Section 1017
California Building Code (Title 24, Part 2) · 2019 edition · updated 2026-09-12 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
1017.1 General.¶
Travel distance within the exit access portion of the means of egress system shall be in accordance with this section.
1017.2 Limitations.¶
Exit access travel distance shall not exceed the values given in Table 1017.2.
1017.2.1 Exterior egress balcony increase. Exit access travel distances specified in Table 1017.2 shall be increased up to an additional 100 feet (30 480 mm) provided that the last portion of the exit access leading to the exit occurs on an exterior egress balcony constructed in accordance with Section 1021. The length of such balcony shall be not less than the amount of the increase taken.
| OCCUPANCY | WITHOUT SPRINKLER SYSTEM (feet) |
WITH SPRINKLER SYSTEM (feet) |
|---|---|---|
| A, E, F-1, M, R, S-1 | 200e | 250b |
| R-2.1 | Not Permitted | 250b |
| B | 200 | 300c |
| F-2, S-2, U | 300 | 400c |
| H-1 | Not Permitted | 75d |
| H-2 | Not Permitted | 100d |
| H-3 | Not Permitted | 150d |
| H-4 | Not Permitted | 175d |
| H-5 | Not Permitted | 200c |
| I-2,I-2.1, I-3_f_ | Not Permitted | 200c |
| I-4 | 150 | 200c |
| L | Not Permitted | 200c |
For SI: 1 foot = 304.8 mm. a. See the following sections for modifications to exit access travel distance
requirements:
Section 402.8: For the distance limitation in malls. Section 404.9: For the distance limitation through an atrium space. Section 407.4: For the distance limitation in Group I-2 or I-2.1 . Section 408.3.10: For increased limitation in Group I-3 Sections 408.6.1 and 408.8.1: For the distance limitations in Group I-3. Section 411.3: For the distance limitation in special amusement buildings. Section 412.6: For the distance limitations in aircraft manufacturing
facilities. Section 1006.2.2.2: For the distance limitation in refrigeration
machinery rooms. Section 1006.2.2.3: For the distance limitation in refrigerated rooms and
spaces. Section 1006.3.3: For buildings with one exit. Section 1017.2.2: For increased distance limitation in Groups F-1 and S-1. Section 1029.7: For increased limitation in assembly seating. Section 3103.4: For temporary structures. Section 3104.9: For pedestrian walkways. b. Buildings equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1 or 903.3.1.2. See Section 903 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.2. c. Buildings equipped throughout with an automatic sprinkler system in
accordance with Section 903.3.1.1. d. Group H occupancies equipped throughout with an automatic sprinkler
system in accordance with Section 903.2.5.1. e. Group R-3 and R-4 buildings equipped throughout with an automatic
sprinkler system in accordance with Section 903.3.1.3. See Section 903.2.8 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.3. f. Not permitted in nonsprinklered Group I-3 occupancies.
1017.2.2 Groups F-1 and S-1 increase. The maximum exit access travel distance shall be 400 feet (122 m) in Group F-1 or S-1 occupancies where all of the following conditions are met:
The portion of the building classified as Group F-1 or S-1 is limited to one story in height.
The minimum height from the finished floor to the bottom of the ceiling or roof slab or deck is 24 feet (7315 mm).
MEANS OF EGRESS
TABLE 1017.2 EXIT ACCESS TRAVEL DISTANCE a
Copyright © 2019 ICC. ALL RIGHTS RESERVED. Accessed by Kevin Day (kevin.day@dgs.ca.gov), (California Building Standards Commission) Order Number #100735044 on Jul 24, 2019 03:54 PM (PDT) pursuant to License Agreement with ICC. No further reproduction or distribution authorized. Single user only, copying and networking prohibited. ANY UNAUTHORIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT, AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
100735044
MEANS OF EGRESS
- The building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
1017.3 Measurement.¶
Exit access travel distance shall be measured from the most remote point of each room, area or space along the natural and unobstructed path of horizontal and vertical egress travel to the entrance to an exit.
Exception: In open parking garages, exit access travel distance is permitted to be measured to the closest riser of an exit access stairway or the closest slope of an exit access ramp.
1017.3.1 Exit access stairways and ramps. Travel distance on exit access stairways or ramps shall be included in the exit access travel distance measurement. The measurement along stairways shall be made on a plane parallel and tangent to the stair tread nosings in the center of the stair and landings. The measurement along ramps shall be made on the walking surface in the center of the ramp and landings.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸Contents — California Building Code (Title 24, Part 2)
- Chapter 2 — DEFINITIONS AND ABBREVIATIONS
- Appendix G — FLOOD-RESISTANT
- Appendix L — EARTHQUAKE RECORDING
- Appendix M — TSUNAMI-GENERATED
- Chapter 1 — SCOPE AND ADMINISTRATION
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
▸Chapter 10 — MEANS OF EGRESS
Overview- Section 1001
- Section 1003
- Section 1004
- Section 1005
- Section 1006
- Section 1007
- Section 1008
- Section 1009
- Section 1010
- Section 1011
- Section 1012
- Section 1013
- Section 1014
- Section 1015
- Section 1016
- Section 1017
- Section 1018
- Section 1019
- Section 1020
- Section 1021
- Section 1022
- Section 1023
- Section 1024
- Section 1025
- Section 1026
- Section 1027
- Section 1028
- Section 1029
- Section 1030
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 19 — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 22 — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31B — PUBLIC POOLS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U – AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix F — RODENTPROOFING
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — EMERGENCY HOUSING