Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
Section 909 — SMOKE CONTROL SYSTEMS
2025 California Building Code (Title 24, Part 2) · 2025 edition · ingested 2026-07-07 · California
Full text via GoCodebook AI
We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.
[F] 909.1 Scope and purpose. This section applies to mechanical or passive smoke control systems where they are required by other provisions of this code. The purpose of this section is to establish minimum requirements for the design, installation and acceptance testing of smoke control systems that are intended to provide a tenable environment for the evacuation or relocation of occupants. These provisions are not intended for the preservation of contents, the timely restoration of operations or for assistance in fire suppression or overhaul activities. Smoke control systems regulated by…
909.20 Smokeproof enclosures. ¶
909.20 Smokeproof enclosures. Where required by Section 1023.12, a smokeproof enclosure shall be constructed in accordance with this section. A smokeproof enclosure shall consist of an interior exit stairway or ramp that is enclosed in accordance with the applicable provisions of Section 1023 and an open exterior balcony or pressurized stair and pressurized entrance vestibule meeting the requirements of this section. Where access to the roof is required by the California Fire Code, such access shall be from the smokeproof enclosure where a smokeproof enclosure is required. 909.20.1 Access.…
909.21 Elevator hoistway pressurization alternative. ¶
909.21 Elevator hoistway pressurization alternative. Where elevator hoistway pressurization is provided in lieu of required enclosed elevator lobbies, the pressurization system shall comply with Sections 909.21.1 through 909.21.11. The design shall consider the interaction effects of the operation of multiple smoke control systems for all design scenarios in accordance with Section 909.4.7. All components or systems associated with the means of mitigating adverse interaction shall comply with the applicable subsections of Section 909. 909.21.1 Pressurization requirements. Elevator hoistways…