110.11 Mandatory Requirements for Electrical Power Distribution System — 2025 California Energy Code
California Energy Code (Title 24, Part 6) · 2025 edition · updated 2026-09-24 · California
Cite as: 2025 California Energy Code (Title 24, Part 6) § 110.11 · Effective January 1, 2026 · Official source: Building Standards Commission
Certification by Manufacturers. Any electrical power distribution system equipment listed in this section may be installed only if the manufacture has certified to the Commission that the equipment complies with all the applicable requirements of this section.
62 2025 CALIFORNIA ENERGY CODE
ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS
(a) Low-voltage dry-type distribution transformer shall be certified by the Manufacturer as required by the Title 20 Appliance Efficiency Regulations.
EXCEPTION to Section 110.11(a):
autotransformer;
drive (isolation) transformer;
grounding transformer;
machine-tool (control) transformer;
nonventilated transformer;
rectifier transformer;
regulating transformer;
sealed transformer;
special-impedance transformer;
testing transformer;
transformer with tap range of 20 percent or more;
uninterruptible power supply transformer; or
welding transformer.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code.