Chapter 16 — STRUCTURAL DESIGN
1613 Earthquake Loads — 2025 California Building Code
California Building Code (Title 24, Part 2) · 2025 edition · updated 2026-09-25 · California
CBSC: official editions, supplements and errata
Italicized text is a California amendment to the model code, as printed in the official publication.
Cite as: 2025 California Building Code (Title 24, Part 2) § 1613 · Effective January 1, 2026 · Official source: Building Standards Commission
1613.1 Scope.¶
Every structure, and portion thereof, including nonstructural components that are permanently attached to structures and their supports and attachments, shall be designed and constructed to resist the effects of earthquake motions in accordance with Chapters 11, 12, 13, 15, 17 and 18 of ASCE 7, as applicable. The seismic design category for a structure is permitted to be determined in accordance with Section 1613 or ASCE 7.
Exceptions:
- Detached one- and two-family dwellings, assigned to Seismic Design Category A, B or C.
- The seismic force-resisting system of wood-frame buildings that conform to the provisions of Section 2308 are not required to be analyzed as specified in this section. [OSHPD 1R, 2 & 5] Not permitted by OSHPD, see Section 2308.
- Agricultural storage structures intended only for incidental human occupancy.
- Structures that require special consideration of their response characteristics and environment that are not addressed by this code or ASCE 7 and for which other regulations provide seismic criteria, such as vehicular bridges, electrical transmission towers, hydraulic structures, buried utility lines and their appurtenances and nuclear reactors.
- References within ASCE 7 to Chapter 14 shall not apply, except as specifically required herein.
- Temporary structures complying with Section 3103.6.1.4.
1613.1.1 Scope. [SL] For applications listed in Section 1.12 regulated by the State Librarian, only the provisions of ASCE 7 Tables 13.5- 1 and 1607.1, as amended, of this code shall apply.
1613.1.2 State-owned buildings. [BSC] State-owned buildings, including those of the University of California, CSU and Judicial Council, shall not be constructed where any portion of the foundation would be within a mapped area of earthquake-induced lique- faction or landsliding or within 50 feet of a mapped fault rupture hazard as established by Section 1803.7.
1613.1.3 Existing state buildings. [BSC] Additions, alterations, repairs or change of occupancy category of existing buildings shall be in accordance with the California Existing Building Code, Part 10.
1613.2 Determination of seismic design category.¶
Structures shall be assigned to a seismic design category based on one of the following methods unless the authority having jurisdiction or geotechnical data determines that Site Class DE, E or F soils are present at the site:
Based on the structure risk category using Figure 1613.2(1).
Determined in accordance with ASCE 7.
Where Site Class DE, E or F soils are present, the seismic design category shall be determined in accordance with ASCE 7.
[OSHPD 1R, 2 & 5] Seismic design category shall be D or higher.
16-34 2025 CALIFORNIA BUILDING CODE
STRUCTURAL DESIGN
FIGURE 1613.2(1)—SEISMIC DESIGN CATEGORIES FOR DEFAULT SITE CONDITIONS FOR THE CONTERMINOUS UNITED STATES (WESTERN)
STRUCTURAL DESIGN
1613.3 Simplified design procedure.¶
Where the alternate simplified design procedure of ASCE 7 is used, the seismic design category shall be determined in accordance with ASCE 7.
1613.4 Ballasted photovoltaic panel systems.¶
Ballasted, roof-mounted photovoltaic panel systems need not be rigidly attached to the roof or supporting structure. Ballasted, unattached PV panel systems shall be designed and installed only on roofs with slopes not more than 1 unit vertical in 12 units horizontal. Ballasted, unattached PV panel systems shall be designed to accommodate sliding in accordance with ASCE 7 Chapter 13. [OSHPD 1R, 2 & 5] Ballasted photovoltaic panel systems shall be considered as an alternative system.
1613.5 Elevators, escalators and other conveying systems.¶
Elevators, escalators and other conveying systems and their components shall satisfy the seismic requirements of ASCE 7 and ASME A17.1/CSA B44 as applicable.
1613.6 Automatic sprinkler systems.¶
Where required, automatic sprinkler systems, including anchorage and bracing, shall comply with ASCE 7 and Section 903.3.1.1.
1613.7 Component importance factors. [OSHPD 1R, 2 & 5]¶
Nonstructural components designated below shall have a component importance factor, I p , equal to 1.5: 1. For components that are required for life-safety purposes after an earthquake, including emergency and standby power systems, mechanical smoke removal systems, fire protection sprinkler systems and fire alarm control panels. 2. For medical equipment required for patient life support.