Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
Section 3010 — SPECIAL REQUIREMENTS FOR ELEVATORS IN HOSPITALS
2025 California Building Code (Title 24, Part 2) · 2025 edition · ingested 2026-07-07 · California
Full text via GoCodebook AI
We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.
3010.1 General. ¶
3010.1 General. [OSHPD 1] In hospital buildings, all elevators shall comply with the provisions of this section. 3010.1.1 Seismic switch. The seismic switch, as required by ASME A17.1, shall be connected to the essential electrical system. 3010.1.2 Annunciator. Either a visible or an audible annunciator shall be connected to the essential electrical system and be located in the elevator machine room. The annunciator will indicate if the seismic switch is inoperative due to a loss of power. If a visual annunciator is used, it shall be clearly visible in the room. 3010.1.3 Travel speed. After a…