Appendix C — GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUILDINGS
Section C103 — MATERIALS OF CONSTRUCTION
2025 California Existing Building Code (Title 24, Part 10) · 2025 edition · updated 2026-07-27 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
[BS] C103.1 Existing materials. Existing wood materials that will be part of the retrofitting work (such as trusses, rafters, ceiling joists, top plates and wall studs) shall be in sound condition and free from defects or damage that substantially reduces the loadcarrying capacity of the member. Any wood materials found to be damaged or deteriorated shall be strengthened or replaced with new materials to provide a net dimension of sound wood equivalent to its undamaged original dimensions.
[BS] C103.2 New materials. All new materials shall comply with the standards for those materials as specified in the California Build- ing Code or the California Residential Code .
[BS] C103.3 Material specifications for retrofits. Materials for retrofitting gable end walls shall comply with Table C103.3.
[BS] TABLE C103.3—MATERIAL SPECIFICATIONS FOR RETROFITSa
| COMPONENT | MINIMUM SIZE OR THICKNESS |
MINIMUM MATERIAL GRADE | MINIMUM CAPACITY |
|---|---|---|---|
| Anchor blocks, compression blocks and horizontal braces | 2 × 4 nominal lumber | #2 Spruce-Pine-Fir or better | NA |
| Nail plates | 20 gage thickness 8d minimum nail holes |
Galvanized sheet steel | NA |
| Retrofit studs | 2 × 4 nominal lumber | #2 Spruce-Pine-Fir or better | NA |
| Gusset angle | 14 gage thickness | Galvanized sheet steel | 350 pounds uplift and lateral load |
| Stud-to-plate connector | 20 gage thickness | Galvanized sheet steel | 500 pounds uplift |
| Metal plate connectors, straps and anchors | 20 gage thickness | Galvanized sheet steel | NA |
| For SI: 1 pound = 4.4 N. NA = Not Applicable. a. Metal plate connectors, nail plates, stud-to-plate connectors, straps and anchors shall be products approved for connecting wood-to-wood or wood-to-concrete as appropriate. |
[BS] C103.4 Twists in straps. Straps shall be permitted to be twisted or bent where they transition between framing members or connection points. Straps shall be bent only once at a given location though it is permissible that they be bent or twisted at multiple locations along their length.
[BS] C103.5 Fasteners. Fasteners shall meet the requirements of Table C103.5, Sections C103.5.1 and C103.5.2, and shall be permitted to be screws or nails meeting the minimum length requirement shown in the figures and specified in the tables of this appendix. Fastener spacing shall meet the requirements of Section C103.5.3.
[BS]TABLE C103.5—NAIL AND SCREW REQUIREMENTS
| FASTENER TYPE | MINIMUM SHANK DIAMETER | MINIMUM HEAD DIAMETER | MINIMUM FASTENER LENGTH |
|---|---|---|---|
| #8 screws | NA | 0.28 inches | 11/4 inches |
| 8d common nails | 0.131 inches | 0.28 inches | 21/2 inches |
| 10d common nails | 0.148 inches | 0.28 inches | 3 inches |
| For SI: 1 inch = 25.4 mm. NA = Not Applicable. |
[BS] C103.5.1 Screws. Unless otherwise indicated in the appendix, screw sizes and lengths shall be in accordance with Table C103.5. Permissible screws include deck screws and wood screws. Screws shall have not less than 1 inch (25 mm) of thread. Fine threaded screws or drywall screws shall not be permitted. Select the largest possible diameter screw such that the shank adjacent to the head fits through the hole in the strap.
[BS] C103.5.2 Nails. Unless otherwise indicated in this appendix, nail sizes and lengths shall be in accordance with Table C103.5.
[BS] C103.5.3 General fastener spacing. Fastener spacing for shear connections of lumber-to-lumber shall meet the requirements shown in Figure C103.5.3 and the following conditions.
APPENDIX C-4 2025 CALIFORNIA EXISTING BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
APPENDIX C—GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUILDINGS
[BS] FIGURE C103.5.3—FASTENER SPACINGS FOR LUMBER-TO-LUMBER CONNECTIONS OPERATING IN SHEAR PARALLEL TO GRAIN
FASTENER SPACING FOR LUMBER TO LUMBER
CONNECTIONS
OPERATING IN SHEAR PARALLEL TO GRAIN
END DISTANCE MINIMUM 2¹/�″
EDGE DISTANCE MINIMUM ¹/�″
DISTANCE ACROSS GRAIN MINIMUM 1″
DISTANCE PARALLEL TO GRAIN
MINIMUM 2¹/�″
For SI: 1 inch = 25.4 mm.
[BS] C103.5.3.1 General fastener spacing. Fastener spacing shall meet the following conditions except as provided for in Section C103.5.3.
The distance between fasteners and the edge of lumber that is less than 3 [1] / 2 inches (89 mm) deep in the direction of the fastener length shall be not less than [3] / 4 inch (19.1 mm).
- The distance between fasteners and the edge of lumber that is more than 2 inches (51 mm) thick in the direction of the fastener length shall be not less than [1] / 2 inch (12.7 mm).
- The distance between a fastener and the end of lumber shall be not less than 2 [1] / 2 inches (64 mm).
- The distance between fasteners parallel to the grain (center-to-center) shall be not less than 2 [1] / 2 inches (64 mm).
- The distance between fasteners perpendicular to the grain (center-to-center) in lumber that is less than 3 [1] / 2 inches (89 mm) deep in the direction of the fastener length shall be 1 inch (25 mm).
- The distance between fasteners perpendicular to the grain (center-to-center) in lumber that is more than 2 inches (51 mm) thick in the direction of the fastener length shall be [1] / 2 inch (12.7 mm).
distance between fasteners perpendicular to the grain (center-to-center) in lumber that is less than 3 [1] / 2 inches (89 mm) deep in the direction of the fastener length shall be 1 inch (25 mm). 5. The distance between fasteners perpendicular to the grain (center-to-center) in lumber that is more than 2 inches (51 mm) thick in the direction of the fastener length shall be [1] / 2 inch (12.7 mm).
[BS] C103.5.3.2 Wood-to-wood connections of two members each 2 inches or less in thickness. Wood-to-wood connections fastener spacing shall meet the following conditions:
- The distance between fasteners parallel to grain (center-to-center) shall be not less than 2 [1] / 2 inches (64 mm).
- The distance between fasteners across grain (center-to-center) shall be not less than 1 inch (25 mm).
- For wood-to-wood connections of lumber at right angles, fasteners shall be spaced not less than 2 [1] / 2 inches (64 mm) parallel to the grain and 1 inch (25 mm) perpendicular to the grain in any direction.
[BS] C103.5.3.3 Metal connectors for wood-to-wood connections. Metal connectors for wood-to-wood connections shall meet the following conditions.
- Fastener spacing to edge or ends of lumber shall be as dictated by the prefabricated holes in the connectors and the connectors shall be installed in a configuration that is similar to that shown by the connector manufacturer.
- Fasteners in 1 [1] / 4 -inch-wide (32 mm) metal straps that are installed on the narrow face of lumber shall be a minimum 1 / 4 inch (6.4 mm) from either edge of the lumber. Consistent with Section C103.5.3.1, fasteners shall be permitted to be spaced according to the fastener holes fabricated into the strap.
- Fasteners in metal nail plates shall be spaced not less than [1] / 2 inch (12.7 mm) perpendicular to grain and not less than 1 [1] / 2 inches (38 mm) parallel to grain.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Existing Building Code (Title 24, Part 10)
- 104.11 for consideration of alternative means of compliance.
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 3A — PROVISIONS FOR ALL COMPLIANCE METHODS
- Chapter 4 — REPAIRS
- Chapter 4A — REPAIRS
- Chapter 5 — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 5A — PRESCRIPTIVE COMPLIANCE METHOD
- Chapter 6 — CLASSIFICATION OF WORK
- Chapter 7 — ALTERATIONS—LEVEL 1
- Chapter 8 — ALTERATIONS—LEVEL 2
- Chapter 9 — ALTERATIONS—LEVEL 3
- Chapter 10 — CHANGE OF OCCUPANCY
- Chapter 11 — ADDITIONS
- Chapter 12 — HISTORIC BUILDINGS
- Chapter 13 — PERFORMANCE COMPLIANCE METHODS
- Chapter 14 — RELOCATED OR MOVED BUILDINGS
- Chapter 15 — CONSTRUCTION SAFEGUARDS
- Chapter 16 — REFERENCED STANDARDS
- Appendix A — GUIDELINES FOR THE SEISMIC RETROFIT OF EXISTING B…
- Appendix B — SUPPLEMENTARY ACCESSIBILITY REQUIREMENTS FOR EXIS…
-
▸ Appendix C — GUIDELINES FOR THE WIND RETROFIT OF EXISTING BUIL…
- Appendix D — BOARD OF APPEALS
- Appendix E — TEMPORARY EMERGENCY USES
- Appendix A — GUIDELINES ON FIRE RATINGS OF ARCHAIC MATERIALS A…