Part 1 — UNREINFORCED MASONRY BEARING WALL BUILDINGS8928. - INFORMATION REQUIRED ON PLANS.

8928.2. - INFORMATION REQUIRED.

Arcadia Building Code · 2026-07 edition · updated 2026-07-25 · Arcadia

The plans shall accurately reflect the results of the engineering investigation and design and show all pertinent dimensions and sizes for plan review and construction. The following shall be provided:

(a)

Floor plans and roof plans shall show existing framing construction, diaphragm construction, proposed wall anchors, cross-ties and collectors. Existing nailing, anchors, ties and collectors shall also be shown on the plans if these are part of the design, and these structural elements need to be verified in the field.

(b)

At elevations where there are alterations or damage, details shall show roof and floor heights, dimensions of openings, location and extent of existing damage, and proposed repair.

(c)

Typical wall panel sections with panel thickness, height, location of anchors shall be provided.

(d)

Details shall include existing and new anchors and the method of development of anchor forces into the diaphragm framing; existing and/or new cross-ties; existing and/or new or improved support of roof and floor girders at pilasters or walls.