Section 110.2 — MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT
2025 California Energy Code (Title 24, Part 6) · 2025 edition · updated 2026-07-25 · California
Certification by manufacturers. Any space-conditioning equipment listed in this section may be installed only if the manufacturer has certified to the Commission that the equipment complies with all the applicable requirements of this section.
(a) Efficiency. Equipment shall meet the applicable efficiency requirements in Tables 110.2-A through 110.2-L, subject to the following:
- If more than one efficiency standard is listed for any equipment in Tables 110.2-A through 110.2-L, the equipment shall meet all the applicable standards that are listed; and
- If more than one test method is listed in Tables 110.2-A through 110.2-L, the equipment shall comply with the applicable efficiency standard when tested with each listed test method; and
- Where equipment serves more than one function, it shall comply with the efficiency standards applicable to each function; and
- Where a requirement is for equipment rated at its “maximum rated capacity” or “minimum rated capacity,” the capacity shall be as provided for and allowed by the controls, during steady-state operation. Exception 1 to Section 110.2(a): Water-cooled centrifugal water-chilling packages that are not designed for operation at ANSI/AHRI Standard 550/590 test conditions of 44°F leaving chilled water temperature and 85°F entering condenser water temperature with 3 gallons per minute per ton condenser water flow shall have a maximum full load kW/ton and NPLV ratings adjusted using the following equation: Adjusted maximum full-load kW/ton rating = (full- load kW/ton from Table 110.2-D)/ K adj Adjusted maximum NPLV rating = (IPLV from Table 110.2-D)/ K adj
Where:
K adj = (A) × (B) A = 0.00000014592 × (LIFT) [4] – 0.0000346496 × (LIFT) [3] + 0.00314196 × (LIFT) [2] – 0.147199 × (LIFT) + 3.9302
LIFT = L vg Cond – L vg Evap (°F) L vg Cond = Full-load leaving condenser fluid temperature (°F) L vg Evap = Full-load leaving evaporator fluid temperature (°F) B = (0.0015 × L vg Evap) + 0.934 The adjusted full-load and NPLV values are only applicable for centrifugal chillers meeting all of the following full-load design
ranges:
- Minimum Leaving Evaporator Fluid Temperature: 36°F
- Maximum Leaving Condenser Fluid Temperature: 115°F
- LIFT ≥ 20°F and ≤ 80°F
Centrifugal chillers designed to operate outside of these ranges are not covered by this exception.
Exception 2 to Section 110.2(a): Positive displacement (air-cooled and water-cooled) chillers with a leaving evaporator fluid temperature higher than 32°F shall show compliance with Table 110.2-D when tested or certified with water at standard rating conditions, per the referenced test procedure.
Exception 3 to Section 110.2(a): Equipment primarily serving refrigerated warehouses or commercial refrigeration.
(b) Controls for heat pumps with supplementary heaters.
Control requirements for heat pumps with supplementary heaters in single-family residential buildings are specified in Section 150.0(h)7 and Section 150.0(i)2. Heat pumps with supplementary heaters in nonresidential and multifamily buildings shall have controls:
- That prevent supplementary heater operation when the heating load can be met by the heat pump alone; and
- In which the cut-on temperature for heat pump heating is higher than the cut-on temperature for supplementary heating, and the cut-off temperature for heat pump heating is higher than the cut-off temperature for supplementary heating. Exception 1 to Section 110.2(b): The controls may allow supplementary heater operation during: A. Defrost; and
B. Transient periods such as start-ups and following room thermostat setpoint advance, if the controls provide preferential rate control, intelligent recovery, staging, ramping or another control mechanism designed to preclude the unnecessary operation of supplementary heating.
Exception 2 to Section 110.2(b): Room air-conditioner heat pumps.
40 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
(c) Thermostats. All heating or cooling systems not controlled by a central energy management control system (EMCS) shall have a setback thermostat.
- Setback capabilities. All thermostats shall have a clock mechanism that allows the building occupant to program the temperature setpoints for at least four periods within 24 hours. Thermostats for heat pumps shall meet the requirements of Section 110.2(b).
Exception to Section 110.2(c): Gravity gas wall heaters, gravity floor heaters, gravity room heaters, noncentral electric heaters, fireplaces or decorative gas appliances, wood stoves, room air conditioners and room air-conditioner heat pumps.
(d) Gas-fired and oil-fired furnace standby loss controls. Gas-fired and oil-fired forced-air furnaces with input ratings ≥ 225,000 Btu/hr shall also have an intermittent ignition or interrupted device (IID), and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for furnaces where combustion air is drawn from the conditioned space. All furnaces with input ratings ≥ 225,000 Btu/hr, including electric furnaces, that are not located within the conditioned space shall have jacket losses not exceeding 0.75 percent of the input rating.
upted device (IID), and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for furnaces where combustion air is drawn from the conditioned space. All furnaces with input ratings ≥ 225,000 Btu/hr, including electric furnaces, that are not located within the conditioned space shall have jacket losses not exceeding 0.75 percent of the input rating.
(e) Open and closed-circuit cooling towers. All open and closed-circuit cooling tower installations shall comply with the following:
- Be equipped with conductivity controls that maximize cycles of concentration based on local water quality conditions. Controls shall automate system bleed and chemical feed based on conductivity. Conductivity controllers shall be installed in accordance with manufacturer’s specifications in order to maximize accuracy.
- Documentation of maximum achievable cycles of concentration. Building owners shall document the cycles of concentration achievable based on local water supply conditions as reported annually by the local water supplier, and using the calculations below. The calculations are intended to determine maximum achievable cycles of concentration based on the parameters identified in Table 110.2-A-1. Building owner shall document maximum achievable cycles of concentration on the mechanical compliance form which shall be reviewed and signed by the Professional Engineer (P.E.) of Record. The maximum achievable cycles of concentrations are based on the local water supply quality as reported by the local water supplier, and shall be the minimum of: A. 2,970 divided by the conductivity of the entering make-up water. B. 1,845 divided by the total dissolved solids of the entering make-up water. C. 540 divided by the M-alkalinity excluding galvanized steel of the entering make-up water. D. 450 divided by the M-alkalinity including galvanized steel of the entering make-up water. E. 540 divided by the calcium hardness of the entering make-up water. F. 270 divided by the chlorides of the entering make-up water. G. 225 divided by the sulfates of the entering make-up water. H. 135 divided by the silica of the entering make-up water. I. Langelier Saturation Index = 10 ( --------------------–1 - ∗ [ Log ( M ∗ 0.9 ∗ 1.219) − 0.061105 ∗ Log ( C ∗ 0.8) + 0.55 ∗ Log ( H ∗ M ) + 0.0050325
2.038895
∗ T − 5.95])
where:
C = Conductivity of the entering make-up water.
H = Calcium hardness of the entering make-up water.
M = M-alkalinity excluding galvanized steel of the entering make-up water.
T = Max skin temperature. 3. Cooling towers shall not allow blowdown until one or more of the parameters in Table 110.2-A-1 reaches the maximum value specified:
TABLE 110.2-A-1 RECIRCULATING WATER PROPERTIES
| RECIRCULATING WATER PARAMETERS | MAXIMUM VALUES |
|---|---|
| Conductivity (micro-siemens/cm) | 2,970 micro-siemens/cm |
| Total dissolved solids (ppm) | 1,845 ppm |
| Total alkalinity as CaCO3 (ppm) excluding galvanized steel | 540 ppm |
| Total alkalinity as CaCO3 (ppm) galvanized steel (passivated) | 450 ppm |
| Calcium hardness as CACO3 (ppm) | 540 ppm |
| Chlorides as Cl (ppm) | 270 ppm |
| Sulfates (ppm) | 225 ppm |
| Silica (ppm) | 135 ppm |
| Langelier saturation index (LSI) | 2.5 (LSI) |
- Be equipped with a flow meter with an analog output for flow either hardwired or available through a gateway on the makeup water line.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
- Be equipped with an overflow alarm to prevent overflow of the sump in case of makeup water valve failure. Overflow alarm shall send an audible signal or provide an alert via the energy management control system to the tower operator in case of sump overflow.
- Be equipped with efficient drift eliminators that achieve drift reduction to 0.002 percent of the circulated water volume for counter-flow towers and 0.005 percent for cross-flow towers.
- Conductivity controls and overflow alarm shall be verified according to NA 7.5.18.
Exception to Section 110.2(e): Open and closed-circuit cooling towers with rated capacity < 150 tons.
(f) Low leakage air-handling units. To qualify as a low leakage air-handling unit for use for meeting the requirements for applicable low leakage air-handling unit compliance credit(s) available in the performance standards set forth in Sections 150.1(b) and 140.1, the manufacturer shall certify to the Energy Commission that the air-handling unit meets the specifications in Reference Joint Appendix JA9.
leakage air-handling units.** To qualify as a low leakage air-handling unit for use for meeting the requirements for applicable low leakage air-handling unit compliance credit(s) available in the performance standards set forth in Sections 150.1(b) and 140.1, the manufacturer shall certify to the Energy Commission that the air-handling unit meets the specifications in Reference Joint Appendix JA9.
TABLE 110.2-A—AIR CONDITIONERS AND CONDENSING UNITS—MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE | SIZE CATEGORY | EFFICIENCYa | TEST PROCEDUREb |
|---|---|---|---|
| Air conditioners, air cooled both split system and single package |
≥ 65,000 Btu/h and < 135,000 Btu/h |
11.2 EERa Federal Minimum IEERa |
ANSI/AHRI 340/360 |
| Air conditioners, air cooled both split system and single package |
≥ 135,000 Btu/h and < 240,000 Btu/h |
11.0 EERa Federal Minimum IEERa |
ANSI/AHRI 340/360 |
| Air conditioners, air cooled both split system and single package |
≥ 240,000 Btu/h and < 760,000 Btu/h |
10.0 EERa Federal Minimum IEERa |
10.0 EERa Federal Minimum IEERa |
| Air conditioners, air cooled both split system and single package |
≥ 760,000 Btu/h | 9.7 EERa 12.5 IEERa |
9.7 EERa 12.5 IEERa |
| Air conditioners, water cooled | ≥ 65,000 Btu/h and < 135,000 Btu/h |
Federal Minimum EERa 13.9 IEERa |
ANSI/AHRI 340/360 |
| Air conditioners, water cooled | ≥ 135,000 Btu/h and < 240,000 Btu/h |
Federal Minimum EERa 13.9 IEERa |
ANSI/AHRI 340/360 |
| Air conditioners, water cooled | ≥ 240,000 Btu/h and < 760,000 Btu/h |
Federal Minimum EERa 13.6 IEERa |
ANSI/AHRI 340/360 |
| Air conditioners, water cooled | ≥ 760,000 Btu/h | 12.2 EERa 13.5 IEERa |
ANSI/AHRI 340/360 |
| Air conditioners, evaporatively cooled | ≥ 65,000 Btu/h and < 135,000 Btu/h |
Federal Minimum EERa 12.3 IEERa |
ANSI/AHRI 340/360 |
| Air conditioners, evaporatively cooled | ≥ 135,000 Btu/h and < 240,000 Btu/h |
Federal Minimum EERa 12.2 IEERa |
ANSI/AHRI 340/360 |
| Air conditioners, evaporatively cooled | ≥ 240,000 Btu/h and < 760,000 Btu/h |
Federal Minimum EERa 12.1 IEERa |
ANSI/AHRI 340/360 |
| Air conditioners, evaporatively cooled | ≥ 760,000 Btu/h | 11.7 EERa 11.9 IEERa |
ANSI/AHRI 340/360 |
| Condensing units, air cooled | ≥ 135,000 Btu/h | 10.5 EER Federal Minimum IEER |
ANSI/AHRI 365 |
| Condensing units, water cooled | ≥ 135,000 Btu/h | 13.5 EER Federal Minimum IEER |
13.5 EER Federal Minimum IEER |
| Condensing units, evaporatively cooled | ≥ 135,000 Btu/h | 13.5 EER Federal Minimum IEER |
13.5 EER Federal Minimum IEER |
| a. Deduct 0.2 from the required EERs and IEERs for units with a heating section other than electric resistance heat. b. Applicable test procedure and reference year are provided under the definitions. |
TABLE 110.2-B—HEAT PUMPS—MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE | SIZE CATEGORY | SUBCATEGORY OR RATING CONDITION |
EFFICIENCYa | TEST PROCEDUREb |
|---|---|---|---|---|
| Air cooled (cooling mode), both split system and single package |
≥ 65,000 Btu/h and < 135,000 Btu/h |
11.0 EER Federal Minimum IEER |
AHRI 340/360 | |
| Air cooled (cooling mode), both split system and single package |
≥ 135,000 Btu/h and < 240,000 Btu/h |
10.6 EER Federal Minimum IEER |
10.6 EER Federal Minimum IEER |
|
| Air cooled (cooling mode), both split system and single package |
≥ 240,000 Btu/h | 9.5 EER Federal Minimum IEER |
9.5 EER Federal Minimum IEER |
|
| Water source (cooling mode) |
≥ 65,000 Btu/h and < 135,000 Btu/h |
86ºF entering water | Federal Minimum EER | ISO-13256-1 |
| Groundwater source (cooling mode) |
< 135,000 Btu/h | 59ºF entering water | 18.0 EER | ISO-13256-1 |
42 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-B—HEAT PUMPS—MINIMUM EFFICIENCY REQUIREMENTS—continued
| EQUIPMENT TYPE | SIZE CATEGORY | SUBCATEGORY OR RATING CONDITION |
EFFICIENCYa | TEST PROCEDUREb |
|---|---|---|---|---|
| Ground source (cooling mode) |
< 135,000 Btu/h | 77ºF entering water | 14.1 EER | ISO-13256-1 |
| Water source water-to-water (cooling mode) |
< 135,000 Btu/h | 86ºF entering water | 10.6 EER | ISO-13256-2 |
| Groundwater source water-to-water (cooling mode) |
< 135,000 Btu/h | 59ºF entering water | 16.3 EER | ISO-13256-2 |
| Ground source brine-to-water (cooling mode) |
< 135,000 Btu/h | 77ºF entering water | 12.1 EER | ISO-13256-2 |
| Air cooled (heating mode) Split system and single package |
≥ 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) |
47°F db/43°F wb outdoor air |
Federal Minimum COP | AHRI 340/360 |
| Air cooled (heating mode) Split system and single package |
≥ 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) |
17°F db/15°F wb outdoor air |
2.25 COP | 2.25 COP |
| Air cooled (heating mode) Split system and single package |
≥ 135,000 Btu/h and < 240,000 Btu/h (cooling capacity) |
47°F db/43°F wb outdoor air |
Federal Minimum COP | Federal Minimum COP |
| Air cooled (heating mode) Split system and single package |
≥ 240,000 Btu/h and < 760,000 Btu/h |
≥ 240,000 Btu/h and < 760,000 Btu/h |
Federal Minimum COP | Federal Minimum COP |
| Air cooled (heating mode) Split system and single package |
≥ 135,000 Btu/h (cooling capacity) |
17°F db/15°F wb outdoor air |
2.05 COP | 2.05 COP |
| Water source (heating mode) |
< 135,000 Btu/h (cooling capacity) |
68ºF entering water | Federal Minimum COP | ISO-13256-1 |
| Water source (heating mode) |
≥ 135,000 Btu/h and < 240,000 Btu/h |
68ºF entering water | Federal Minimum COP | ISO-13256-1 |
| Groundwater source (heating mode) |
< 135,000 Btu/h (cooling capacity) |
50ºF entering water | 3.7 COP | ISO-13256-1 |
| Ground source (heating mode) |
< 135,000 Btu/h (cooling capacity) |
32ºF entering water | 3.2 COP | ISO-13256-1 |
| Water source water-to-water (heating mode) |
< 135,000 Btu/h (cooling capacity) |
68ºF entering water | 3.7 COP | ISO-13256-2 |
| Groundwater source water-to- water (heating mode) |
< 135,000 Btu/h (cooling capacity) |
50ºF entering water | 3.1 COP | ISO-13256-2 |
| Ground source brine-to-water (heating mode) |
< 135,000 Btu/h (cooling capacity) |
32ºF entering water | 2.5 COP | ISO-13256-2 |
| a. Deduct 0.2 from the required EERs and IEERs for units with a heating section other than electric resistance heat. b. Applicable test procedure and reference year are provided under the definitions. |
TABLE 110.2-C—AIR-COOLED GAS-ENGINE HEAT PUMPS
| EQUIPMENT TYPE | SIZE CATEGORY | SUBCATEGORY OR RATING CONDITION |
EFFICIENCY | TEST PROCEDUREa |
|---|---|---|---|---|
| Air-cooled gas-engine heat pump (cooling mode) |
All capacities | 95°F db outdoor air | 0.60 COP | ANSI Z21.40.4A |
| Air-cooled gas-engine heat pump (heating mode) |
All capacities | 47°F db/43°F wb outdoor air | 0.72 COP | ANSI Z21.40.4A |
| a. Applicable test procedure and reference year are provided under the definitions. |
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-D—WATER CHILLING PACKAGES—MINIMUM EFFICIENCY REQUIREMENTSa, b
| EQUIPMENT TYPE | SIZE CATEGORY | PATH A EFFICIENCYa, b |
PATH B EFFICIENCYa, b |
TEST PROCEDUREc |
|---|---|---|---|---|
| Air cooled, with condenser electrically operated |
< 150 tons | ≥ 10.100 EER ≥ 13.700 IPLV |
≥ 9.700 EER ≥ 15.800 IPLV |
AHRI 550/590 |
| Air cooled, with condenser electrically operated |
≥ 150 tons | ≥ 10.100 EER ≥ 14.000 IPLV |
≥ 9.700 EER ≥ 16.100 IPLV |
≥ 9.700 EER ≥ 16.100 IPLV |
| Air cooled, without condenser electrically operated |
All capacities | Air-cooled chillers without condensers must be rated with matching condensers and comply with the air-cooled chiller efficiency requirements. |
Air-cooled chillers without condensers must be rated with matching condensers and comply with the air-cooled chiller efficiency requirements. |
AHRI 550/590 |
| Water cooled, electrically operated reciprocating |
All capacities | Reciprocating units must comply with the water- cooled positive displacement efficiency requirements. |
Reciprocating units must comply with the water- cooled positive displacement efficiency requirements. |
AHRI 550/590 |
| Water cooled, electrically operated, positive displacement |
< 75 tons | ≤ 0.750 kW/ton ≤ 0.600 IPLV |
≤ 0.780 kW/ton ≤ 0.500 IPLV |
AHRI 550/590 |
| Water cooled, electrically operated, positive displacement |
≥ 75 tons and < 150 tons |
≤ 0.720 kW/ton ≤ 0.560 IPLV |
≤ 0.750 kW/ton ≤ 0.490 IPLV |
≤ 0.750 kW/ton ≤ 0.490 IPLV |
| Water cooled, electrically operated, positive displacement |
≥ 150 tons and < 300 tons |
≤ 0.660 kW/ton ≤ 0.540 IPLV |
≤ 0.680 kW/ton ≤ 0.440 IPLV |
≤ 0.680 kW/ton ≤ 0.440 IPLV |
| Water cooled, electrically operated, positive displacement |
≥ 300 tons and < 300 tons |
≤ 0.610 kW/ton ≤ 0.520 IPLV |
≤ 0.625 kW/ton ≤ 0.410 IPLV |
≤ 0.625 kW/ton ≤ 0.410 IPLV |
| Water cooled, electrically operated, positive displacement |
≥ 600 tons | ≤ 0.560 kW/ton ≤ 0.500 IPLV |
≤ 0.585 kW/ton ≤ 0.380 IPLV |
≤ 0.585 kW/ton ≤ 0.380 IPLV |
| Water cooled, electrically operated, centrifugal |
> 150 ton | ≤ 0.610 kW/ton ≤ 0.550 IPLV |
≤ 0.695 kW/ton ≤ 0.440 IPLV |
≤ 0.695 kW/ton ≤ 0.440 IPLV |
| Water cooled, electrically operated, centrifugal |
≥ 150 tons and < 300 tons |
≤ 0.610 kW/ton ≤ 0.550 IPLV |
≤ 0.635 kW/ton ≤ 0.400 IPLV |
≤ 0.635 kW/ton ≤ 0.400 IPLV |
| Water cooled, electrically operated, centrifugal |
≥ 300 tons and < 400 tons |
≤ 0.560 kW/ton ≤ 0.520 IPLV |
≤ 0.595 kW/ton ≤ 0.390 IPLV |
≤ 0.595 kW/ton ≤ 0.390 IPLV |
| Water cooled, electrically operated, centrifugal |
≥ 400 tons and < 600 tons |
≤ 0.560 kW/ton ≤ 0.500 IPLV |
≤ 0.585 kW/ton ≤ 0.380 IPLV |
≤ 0.585 kW/ton ≤ 0.380 IPLV |
| Water cooled, electrically operated, centrifugal |
≥ 600 tons | ≤ 0.560 kW/ton ≤ 0.500 IPLV |
≤ 0.585 kW/ton ≤ 0.380 IPLV |
≤ 0.585 kW/ton ≤ 0.380 IPLV |
| Air cooled absorption single effect | All capacities | ≥ 0.600 COP | N.A.d | AHRI 560 |
| Water cooled absorption single effect | All capacities | ≥ 0.700 COP | N.A.d | N.A.d |
| Absorption double effect, indirect-fired |
All capacities | ≥ 1.000 COP ≥ 1.050 IPLV |
N.A.d | N.A.d |
| Absorption double effect, direct-fired |
All capacities | ≥ 1.000 COP ≥ 1.000 IPLV |
N.A.d | N.A.d |
| Water cooled gas engine driven chiller |
All capacities | ≥ 1.2 COP ≥ 2.0 IPLV |
N.A.d | ANSI Z21.40.4 |
| a. No requirements for: • Centrifugal chillers with design leaving evaporator temperature < 36°F; or • Positive displacement chillers with design leaving fluid temperature ≤ 32°F; or • Absorption chillers with design leaving fluid temperature < 40°F. b. Must meet the minimum requirements of Path A or Path B. However, both the full load (COP) and IPLV must be met to fulfill the requirements of the applicable path. c. See Section 100.1 for definitions. d. N.A. means not applicable. |
44 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-E—PERFORMANCE REQUIREMENTS FOR HEAT REJECTION EQUIPMENT
| EQUIPMENT TYPE | TOTAL SYSTEM HEAT REJECTION CAPACITY AT RATED CONDITIONS |
SUBCATEGORY OR RATING CONDITION |
PERFORMANCE REQUIREDa, b, c, d |
TEST PROCEDUREe |
|---|---|---|---|---|
| Propeller or axial fan open- circuit cooling towers |
All | 95°F entering water 85°F leaving water 75°F entering air wb |
≥ 42.1 gpm/hp | CTI ATC-105 and CTI STD-201 RS |
| Centrifugal fan open-circuit cooling towers |
All | 95°F entering water 85°F leaving water 75°F entering air wb |
≥ 20.0 gpm/hp | ≥ 20.0 gpm/hp |
| Propeller or axial fan closed- circuit cooling towers |
All | 102°F entering water 90°F leaving water 75°F entering air wb |
≥ 16.1 gpm/hp | CTI ATC-105S and CTI STD-201 RS |
| Centrifugal fan closed- circuit cooling towers |
All | 102°F entering water 90°F leaving water 75°F entering air wb |
≥ 7.0 gpm/hp | ≥ 7.0 gpm/hp |
| Propeller or axial fan evaporative condensers |
All | R-448A test fluid 165°F entering gas temp 105°F condensing temp 75°F entering air wb |
≥ 157,000 Btu/h**·** hp |
CTI ATC-106 |
| Propeller or axial fan evaporative condensers |
All | Ammonia test fluid 140°F entering gas temp 96.3°F condensing temp 75°F entering air wb |
≥ 134,000 Btu/h**·** hp |
≥ 134,000 Btu/h**·** hp |
| Centrifugal fan evaporative condensers |
All | R-448A test fluid 165°F entering gas temp 105°F condensing temp 75°F entering air wb |
≥ 135,000 Btu/h**·** hp |
≥ 135,000 Btu/h**·** hp |
| Centrifugal fan evaporative condensers |
All | Ammonia test fluid 140°F entering gas temp 96.3°F condensing temp 75°F entering air wb |
≥ 110,000 Btu/h**·** hp |
≥ 110,000 Btu/h**·** hp |
| Air cooled condensers | All | 125°F condensing temperature 190°F entering gas temperature 15°F subcooling 95°F entering dry-bulb |
≥ 176,000 Btu/h·hp | AHRI 460 |
| Propeller or axial fan dry coolers (air-cooled fluid coolers) |
All | 115°F entering water 105°F leaving water 95°F entering air db |
≥ 4.5 gpm/hp | CTI ATC-105DS |
a. For purposes of this table, open-circuit cooling tower performance is defined as the water flow rating of the tower at the given rated conditions divided by the fan motor
nameplate power.
b. For purposes of this table, closed-circuit cooling tower performance is defined as the process water flow rating of the tower at the given rated conditions divided by the sum
of the fan motor nameplate rated power and the integral spray pump motor nameplate power.
c. For purposes of this table, dry cooler performance is defined as the process water flow rating of the unit at the given thermal rating condition divided by the total fan motor
nameplate power of the unit and air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the fan motor nameplate power of the unit.
d. Open cooling towers shall be tested using the test procedures in CTI ATC-105. Performance of factory-assembled open cooling towers shall be either certified as base models
as specified in CTI STD-201 or verified by testing in the field by a CTI approved testing agency. Open factory assembled cooling towers with custom options added to a CTI
certified base model for the purpose of safe maintenance or to reduce environmental or noise impact shall be rated at 90 percent of the CTI certified performance of the asso-
ciated base model or at the manufacturer’s stated performance, whichever is less. Base models of open factory-assembled cooling towers are open cooling towers configured
in exact accordance with the Data of Record submitted to CTI as specified by CTI STD-201. There are no certification requirements for field-erected cooling towers.
e. Applicable test procedure and reference year are provided under the definitions. For refrigerated warehouses or commercial refrigeration applications, condensers shall
comply with requirements specified by Section 120.6(a) or Section 120.6(b).
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-F —ELECTRICALLY OPERATED VARIABLE REFRIGERANT FLOW (VRF) AIR CONDITIONERS MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE |
SIZE CATEGORY | HEATING ** SECTION TYPE** |
SUBCATEGORY OR RATING CONDITION |
MINIMUM EFFICIENCY |
TEST PROCEDUREa |
|---|---|---|---|---|---|
| VRF Air conditioners, Air cooled |
< 65,000 Btu/h | All | VRF multisplit system | 13.0 SEER Before 1/1/2023 Federal Minimum SEER2 On or After 1/1/2023 |
AHRI 1230 Before 1/1/2023 AHRI 210/240 On or After 1/1/2023 |
| VRF Air conditioners, Air cooled |
≥ 65,000 Btu/h and < 135,000 Btu/h |
Electric resistance (or none) |
VRF multisplit system | 10.5 EER Federal Minimum IEERb |
AHRI 1230 |
| VRF Air conditioners, Air cooled |
≥ 135,000 Btu/h and < 240,000 Btu/h |
Electric resistance (or none) |
VRF multisplit system | 10.3 EER Federal Minimum IEERb |
10.3 EER Federal Minimum IEERb |
| VRF Air conditioners, Air cooled |
≥ 240,000 Btu/h | Electric resistance (or none) |
VRF multisplit system | 9.5 EER Federal Minimum IEERb |
9.5 EER Federal Minimum IEERb |
| a. Applicable test procedure and reference year are provided under the definitions. b. IEERs are only applicable to equipment with capacity control as specified in ANSI/AHRI 1230 test procedures. |
TABLE 110.2-G —ELECTRICALLY OPERATED VARIABLE REFRIGERANT FLOW
AIR-TO-AIR AND APPLIED HEAT PUMPS—MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE | SIZE CATEGORY | HEATING ** SECTION TYPE** |
SUBCATEGORY OR RATING CONDITION |
MINIMUM EFFICIENCY |
TEST PROCEDUREa, b |
|---|---|---|---|---|---|
| VRF Air cooled (cooling mode) |
< 65,000 Btu/h | All | VRF multisplit system | 13.0 SEER Before 1/1/2023 Federal Minimum SEER2 On or After 1/1/2023 |
AHRI 1230 Before 1/1/2023 AHRI 210/240 On or After 1/1/2023 |
| VRF Air cooled (cooling mode) |
≥ 65,000 Btu/h and < 135,000 Btu/h |
Electric resistance (or none) |
VRF multisplit systema | 10.3 EER Federal Minimum IEERc |
AHRI 1230 |
| VRF Air cooled (cooling mode) |
≥ 135,000 Btu/h and < 240,000 Btu/h |
Electric resistance (or none) |
VRF multisplit systema | 9.9 EER Federal Minimum IEERc |
9.9 EER Federal Minimum IEERc |
| VRF Air cooled (cooling mode) |
≥ 240,000 Btu/h | Electric resistance (or none) |
VRF multisplit systema | 9.1 EER Federal Minimum IEERc |
9.1 EER Federal Minimum IEERc |
| VRF Water source (cooling mode) |
< 65,000 Btu/h | All | VRF multisplit systema 86ºF entering water |
12.0 EER Federal Minimum IEERc |
AHRI 1230 |
| VRF Water source (cooling mode) |
≥ 65,000 Btu/h and < 135,000 Btu/h |
All | VRF multisplit systema 86ºF entering water |
12.0 EER Federal Minimum IEERc |
12.0 EER Federal Minimum IEERc |
| VRF Water source (cooling mode) |
≥ 135,000 Btu/h and < 240,000 Btu/h |
All | VRF multisplit systema 86ºF entering water |
10.0 EER Federal Minimum IEERc |
10.0 EER Federal Minimum IEERc |
| VRF Water source (cooling mode) |
≥ 240,000 Btu/h | All | VRF multisplit systema 86ºF entering water |
10.0 EER Federal Minimum IEER |
10.0 EER Federal Minimum IEER |
| VRF Groundwater source (cooling mode) |
< 135,000 Btu/h | All | VRF multisplit systema 59ºF entering water |
16.2 EER | AHRI 1230 |
| VRF Groundwater source (cooling mode) |
≥ 135,000 Btu/h | All | VRF multisplit systema 59ºF entering water |
13.8 EER | 13.8 EER |
| VRF Ground source (cooling mode) |
< 135,000 Btu/h | All | VRF multisplit systema 77ºF entering water |
13.4 EER | AHRI 1230 |
| VRF Ground source (cooling mode) |
≥ 135,000 Btu/h | All | VRF multisplit systema 77ºF entering water |
11.0 EER | 11.0 EER |
| VRF Air cooled (heating mode) |
< 65,000 Btu/h (cooling capacity) |
— | VRF multisplit system | 7.7 HSPF Before 1/1/2025 7.5 HSPF2 On or after 1/1/2025 |
AHRI 1230 |
| VRF Air cooled (heating mode) |
≥ 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) |
— | VRF multisplit system 47ºF db/43ºF wb outdoor air |
Federal Minimum COP | Federal Minimum COP |
| VRF Air cooled (heating mode) |
≥ 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) |
— | VRF multisplit system 17ºF db/15ºF wb outdoor air |
2.25 COP | 2.25 COP |
| VRF Air cooled (heating mode) |
≥ 135,000 Btu/h (cooling capacity) |
— | VRF multisplit system 47ºF db/43ºF wb outdoor air |
Federal Minimum COP | Federal Minimum COP |
| VRF Air cooled (heating mode) |
≥ 135,000 Btu/h (cooling capacity) |
— | VRF multisplit system 17ºF db/15ºF wb outdoor air |
2.05 COP | 2.05 COP |
46 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-G —ELECTRICALLY OPERATED VARIABLE REFRIGERANT FLOW
AIR-TO-AIR AND APPLIED HEAT PUMPS—MINIMUM EFFICIENCY REQUIREMENTS—continued
| EQUIPMENT TYPE | SIZE CATEGORY | HEATING ** SECTION TYPE** |
SUBCATEGORY OR RATING CONDITION |
MINIMUM EFFICIENCY |
TEST PROCEDUREa, b |
|---|---|---|---|---|---|
| VRF Water source (heating mode) |
< 65,000 Btu/h (cooling capacity) |
— | VRF multisplit system 68ºF entering water |
Federal Minimum COP | AHRI 1230 |
| VRF Water source (heating mode) |
≥ 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) |
— | VRF multisplit system 68ºF entering water |
Federal Minimum COP | Federal Minimum COP |
| VRF Water source (heating mode) |
≥ 135,000 Btu/h and < 240,000 Btu/h (cooling capacity) |
— | VRF multisplit system 68ºF entering water |
Federal Minimum COP | Federal Minimum COP |
| VRF Water source (heating mode) |
≥ 240,000 Btu/h (cooling capacity) |
— | VRF multisplit system 68ºF entering water |
Federal Minimum COP | Federal Minimum COP |
| VRF Groundwater source (heating mode) |
< 135,000 Btu/h (cooling capacity) |
— | VRF multisplit system 50ºF entering water |
3.6 COP | AHRI 1230 |
| VRF Groundwater source (heating mode) |
≥ 135,000 Btu/h (cooling capacity) |
— | VRF multisplit system 50ºF entering water |
3.3 COP | 3.3 COP |
| VRF Ground source (heating mode) |
< 135,000 Btu/h (cooling capacity) |
— | VRF multisplit system 32ºF entering water |
3.1 COP | AHRI 1230 |
| VRF Ground source (heating mode) |
≥ 135,000 Btu/h (cooling capacity) |
— | VRF multisplit system 32ºF entering water |
2.8 COP | 2.8 COP |
| a. Deduct 0.2 from the required EERs and IEERs for variable refrigerant flow (VRF) multisplit system units with a heating recovery section. b. Applicable test procedure and reference year are provided under the definitions. c. IEERs are only applicable to equipment with capacity control as specified in ANSI/AHRI 1230 test procedures. |
TABLE 110.2-H—DX-DOAS UNITS, SINGLE-PACKAGE AND REMOTE CONDENSER—MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE |
ENERGY RECOVERY | SUBCATEGORY OR RATING CONDITION |
MINIMUM EFFICIENCY |
TEST PROCEDUREa |
|---|---|---|---|---|
| Air cooled (dehumidification mode) |
Without energy recovery | NA | 3.8 ISMRE2 | AHRI 920 |
| Air source heat pumps (dehumidification mode) |
Without energy recovery | NA | 3.8 ISMRE2 | AHRI 920 |
| Water cooled (dehumidification mode) |
Without energy recovery | Cooling tower condenser water | 4.7 ISMRE2 | AHRI 920 |
| Water source heat pump (dehumidification mode) |
Without energy recovery | Ground source, closed and open loop | 4.6 ISMRE2 | AHRI 920 |
| Water source heat pump (dehumidification mode) |
Without energy recovery | Water source | 3.8 ISMRE2 | AHRI 920 |
| Air source heat pumps (heating mode) |
Without energy recovery | NA | 2.05 ISCOP2 | AHRI 920 |
| Water source heat pump (heating mode) |
Without energy recovery | Ground source, closed and open loop | 2.13 ISCOP2 | AHRI 920 |
| Water source heat pump (heating mode) |
Without energy recovery | Water source | 2.13 ISCOP2 | AHRI 920 |
| Air cooled (dehumidification mode) |
With energy recovery | NA | 5 ISMRE2 | AHRI 920 |
| Air source heat pumps (dehumidification mode) |
With energy recovery | NA | 5 ISMRE2 | AHRI 920 |
| Water cooled (dehumidification mode) |
With energy recovery | Cooling tower condenser water | 5.1 ISMRE2 | AHRI 920 |
| Water source heat pump (dehumidification mode) |
With energy recovery | Ground source, closed and open loop | 5.0 ISMRE2 | AHRI 920 |
| Water source heat pump (dehumidification mode) |
With energy recovery | Water source | 4.6 ISMRE2 | AHRI 920 |
| Air source heat pumps (heating mode) |
With energy recovery | NA | 3.2 ISCOP2 | AHRI 920 |
| Water source heat pump (heating mode) |
With energy recovery | Ground source, closed and open loop | 3.5 ISCOP2 | AHRI 920 |
| Water source heat pump (heating mode) |
With energy recovery | Water source | 4.04 ISCOP2 | AHRI 920 |
| a. Applicable test procedure and reference year are provided under the definitions. |
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
TABLE 110.2-I—HEAT PUMP AND HEAT RECOVERY CHILLER PACKAGES, COOLING OPERATION– MINIMUM EFFICIENCY REQUIREMENTS
| EQUIPMENT TYPE | SIZE CATEGORY REFRIGERATING CAPACITYa, TONR |
COOLING OPERATION EFFICIENCYb, c, d, e, AIR SOURCE EER (FL/IPLV), Btu/Wh, LIQUID SOURCE POWER INPUT PER CAPACITY (FL/IPLV), kW/TONR PATH A |
COOLING OPERATION EFFICIENCYb, c, d, e, AIR SOURCE EER (FL/IPLV), Btu/Wh, LIQUID SOURCE POWER INPUT PER CAPACITY (FL/IPLV), kW/TONR PATH B |
TEST PROCEDURE |
|
|---|---|---|---|---|---|
| Air source | < 150 | > 5.595 FL |
> 13.02 IPLV.IP | > 9.215 FL > 15.01 IPLV.IP |
AHRI/550/590 |
| Air source | > 150 | > 5.595 FL > 13.30 IPLV.IP |
> 9.215 FL > 15.30 IPLV.IP |
AHRI/550/590 | |
| Liquid source electrically operated positive displacement |
> 11.25f and < 150 | < 0.7895 FL < 0.6316 IPLV.IP |
< 0.8211 FL < 0.5263 IPLV.IP |
AHRI/550/590 | |
| Liquid source electrically operated positive displacement |
> 150 and < 300 | < 0.7579 FL < 0.5895 IPLV.IP |
< 0.7895 FL < 0.5158 IPLV.IP |
AHRI/550/590 | |
| Liquid source electrically operated positive displacement |
> 300 and < 400 | < 0.6947 FL < 0.5684 IPLV.IP |
< 0.7158 FL < 0.4632 IPLV.IP |
AHRI/550/590 | |
| Liquid source electrically operated positive displacement |
> 400 and < 600 | < 0.6421 FL < 0.5474 IPLV.IP |
< 0.6579 FL < 0.4316 IPLV.IP |
AHRI/550/590 | |
| Liquid source electrically operated positive displacement |
> 600 | < 0.5895 FL < 0.5263 IPLV.IP |
< 0.6158 FL < 0.4000 IPLV.IP |
AHRI/550/590 | |
| Liquid source electrically operated centrifugal |
> 11.25f and < 150 | < 0.6421 FL < 0.5789 IPLV.IP |
< 0.7316 FL < 0.4632 IPLV.IP |
AHRI/550/590 | |
| Liquid source electrically operated centrifugal |
> 150 and < 300 | < 0.6190 FL < 0.5748 IPLV.IP |
< 0.6684 FL < 0.4211 IPLV.IP |
AHRI/550/590 | |
| Liquid source electrically operated centrifugal |
> 300 and < 400 | < 0.5895 FL < 0.5526 IPLV.IP |
< 0.6263 FL < 0.4105 IPLV.IP |
AHRI/550/590 | |
| Liquid source electrically operated centrifugal |
> 400 and < 600 | < 0.5895 FL < 0.5263 IPLV.IP |
< 0.6158 FL < 0.4000 IPLV.IP |
AHRI/550/590 | |
| Liquid source electrically operated centrifugal |
> 600 | < 0.5895 FL < 0.5263 IPLV.IP |
< 0.6158 FL < 0.4000 IPLV.IP |
AHRI/550/590 |
a.
The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load external to the chill-
ing package.
b.
Cooling rating conditions are standard rating conditions defined in AHRI 550/590 (I-P), Table 4, except for liquid cooled centrifugal chilling packages, which can adjust cooling
efficiency for nonstandard rating conditions using the_Kadj_ procedure in accordance with Section 110.2(a).
c.
For cooling operation, compliance with both the FL and IPLV is required, but only compliance with Path A or Path B cooling efficiency is required.
d.
For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required.
e.
For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recover COPHR is only
required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling-only performance
is required as defined in Notes b and c.
f.
Water-to-water heat pumps with a capacity less than 135,000 Btu/h are included in Table 110.2-B, Heat Pumps—Minimum Efficiency Requirements.
48 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
| TABLE 110.2-J—HEAT PUMP AND HEAT RECOVERY CHILLER PACKAGES, HEAT PUMP, HEATING OPERATION—MINIMUM EFFICIENCY REQUIREMENTS |
||||||
|---|---|---|---|---|---|---|
| Equipment Type: Air source | Equipment Type: Air source | Equipment Type: Air source | Equipment Type: Air source | Equipment Type: Air source | Equipment Type: Air source | Equipment Type: Air source |
| SIZE CATEGORY REFRIGERATING CAPACITYa, TONR |
HEATING SOURCE CONDITIONS (LEAVING LIQUID) OR OAT (db/wb)b,°F |
HEAT PUMP HEATING-FULL LOAD HEATING EFFICIENCY (COPH) c, d, e, f, g, W/W, ENTERING/LEAVING HEATING LIQUID TEMPERATURE, LOW, 95°F/105°F |
HEAT PUMP HEATING FULL LOAD HEATING EFFICIENCY (COPH) c, d, e, f, g, W/W, ENTERING/LEAVING HEATING LIQUID TEMPERATURE, MEDIUM, 105°F/120°F |
HEAT PUMP HEATING-FULL LOAD HEATING EFFICIENCY (COPH) c, d, e, f, g, W/W, ENTERING/LEAVING HEATING LIQUID TEMPERATURE, HIGH, 120°F/140°F |
HEAT PUMP HEATING-FULL LOAD HEATING EFFICIENCY (COPH) c, d, e, f, g, W/W, ENTERING/LEAVING HEATING LIQUID TEMPERATURE, BOOST, 120°F/140°F |
TEST PROCEDURE |
| < 150 | 47 db 43 wb |
> 3.29 | > 2.77 | > 2.31 | NAj | AHRI 550/590 |
| < 150 | 17 db 15 wb |
> 2.029 | > 1.775 | > 1.483 | NAj | AHRI 550/590 |
| > 150 | 47 db 43 wb |
> 3.29 | > 2.77 | > 2.31 | NAj | AHRI 550/590 |
| > 150 | 17 db 15 wb |
> 2.029 | > 1.775 | > 1.483 | NAj | AHRI 550/590 |
| Equipment Type: Liquid source electrically operated positive displacement | ||||||
| > 11.25h and < 150 | 44i | > 4.64 | > 3.68 | > 2.68 | NAj | AHRI 550/590 |
| > 11.25 h and < 150 | 65 i | NAj | NAj | NAj | > 3.55 | AHRI 550/590 |
| > 150 and < 300 | 44i | > 4.64 | > 3.68 | > 2.68 | NAj | AHRI 550/590 |
| > 150 and < 300 | 65 i | NAj | NAj | NAj | > 3.55 | AHRI 550/590 |
| > 300 and < 400 | 44i | > 4.64 | > 3.68 | > 2.68 | NAj | AHRI 550/590 |
| > 300 and < 400 | 65 i | NAj | NAj | NAj | > 3.55 | AHRI 550/590 |
| > 400 and < 600 | 44i | > 4.93 | > 3.96 | > 2.97 | NAj | AHRI 550/590 |
| > 400 and < 600 | 65 i | NAj | NAj | NAj | > 3.9 | AHRI 550/590 |
| > 600 | 44i | > 4.93 | > 3.96 | > 2.97 | NAg | AHRI 550/590 |
| > 600 | 65 i | NAj | NAj | NAj | > 3.9 | AHRI 550/590 |
| Equipment Type: Liquid source electrically operated centrifugal | ||||||
| > 11.25h and < 150 | 44i | > 4.64 | > 3.68 | > 2.68 | NAj | AHRI 550/590 |
| > 11.25 h and < 150 | 65 i | NAj | NAj | NAj | > 3.55 | AHRI 550/590 |
| > 150 and < 300 | 44i | > 4.64 | > 3.68 | > 2.68 | NAj | AHRI 550/590 |
| > 150 and < 300 | 65 i | NAj | NAj | NAj | > 3.55 | AHRI 550/590 |
| > 300 and < 400 | 44i | > 4.64 | > 3.68 | > 2.68 | NAj | AHRI 550/590 |
| > 300 and < 400 | 65 i | NAg | NAg | NAg | > 3.55 | AHRI 550/590 |
| > 400 and < 600 | 44i | > 4.93 | > 3.96 | > 2.97 | NAj | AHRI 550/590 |
| > 400 and < 600 | 65 i | NAj | NAj | NAj | > 3.9 | AHRI 550/590 |
| > 600 | 44i | > 4.93 | > 3.96 | > 2.97 | NAj | AHRI 550/590 |
| > 600 | 65 i | NAj | NAj | NAj | > 3.9 | AHRI 550/590 |
a. The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load external to the chill-
ing package.
b. For air source heat pumps, compliance with both the 47°F and 17°F heating source outdoor air temperature (OAT) rating efficiency is required for heating.
c. Heating full-load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, includes the impact of defrost for air source heating ratings.
d. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required.
e. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recover COPHR is
only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling-only perfor-
mance is required as defined in Notes b and c of Table 110.2-I.
f. For applications where the chilling package is installed to operate only in heating, compliance only with the heating performance COPH is required at only one of the heating
AHRI 550/590 (I-P) standard rating conditions of Low, Medium, High, or Boost. Compliance with cooling performance is not required.
g. For heat pump chilling package applications where the cooling capacity is not being used for conditioning, compliance with the heating performance COPH is only required at
one of the heating AHRI 550/590 (I-P) standard rating conditions of Low, Medium, High, or Boost. Compliance with the cooling performance is required as defined in Notes b
and c of Table 110.2-I, except as noted in Note f.
h. Water-to-water heat pumps with a capacity less than 135,000 Btu/h are included in Table 110.2-B, Heat Pumps—Minimum Efficiency Requirements.
i. Source leaving liquid temperature.
1. The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air-to-water heat pump shall be the flow rate determined during the full load cooling rating.
2. The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates
from the cooling operation full-load rating.
3. For heating-only fluid-to-fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54°F and a leaving liquid temperature of 44°F
shall be used.
j. NA means the requirements are not applicable.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
| TABLE 110.2-K—HEAT PUMP AND HEAT RECOVERY CHILLER PACKAGES, SIMULTANEOUS COOLING AND HEATING, HEATING OPERATION—MINIMUM EFFICIENCY REQUIREMENTS |
||||||
|---|---|---|---|---|---|---|
| Equipment Type: Air source | Equipment Type: Air source | Equipment Type: Air source | Equipment Type: Air source | Equipment Type: Air source | Equipment Type: Air source | Equipment Type: Air source |
| SIZE CATEGORY REFRIGERATING **CAPACITYa, ** TONR |
HEATING SOURCE CONDITIONS (LEAVING LIQUID) OR OAT (db/wb)b,°F |
SIMULTANEOUS COOLING AND HEATING FULL-LOAD ** EFFICIENCY** (COPSHC) c, d, e, f, g, W/W, ENTERING/LEAVING HEATING LIQUID TEMPERATURE, LOW, 95°F/105°F |
SIMULTANEOUS COOLING AND HEATING FULL-LOAD ** EFFICIENCY** (COPH) c, d, e, f, g, W/W, ENTERING/LEAVING HEATING LIQUID TEMPERATURE, MEDIUM, 105°F/120°F |
SIMULTANEOUS COOLING AND HEATING FULL-LOAD ** EFFICIENCY** (COPSHC) c, d, e, f, g, W/W, ENTERING/LEAVING HEATING LIQUID TEMPERATURE, HIGH, 120°F/140°F |
SIMULTANEOUS COOLING AND HEATING FULL-LOAD ** EFFICIENCY** (COPSHC) c, d, e, f, g, W/W, ENTERING/LEAVING HEATING LIQUID TEMPERATURE, BOOST, 120°F/140°F |
TEST PROCEDURE |
| < 150 | 47 db 43 wb |
NAj | NAj | NAj | NAj | AHRI 550/590 |
| < 150 | 17 db 15 wb |
NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 150 | 47 db 43 wb |
NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 150 | 17 db 15 wb |
NAj | NAj | NAj | NAj | AHRI 550/590 |
| Equipment Type: Liquid source electrically operated positive displacement | ||||||
| > 11.25h and < 150 | 44i | > 8.33 | > 6.41 | > 4.42 | NAj | AHRI 550/590 |
| > 11.25 h and < 150 | 65 i | NAj | NAj | NAj | > 6.150 | AHRI 550/590 |
| > 150 and < 300 | 44i | > 8.33 | > 6.41 | > 4.42 | NAj | AHRI 550/590 |
| > 150 and < 300 | 65 i | NAj | NAj | NAj | > 6.150 | AHRI 550/590 |
| > 300 and < 400 | 44i | > 8.33 | > 6.41 | > 4.42 | NAj | AHRI 550/590 |
| > 300 and < 400 | 65 i | NAj | NAj | NAj | > 6.150 | AHRI 550/590 |
| > 400 and < 600 | 44i | > 8.9 | > 6.98 | > 5 | NAj | AHRI 550/590 |
| > 400 and < 600 | 65 i | NAj | NAj | NAj | > 6.85 | AHRI 550/590 |
| > 600 | 44i | > 8.9 | > 6.98 | > 5 | NAj | AHRI 550/590 |
| > 600 | 65 i | NAj | NAj | NAj | > 6.85 | AHRI 550/590 |
| Equipment Type: Liquid source electrically operated centrifugal | ||||||
| > 11.25h and < 150 | 44i | > 8.33 | > 6.41 | > 4.42 | NAj | AHRI 550/590 |
| > 11.25 h and < 150 | 65 i | NAj | NAj | NAj | > 6.150 | AHRI 550/590 |
| > 150 and < 300 | 44i | > 8.33 | > 6.41 | > 4.42 | NAj | AHRI 550/590 |
| > 150 and < 300 | 65 i | NAj | NAj | NAj | > 6.150 | AHRI 550/590 |
| > 300 and < 400 | 44i | > 8.33 | > 6.41 | > 4.42 | NAj | AHRI 550/590 |
| > 300 and < 400 | 65 i | NAj | NAj | NAj | > 6.150 | AHRI 550/590 |
| > 400 and < 600 | 44i | > 8.9 | > 6.98 | > 5 | NAj | AHRI 550/590 |
| > 400 and < 600 | 65 i | NAj | NAj | NAj | > 6.85 | AHRI 550/590 |
| > 600 | 44i | > 8.9 | > 6.98 | > 5 | NAj | AHRI 550/590 |
| > 600 | 65 i | NAj | NAj | NAj | > 6.85 | AHRI 550/590 |
a. The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load external to the chill-
ing package.
b. For air source heat pumps, compliance with both the 47°F and 17°F heating source outdoor air temperature (OAT) rating efficiency is required for heating.
c. Heating full-load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, which includes the impact of defrost for air source heating ratings.
d. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required.
e. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recover COPHR is
only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling-only perfor-
mance is required as defined in Notes b and c of Table 110.2-I.
f. Heating full load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4 which includes the impact of defrost for air source heating ratings.
g. For simultaneous cooling and heating chillers applications where there is simultaneous cooling and heating, compliance with the simultaneous cooling performance heat
recovery COPSHCis only required at one of the heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, High or Boost. Compliance with cooling performance is
required as defined in Notes b and c of Table 110.2-I.
h. Water-to-water heat pumps with a capacity less than 135,000 Btu/h are included in Table 110.2-B, Heat Pumps—Minimum Efficiency Requirements.
i. Source leaving liquid temperature.
1. The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air-to-water heat pump shall be the flow rate determined during the full-load cooling rating.
2. The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates
from the cooling operation full-load rating.
3. For heating-only fluid-to-fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54°F and a leaving liquid temperature of 44°F
shall be used.
j. NA means the requirements are not applicable.
50 2025 CALIFORNIA ENERGY CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
| TABLE 110.2-L—HEAT PUMP AND HEAT RECOVERY CHILLER PACKAGES, HEAT RECOVERY, HEATING OPERATION—MINIMUM EFFICIENCY REQUIREMENTS |
||||||
|---|---|---|---|---|---|---|
| Equipment Type: Air Source | Equipment Type: Air Source | Equipment Type: Air Source | Equipment Type: Air Source | Equipment Type: Air Source | Equipment Type: Air Source | Equipment Type: Air Source |
| SIZE CATEGORY REFRIGERATING **CAPACITYa, ** TONR |
HEATING SOURCE CONDITIONS (LEAVING LIQUID) OR OAT (db/wb)b,°F |
HEAT RECOVERY HEATING FULL-LOAD EFFICIENCY (COPSHC) c, d, e, f, g, W/W, ENTERING/LEAVING HEATING LIQUID TEMPERATURE, LOW, 95°F/105°F |
HEAT RECOVERY HEATING FULL-LOAD EFFICIENCY (COPSHC) c, d, e, f, g, W/W, ENTERING/LEAVING HEATING LIQUID TEMPERATURE, MEDIUM, 105°F/120°F |
HEAT RECOVERY HEATING FULL-LOAD EFFICIENCY (COPSHC) c, d, e, f, g, W/W, ENTERING/LEAVING HEATING LIQUID TEMPERATURE, HIGH, 120°F/140°F |
HEAT RECOVERY HEATING FULL-LOAD EFFICIENCY (COPSHC) c, d, e, f, g, W/W, ENTERING/LEAVING HEATING LIQUID TEMPERATURE, BOOST, 120°F/140°F |
TEST PROCEDURE |
| < 150 | 47 db 43 wb |
NAj | NAj | NAj | NAj | AHRI 550/590 |
| < 150 | 17 db 15 wb |
NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 150 | 47 db 43 wb |
NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 150 | 17 db 15 wb |
NAj | NAj | NAj | NAj | AHRI 550/590 |
| Equipment Type: Liquid source electrically operated positive displacement | ||||||
| > 11.25h and < 150 | 44i | > 8.33 | > 6.41 | > 4.862 | > 4.42 | AHRI 550/590 |
| > 11.25 h and < 150 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 150 and < 300 | 44i | > 8.33 | > 6.41 | > 4.862 | > 4.42 | AHRI 550/590 |
| > 150 and < 300 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 300 and < 400 | 44i | > 8.33 | > 6.41 | > 4.862 | > 4.42 | AHRI 550/590 |
| > 300 and < 400 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 400 and < 600 | 44i | > 8.9 | > 6.98 | > 5.5 | > 5 | AHRI 550/590 |
| > 400 and < 600 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 600 | 44i | > 8.9 | > 6.98 | > 5.5 | > 5 | AHRI 550/590 |
| > 600 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| Equipment Type: Liquid source electrically operated centrifugal | ||||||
| > 11.25h and < 150 | 44i | > 8.33 | > 6.41 | > 4.862 | > 4.42 | AHRI 550/590 |
| > 11.25 h and < 150 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 150 and < 300 | 44i | > 8.33 | > 6.41 | > 4.862 | > 4.42 | AHRI 550/590 |
| > 150 and < 300 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 300 and < 400 | 44i | > 8.33 | > 6.41 | > 4.862 | > 4.42 | AHRI 550/590 |
| > 300 and < 400 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 400 and < 600 | 44i | > 8.9 | > 6.98 | > 5.5 | > 5 | AHRI 550/590 |
| > 400 and < 600 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
| > 600 | 44i | > 8.9 | > 6.98 | > 5.5 | > 5 | AHRI 550/590 |
| > 600 | 65 i | NAj | NAj | NAj | NAj | AHRI 550/590 |
a. The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load external to the chill-
ing package.
b. For air source heat pumps, compliance with both the 47°F and 17°F heating source outdoor air temperature (OAT) rating efficiency is required for heating.
c. Heating full-load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, which includes the impact of defrost for air source heating ratings.
d. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required.
e. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recover COPHR is
only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling-only perfor-
mance is required as defined in Notes b and c of Table 110.2-I.
f. For liquid source heat recovery chilling packages that have capabilities for heat rejection to a heat recovery condenser and a tower condenser, the COPHR applies to operation
at full load with 100 percent heat recovery (no tower rejection). Units that only have capabilities for partial heat recovery shall meet the requirements of Table 110.2-D, Water
Chilling Packages—Minimum Efficiency Requirements.
g. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recover COPHR is
only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling-only perfor-
mance is required as defined in Notes b and c of Table 110.2-I.
h. Water-to-water heat pumps with a capacity less than 135,000 Btu/h are included in Table 110.2-B, Heat Pumps—Minimum Efficiency Requirements.
i. Source leaving liquid temperature.
1. The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air-to-water heat pump shall be the flow rate determined during the full-load cool-
ing rating.
2. The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates
from the cooling operation full-load rating.
3. For heating-only fluid-to-fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54°F and a leaving liquid temperature of 44°F
shall be used.
j. NA means the requirements are not applicable.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Energy Code (Title 24, Part 6)
- Chapter 1 — ALL OCCUPANCIES—GENERAL PROVISIONS
-
▸ Chapter 2 — ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MAN…
Overview- Section 110.0 — SYSTEMS AND EQUIPMENT—GENERAL
- Section 110.1 — MANDATORY REQUIREMENTS FOR APPLIANCES
- Section 110.2 — MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING …
- Section 110.3 — MANDATORY REQUIREMENTS FOR SERVICE WATER-HEATI…
- Section 110.4 — MANDATORY REQUIREMENTS FOR POOL AND SPA SYSTEM…
- Section 110.5 — NATURAL GAS CENTRAL FURNACES,
- Section 110.6 — MANDATORY REQUIREMENTS FOR FENESTRATION PRODUC…
- Section 110.7 — MANDATORY REQUIREMENTS TO LIMIT AIR LEAKAGE
- Section 110.8 — MANDATORY REQUIREMENTS FOR INSULATION, ROOFING…
- Section 110.9 — MANDATORY REQUIREMENTS FOR LIGHTING CONTROLS
- Section 110.10 — MANDATORY REQUIREMENTS FOR SOLAR READINESS
- Section 110.11 — MANDATORY REQUIREMENTS FOR ELECTRICAL POWER D…
- Section 110.12 — MANDATORY REQUIREMENTS FOR DEMAND MANAGEMENT
- Chapter 3 — NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVER…
- Chapter 4 — NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATO…
- Chapter 5 — NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORM…
- Chapter 6 — NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—
- Chapter 7 — SINGLE-FAMILY RESIDENTIAL BUILDINGS—
- Chapter 8 — SINGLE-FAMILY RESIDENTIAL BUILDINGS—PERFORMANCE AN…
- Chapter 9 — SINGLE-FAMILY RESIDENTIAL BUILDINGS—ADDITIONS AND …
- Chapter 10 — MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS
- Chapter 11 — MULTIFAMILY BUILDINGS—PERFORMANCE AND PRESCRIPTIV…
- Chapter 12 — MULTIFAMILY BUILDINGS—ADDITIONS, ALTERATIONS AND …