1611.1 Design rain loads.

Each portion of a roof shall be designed to sustain the load of rainwater as per the requirements of Chapter 8 of ASCE 7. Rain loads shall be based on the summation of the static head, d s, hydraulic head, d h, and ponding head, d p, using Equation 16-20. The hydraulic head shall be based on hydraulic test data or hydraulic calculations assuming a flow rate corresponding to a rainfall intensity equal to or greater than the 15-minute duration storm with return period given in Table 1611.1. Rainfall intensity shall be determined in inches per hour for 15-minute duration storms for the risk categories given in Table 1611.1. The ponding head shall be based on structural analysis as the depth of water due to deflections of the roof subjected to unfactored rain load and unfactored dead load.

Equation 16-20 R = 5.2( d s + d h + d p ) For SI: R = 0.0098( d s + d h + d p )

where:

d h = Hydraulic head equal to the depth of water on the undeflected roof above the inlet of the secondary drainage system for structural loading (SDSL) required to achieve the design flow, in inches (mm). d p = Ponding head equal to the depth of water due to deflections of the roof subjected to unfactored rain load and unfactored dead load, in inches (mm).

d s = Static head equal to the depth of water on the undeflected roof up to the inlet of the secondary drainage system for structural loading (SDSL), in inches (mm).

16-32 2025 CALIFORNIA BUILDING CODE

STRUCTURAL DESIGN

R = Rain load, in pounds per square foot (kN/m [2] ).

SDSL is the roof drainage system through which water is drained from the roof when the drainage systems listed in ASCE 7 Section 8.2 (a) through (d) are blocked or not working.

TABLE 1611.1—DESIGN STORM RETURN PERIOD BY RISK CATEGORY

RISK CATEGORY DESIGN STORM RETURN PERIOD
I & II 100 years
III 200 years
IV 500 years
Exceptions & meaning →

1611.2 Ponding instability.

Ponding instability on roofs shall be evaluated in accordance with ASCE 7.

Exceptions & meaning →

1611.3 Controlled drainage.

Roofs equipped with hardware to control the rate of drainage shall be equipped with a secondary drainage system at a higher elevation that limits accumulation of water on the roof above that elevation. Such roofs shall be designed to sustain the load of rainwater that will accumulate on them to the elevation of the secondary drainage system plus the uniform load caused by water that rises above the inlet of the secondary drainage system at its design flow determined from Section 1611.1. Such roofs shall be checked for ponding instability in accordance with Section 1611.2.

Exceptions & meaning →