Appendix C — GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUILDINGS
Section C202 — ROOF DECK ATTACHMENT FOR WOOD ROOFS
2025 California Existing Building Code (Title 24, Part 10) · 2025 edition · updated 2026-07-27 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
[BS] C202.1 Roof decking attachment for one- and two-family dwellings. For one- and two-family dwellings, fastening shall be in accordance with Section C202.1.1 or C202.1.2 as appropriate for the existing construction. The diameter of 8d nails shall be not less than 0.131 inch (3 mm) and the length shall be not less than 2 [1] / 4 inches (57 mm) to qualify for the provisions of this section for existing nails regardless of head shape or head diameter.
[BS] C202.1.1 Sawn lumber or wood plank roofs. Roof decking consisting of sawn lumber or wood planks up to 12 inches (30 cm) wide and secured with not fewer than two nails (minimum size 8d) to each roof framing member it crosses shall be deemed to be sufficiently connected. Sawn lumber or wood plank decking secured with smaller fasteners than 8d nails or with fewer than two nails (minimum size 8d) to each framing member it crosses shall be deemed sufficiently connected if fasteners are added such that two clipped head, round head or ring shank nails (minimum size 8d) are in place on each framing member the nail crosses.
[BS] C202.1.2 Wood structural panel roofs For roof decking consisting of wood structural panels, fasteners and spacings required in Table C202.1.2 shall be deemed to comply with the requirements of Section 706.3.
Supplemental fasteners as required by Table C202.1.2 shall be 8d ring shank nails with round heads and the following minimum dimensions:
- 0.113-inch-nominal (3 mm) shank diameter.
- Ring diameter not less than 0.012 inch (0.3 mm) greater than shank diameter.
- 16 to 20 rings per inch.
- A minimum 0.280-inch (7 mm) full round head diameter.
- Ring shank to extend not less than 1 [1] / 2 inches (38 mm) from the tip of the nail.
- Minimum 2 [1] / 4 -inch (57 mm) nail length.
[BS] TABLE C202.1.2—SUPPLEMENT FASTENERS AT PANEL EDGES AND INTERMEDIATE FRAMING
| EXISTING FASTENERS | EXISTING FASTENER SPACING (EDGE OR INTERMEDIATE SUPPORTS) |
MAXIMUM SUPPLEMENTAL FASTENER SPACING FOR 130 MPH <****Vult ≤ 140 MPH |
MAXIMUM SUPPLEMENTAL FASTENER SPACING FOR INTERIOR ZONEc LOCATIONS FOR MPHVult > 140 MPH AND EDGE ZONES NOT COVERED BY THE COLUMN TO THE RIGHT |
EDGE ZONEd FOR Vult > 160 MPH AND EXPOSURE C, OR Vult > 180 MPH AND EXPOSURE B |
|---|---|---|---|---|
| Staples or 6d | Any | 6″ o.c.b | 6″ o.c.b | 4″ o.c.b at panel edges and 4″ o.c.b at intermediate supports |
| 8d clipped head or round head smooth shank |
6″ o.c. or less | None necessary | None necessary along edges of panels but 6″ o.c.b at interme- diate supports of panel |
4″ o.c.a at panel edges and 4″ o.c.a at intermediate supports |
| 8d clipped head or round head ring shank |
6″ o.c. or less | None necessary | None necessary | 4″ o.c.a at panel edges and 4″ o.c.a at intermediate supports |
| 8d clipped head or round head smooth shank |
Greater than 6″ o.c. | 6″ o.c.a | 6″ o.c.a along panel edges and 6″ o.c.b at intermediate supports of panel |
4″ o.c.a at panel edges and 4″ o.c.a at intermediate supports |
| 8d clipped head or round head ring shank |
Greater than 6″ o.c. | 6″ o.c.a | 6″ o.c.a | 4″ o.c.a at panel edges and 4″ o.c.a at intermediate supports |
| For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s. a. Maximum spacing determined based on existing fasteners and supplemental fasteners. b. Maximum spacing determined based on supplemental fasteners only. c. Interior zone = sheathing that is not located within 4 feet of the perimeter edge of the roof or within 4 feet of each side of a ridge. d. Edge zone = sheathing that is located within 4 feet of the perimeter edge of the roof and within 4 feet of each side of a ridge. |
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX C-28 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CALIFORNIA EXISTING BUILDING CODE – MATRIX ADOPTION TABLE
APPENDIX C
CHAPTER C3 – REFERENCED STANDARDS
Not adopted by the State of California (May be available for adoption by local ordinance. See Section 1.1.11.)
| Adopting Agency | BSC | BSC- CG |
SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Adopting Agency | BSC | BSC- CG |
SFM | 1 | 2 | 1/AC | AC | SS | SS/CC | 1 | 1R | 2 | 3 | 4 | 5 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 | 6 |
| Adopt Entire Chapter | ||||||||||||||||||||||||
| Adopt Entire Chapter as amended (amended sections listed below) |
||||||||||||||||||||||||
| Adopt only those sections that are listed below |
||||||||||||||||||||||||
| Chapter / Section |
The state agency does not adopt sections identified with the following symbol: † The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX C-30 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX C—GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUILDINGS
CHAPTER C3
REFERENCED STANDARDS
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Existing Building Code (Title 24, Part 10)
- 104.11 for consideration of alternative means of compliance.
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 3A — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 4 — REPAIRS
- Chapter 4A — REPAIRS
- Chapter 5 — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 5A — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 6 — CLASSIFICATION OF WORK
- Chapter 7 — ALTERATIONS—LEVEL 1
- Chapter 8 — ALTERATIONS—LEVEL 2
- Chapter 9 — ALTERATIONS—LEVEL 3
- Chapter 10 — CHANGE OF OCCUPANCY
- Chapter 11 — ADDITIONS
- Chapter 12 — HISTORIC BUILDINGS
- Chapter 13 — PERFORMANCE COMPLIANCE METHODS
- Chapter 14 — RELOCATED OR MOVED BUILDINGS
- Chapter 15 — CONSTRUCTION SAFEGUARDS
- Chapter 16 — REFERENCED STANDARDS
- Appendix A — GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING B…
- Appendix B — SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS FOR EXIS…
-
▸ Appendix C — GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUIL…
- Appendix D — BOARD OF APPEALS
- Appendix E — TEMPORARY EMERGENCY USES
- Appendix A — GUIDELINES ON FIRE RATINGS OF ARCHAIC MATERIALS A…