9.4.3.1 When fire sprinkler systems are installed in shell buildings of undetermined…¶
considered undetermined if a specific tenant/occupant is not identified at the time the fire sprinkler plan is submitted. Sprinklers in light hazard occupancies shall be one of the following:
(1) Quick-response type as defined in 3.3.223.4.16
(2) Residential Sprinklers in accordance with the requirements of Chapter 12
(3) Quick-response CMSA sprinklers
(4) ESFR Sprinklers
(5) Standard-response sprinklers used for modifications or additions to existing light hazard systems equipped with standard-response sprinklers
(6) Standard-response sprinklers used where individual standard-response sprinklers are replaced in existing light hazard systems
Section 16.12.3.3 is hereby revised as follows: