Section 1901 — GENERAL
2025 California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-07-29 · California
Italicized text is a California amendment to the model code, as printed in the official publication.
1901.1 Scope. ¶
The provisions of this chapter shall govern the materials, quality control, design and construction of concrete used in structures.
1901.1.1 Application. [DSA-SS/CC, OSHPD] The scope of application of Chapter 19 is as follows: 1. Structures regulated by the Division of the State Architect—Structural Safety/Community Colleges (DSA-SS/CC), which include those applications listed in Section 1.9.2.2. 2. Structures regulated by the Department of Health Care Access and Information/Office of Statewide Hospital Planning and Development (OSHPD), which include hospital buildings removed from general acute care service, skilled nursing facility build- ings, intermediate care facility buildings and acute psychiatric hospital buildings listed in Sections 1.10.1, 1.10.2 and 1.10.5.
1901.1.2 Amendments in this chapter. [DSA-SS/CC, OSHPD] DSA-SS/CC and OSHPD adopts this chapter as amended.
1901.1.3 Identification of amendments. [DSA-SS/CC, OSHPD] 1. Division of the State Architect - Structural Safety/Community Colleges amendments appear in this chapter preceded by the appropriate acronym, as follows:
[DSA-SS/CC] – For applications listed in Section 1.9.2.2. 2. [OSHPD 1R, 2 & 5] Office of Statewide Hospital Planning and Development (OSHPD) amendments appear in this chapter preceded by the appropriate acronym, as follows:
[OSHPD 1R ] – For applications listed in Section 1.10.1.
[OSHPD 2] – For applications listed in Section 1.10.2.
[OSHPD 5] – For applications listed in Section 1.10.5.
1901.1.4 Reference to other chapters. [DSA-SS/CC] Where reference within this chapter is made to sections in Chapters 17 and 18, the provisions in Chapters 17A and 18A respectively shall apply instead.
1901.1.5 Additional amendments. [DSA-SS/CC] See Section 1909 for additional requirements.
1901.2 Plain and reinforced concrete. ¶
Structural concrete shall be designed and constructed in accordance with the requirements of this chapter and ACI 318 as supplemented in Section 1905 of this code.
1901.2.1 Structural concrete with GFRP reinforcement. Cast-in-place structural concrete internally reinforced with glass fiber reinforced polymer (GFRP) reinforcement conforming to ASTM D7957 and designed in accordance with ACI CODE 440.11 shall be permitted where fire-resistance ratings are not required and only for structures assigned to Seismic Design Category A.
1901.3 Anchoring to concrete. ¶
Anchoring to concrete shall be in accordance with ACI 318 as supplemented in Section 1905, and applies to cast-in (headed bolts, headed studs and hooked J- or L-bolts), post-installed expansion (torque-controlled and displacement-controlled), undercut, screw, and adhesive anchors.
1901.3.1 Power actuated fasteners. [OSHPD 1R, 2 & 5] Power actuated fasteners qualified in accordance with ICC-ES AC 70 shall be deemed to satisfy the requirements of ASCE 7, Section 13.4.5.
Power actuated fasteners shall be permitted in seismic shear for components exempt from construction documents review by ASCE 7, Section 13.1.4 and for interior non-bearing non-shear wall partitions only. Power actuated fastener shall not be used to anchor seismic bracing, exterior cladding or curtain wall systems.
Exception: Power actuated fasteners in steel to steel connections prequalified for seismic application by cyclic tests in accordance with ICC-ES AC 70 shall be permitted for seismic design.
1901.3.2 Mechanical anchors and specialty inserts. [OSHPD 1R, 2 & 5] Mechanical anchors qualified in accordance with ICC-ES AC 193 shall be deemed to satisfy the requirements of this section. Specialty inserts, including cast-in-place specialty inserts, tested in accordance with ICC-ES AC 232 or AC 446 shall be deemed to satisfy the requirements of this section.
Note: The removal and resetting of post-installed mechanical anchors are prohibited by ACI 318 Section 17.1.3.
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CONCRETE
1901.3.3 Post-installed adhesive anchors. [OSHPD 1R, 2 & 5] Post-installed reinforcing bars, adhesive anchors, and torque- controlled adhesive anchors qualified in accordance with ICC-ES AC 308 shall be deemed to satisfy the requirements of this section.
1901.3.4 Proof tests for post-installed anchors in concrete. [OSHPD 1R, 2 & 5] When post-installed anchors are used in lieu of cast- in place bolts, the proof test loads, frequency and acceptance criteria shall be in accordance with this section.
Exceptions. Proof tests are not required for the following:
1. Undercut anchors that allow visual confirmation of full set.
2. Repetitively installed anchors (with three or more identical anchors) of diameter one-quarter ( [1] / 4 ) inch or less used for distributed systems or architectural components. 3. Power actuated fasteners used to attach tracks of interior nonstructural partition walls resisting only shear loads and with at least three fasteners per segment of track. 4. Shear dowels across cold joints in slabs on grade, where the slab is not structural in accordance with Section 1907.1.
1901.3.4.1 General. [OSHPD 1R, 2 & 5] Test loads or torques, test frequencies, and acceptance criteria shall be shown on the construction documents.
If any anchor fails testing, all anchors of the same type shall be tested until twenty (20) consecutive anchors pass, then resume the initial test frequency.
Anchors to be tested shall be selected at random by the special inspector or inspector of record (IOR) when 100 percent of the anchors are not tested.
The testing of the post-installed anchors shall be done in the presence of the special inspector and a report of the test results shall be submitted to the enforcement agency.
1901.3.4.2 Proof testing procedure. [OSHPD 1R, 2 & 5] Post-installed anchors shall be tension tested in accordance with ASTM E3121 with test frequency and test loads in accordance with Sections 1901.3.4.3 and 1901.3.4.4, respectively. Proof tests using ASTM E3121 tension test procedure do not require displacement measurement.
Exception: Torque-controlled post-installed and screw-type anchors shall be permitted to be tested using torque based on a valid evaluation report using criteria adopted in this code.
1901.3.4.3 Test frequency. [OSHPD 1R, 2 & 5]
1901.3.4.3.1 Structural applications. One hundred percent of post-installed anchors used for sructural applications shall be proof tested.
Exceptions: 1. Sill bolts. When post-installed anchors are used for sill plate or bottom track bolting applications, 10 percent of the anchors shall be tested.
2. Rebar dowels. When adhesive anchor systems are used to install reinforcing dowel bars in hardened concrete, 25 percent of dowels shall be tested if all the following conditions are met: 2.1. The dowels are used exclusively to transmit shear forces across joints between existing and new concrete. 2.2. The number of dowels in any one member equals or exceeds twelve (12). 2.3. The dowels are uniformly distributed across seismic force resisting members (such as shear walls, collec- tors and diaphragms).
1901.3.4.3.2 Nonstructural applications. Fifty percent of post-installed anchors used in nonstructural applications shall be proof tested. The percentage of tested anchors applies to each set of anchors of a common type (e.g., adhesive, wedge, or shell and sleeve for expansion bolts), size, and embedment depth and to each group of anchors. Four or more anchors connected to a common element shall be defined as a group.
Exceptions: 1. Repetitive anchors. When anchors are used repetitively (with three or more identical anchors) in distribution systems (such as pipe, duct or conduit supports) or architectural systems (such as suspended ceilings, cladding, and partitions), 20 percent of anchors, including at least one anchor in each group, shall be tested. 2. Anchors with low tension. When the design tension on anchors is less than 100 pounds and those anchors are clearly noted on the approved construction documents, 10 percent of anchors shall be tested.
onduit supports) or architectural systems (such as suspended ceilings, cladding,_ and partitions), 20 percent of anchors, including at least one anchor in each group, shall be tested. 2. Anchors with low tension. When the design tension on anchors is less than 100 pounds and those anchors are clearly noted on the approved construction documents, 10 percent of anchors shall be tested.
1901.3.4.4 Test loads. [OSHPD 1R, 2 & 5] Required test loads shall be determined by one of the following methods: 1. Twice the maximum allowable tension load or one and a quarter (1 [1] / 4 ) times the maximum design strength of anchors as provided in approved evaluation report using criteria adopted in this code or determined in accordance with Chapter 17 of ACI 318.
Tension test load need not exceed 80 percent of the nominal yield strength of the anchor element (= 0.8 A se f ya ). 2. The manufacturer’s recommended installation torque based on approved evaluation report using criteria adopted in this code.
1901.3.4.5 Test acceptance criteria. [OSHPD 1R, 2 & 5] Proof test shall satisfy the following minimum requirements. 1. Tension test: Anchors shall be tested in the unconfined condition in accordance with ASTM E3121 except that the mini- mum clearance to the test frame shall be 1.5 times the anchor’s embedment depth. Test load shall be maintained for a
19-4 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CONCRETE
minimum of 15 seconds and shall exhibit no discernable movement during the tension test, e.g., as evidenced by loosen- ing of the washer under the nut or an abrupt decrease in the gauge pressure. Exception: Adhesive anchors shall be permitted to be tested in confined conditions in accordance with ASTM E3121 when the approved construction documents indicate that concrete breakout does not control the design tensile strength. 2. Torque test: Torque-controlled post-installed anchors tested with a calibrated torque wrench shall attain the specified torque within [1] / 2 turn of the nut; or one-quarter ( [ 1] / 4 ) turn of the nut for a [3] / 8 -inch sleeve anchor only. Screw-type anchors tested with a calibrated torque wrench shall attain the specified torque within one-quarter ( [ 1] / 4 ) turn of the screw after initial seating of the screw head.
1901.4 Composite structural steel and concrete structures. ¶
Systems of structural steel acting compositely with reinforced concrete shall be designed in accordance with Section 2206 of this code.
1901.5 Construction documents. ¶
The construction documents for structural concrete construction shall include:
The specified compressive strength of concrete at the stated ages or stages of construction for which each concrete element is designed.
The specified strength or grade of reinforcement.
The size and location of structural elements, reinforcement and anchors.
Provision for dimensional changes resulting from creep, shrinkage and temperature.
The magnitude and location of prestressing forces.
Anchorage length of reinforcement and location and length of lap splices.
Type and location of mechanical and welded splices of reinforcement.
Details and location of contraction or isolation joints specified for plain concrete.
Minimum concrete compressive strength at time of posttensioning.
Stressing sequence for posttensioning tendons.
For structures assigned to Seismic Design Category D, E or F, a statement if slab on grade is designed as a structural diaphragm.
1901.6 Special inspections and tests. ¶
S pecial inspections and tests of concrete elements of buildings and structures and concreting operations shall be as required by Chapter 17.
1901.7 Tolerances for structural concrete. ¶
Where not indicated in construction documents, structural tolerances for concrete structural elements shall be in accordance with this section.
1901.7.1 Cast-in-place concrete tolerances. Structural tolerances for cast-in-place concrete structural elements shall be in accordance with ACI 117.
Exceptions:
- Group R-3 detached one- or two-family dwellings are not required to comply with this section.
- Shotcrete is not required to comply with this section.
1901.7.2 Precast concrete tolerances. Structural tolerances for precast concrete structural elements shall be in accordance with ACI ITG-7.
Exception: Group R-3 detached one- or two-family dwellings are not required to comply with this section.
Get a plain-English answer with a citation back to this text.
Ask AI about this code▸ Contents — 2025 California Building Code (Title 24, Part 2)
- Chapter 1 — ADMINISTRATION
- Chapter 2 — DEFINITIONS
- Chapter 3 — OCCUPANCY CLASSIFICATION AND USE
- Chapter 4 — SPECIAL DETAILED REQUIREMENTS BASED ON OCCUPANCY A…
- Chapter 5 — GENERAL BUILDING HEIGHTS AND AREAS
- Chapter 6 — TYPES OF CONSTRUCTION
- Chapter 7 — FIRE AND SMOKE PROTECTION FEATURES
- Chapter 7A — MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR W…
- Chapter 8 — INTERIOR FINISHES
- Chapter 9 — FIRE PROTECTION AND LIFE SAFETY SYSTEMS
- Chapter 10 — MEANS OF EGRESS
- Chapter 11 — RESERVED
- Chapter 11A — HOUSING ACCESSIBILITY
- Chapter 11B — ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMM…
- Chapter 12 — INTERIOR ENVIRONMENT
- Chapter 13 — ENERGY EFFICIENCY
- Chapter 14 — EXTERIOR WALLS
- Chapter 15 — ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
- Chapter 16 — STRUCTURAL DESIGN
- Chapter 16A — STRUCTURAL DESIGN
- Chapter 17 — SPECIAL INSPECTIONS AND TESTS
- Chapter 17A — SPECIAL INSPECTIONS AND TESTS
- Chapter 18 — SOILS AND FOUNDATIONS
- Chapter 18A — SOILS AND FOUNDATIONS
-
▸ Chapter 19 — CONCRETE
Overview- Section 1901 — GENERAL
- Section 1902 — COORDINATION OF TERMINOLOGY
- Section 1903 — SPECIFICATIONS FOR TESTS AND MATERIALS
- Section 1904 — DURABILITY REQUIREMENTS
- Section 1905 — SEISMIC REQUIREMENTS
- Section 1906 — FOOTINGS FOR LIGHT-FRAME CONSTRUCTION
- Section 1907 — SLABS-ON-GROUND
- Section 1908 — SHOTCRETE
- Section 1909 — ADDITIONAL REQUIREMENTS FOR COMMUNITY COLLEGES …
- Section 1910 — ADDITIONAL REQUIREMENTS FOR SKILLED NURSING FAC…
- Section 1911 — EXISTING CONCRETE STRUCTURES [OSHPD 1R, 2 & 5]
- Chapter 19A — CONCRETE
- Chapter 20 — ALUMINUM
- Chapter 21 — MASONRY
- Chapter 21A — MASONRY
- Chapter 22 — STEEL
- Chapter 22A — STEEL
- Chapter 23 — WOOD
- Chapter 24 — GLASS AND GLAZING
- Chapter 25 — GYPSUM PANEL PRODUCTS AND PLASTER
- Chapter 26 — PLASTIC
- Chapter 27 — ELECTRICAL
- Chapter 28 — MECHANICAL SYSTEMS
- Chapter 29 — PLUMBING SYSTEMS
- Chapter 30 — ELEVATORS AND CONVEYING SYSTEMS
- Chapter 31 — SPECIAL CONSTRUCTION
- Chapter 31A — SYSTEMS FOR WINDOW CLEANING OR EXTERIOR BUILDING…
- Chapter 31B — PUBLIC POOLS
- Chapter 31C — RADIATION
- Chapter 31D — FOOD ESTABLISHMENTS
- Chapter 31F — MARINE OIL TERMINALS
- Chapter 32 — ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY
- Chapter 33 — SAFEGUARDS DURING CONSTRUCTION
- Chapter 34 — RESERVED
- Chapter 35 — REFERENCED STANDARDS
- Appendix A — EMPLOYEE QUALIFICATIONS
- Appendix B — BOARD OF APPEALS
- Appendix C — GROUP U—AGRICULTURAL BUILDINGS
- Appendix D — FIRE DISTRICTS
- Appendix E — RESERVED
- Appendix F — RODENTPROOFING
- Appendix G — FLOOD-RESISTANT CONSTRUCTION
- Appendix H — SIGNS
- Appendix I — PATIO COVERS
- Appendix J — GRADING
- Appendix K — GROUP R-3 AND GROUP R-3.1 OCCUPANCIES PROTECTED B…
- Appendix L — EARTHQUAKE RECORDING INSTRUMENTATION
- Appendix M — TSUNAMI-GENERATED FLOOD HAZARDS
- Appendix N — REPLICABLE BUILDINGS
- Appendix O — PERFORMANCE-BASED APPLICATION
- Appendix P — SLEEPING LOFTS
- Appendix Q — EMERGENCY HOUSING