF APPEALS
  24. Appendix E — TEMPORARY EMERGENCY USES
  25. Appendix A — GUIDELINES ON FIRE RATINGS OF ARCHAIC MATERIALS A…

GoCodebook provides public access, search, citation, multilingual explanation, and practical interpretation of legally adopted building regulations. It is not a substitute for the official ICC or California code publications.