2609.1 General.

2609.1 General. Light-transmitting plastic roof panels shall comply with this section and Section 2606. Light-transmitting plastic roof panels shall not be installed in Groups H, I-2 and I-3. In all other groups, light-transmitting plastic roof panels shall comply with any one of the following conditions: 1. The building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. 2. The roof construction is not required to have a fire-resistance rating by Table 601. 3. The roof panels meet the requirements for roof coverings in accordance with Chapter 15.

2609.2 Separation.

2609.2 Separation. Individual roof panels shall be separated from each other by a distance of not less than 4 feet (1219 mm) measured in a horizontal plane. Exceptions: 1. The separation between roof panels is not required in a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. 2. The separation between roof panels is not required in low-hazard occupancy buildings complying with the conditions of Section 2609.4, Exception 2 or 3.

2609.3 Location.

2609.3 Location. Where exterior wall openings are required to be protected by Section 705.9, a roof panel shall not be installed within 6 feet (1829 mm) of such exterior wall.

2609.4 Area limitations.

2609.4 Area limitations. Roof panels shall be limited in area and the aggregate area of panels shall be limited by a percentage of the floor area of the room or space sheltered in accordance with Table 2609.4. Exceptions: 1. The area limitations of Table 2609.4 shall be permitted to be increased by 100 percent in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. 2. Low-hazard occupancy buildings, such as swimming pool shelters, shall be exempt from the area limitations of Table 2609.4, provided that the buildings do not exceed 5,000 square…