Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
Section 3005 — MACHINE ROOMS
2025 California Building Code (Title 24, Part 2) · 2025 edition · ingested 2026-07-07 · California
Full text via GoCodebook AI
We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.
3005.1 Access. ¶
3005.1 Access. A permanent and approved means of access shall be provided to elevator machine rooms, control rooms, control spaces and machinery spaces.
3005.2 Temperature and humidity control. ¶
3005.2 Temperature and humidity control. Elevator machine rooms, machinery spaces that contain the driving machine, and control rooms or spaces that contain the operation or motion controller for elevator operation shall be provided with an independent ventilation or air-conditioning system to protect against the overheating of the electrical equipment. The system shall maintain the temperature and humidity be capable of maintaining temperatures within the range established by the manufacturer of the elevator equipment.
3005.3 Pressurization. ¶
3005.3 Pressurization. The elevator machine room, control rooms or control space with openings into a pressurized elevator hoistway shall be pressurized upon activation of a heat or smoke detector located in the elevator machine room, control room or control space.
3005.4 Machine rooms, control rooms, machinery spaces, and control spaces. ¶
3005.4 Machine rooms, control rooms, machinery spaces, and control spaces. The following rooms and spaces shall be enclosed with fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both: 1. Machine rooms. 2. Control rooms. 30-6 2025 CALIFORNIA BUILDING CODE on Jul 18, 2025 11:14 AM (CDT) THEREUNDER. ELEVATORS AND CONVEYING SYSTEMS 3. Control spaces. 4. Machinery spaces outside of the hoistway enclosure. The fire-resistance rating shall be not less than the required rating of the hoistway enclosure served by the…
3005.5 Shunt trip. ¶
3005.5 Shunt trip. Where elevator hoistways, elevator machine rooms, control rooms and control spaces containing elevator control equipment are protected with automatic sprinklers, a means installed in accordance with Section 21.4 of NFPA 72 shall be provided to automatically disconnect the main line power supply to the affected elevator prior to the application of water. This means shall not be self-resetting. The activation of automatic sprinklers outside the hoistway, machine room, machinery space, control room or control space shall not disconnect the main line power supply.
3005.6 Plumbing systems. ¶
3005.6 Plumbing systems. Plumbing systems shall not be located in elevator equipment rooms.