Chapter 13.04 — FIRE REGULATIONS1

Aliso Viejo Municipal Code § 10.4 Fire REGULATIONS1

Aliso Viejo Municipal Code · 2026-09 edition · updated 2026-09-30 · Aliso Viejo

Cite as: Aliso Viejo Municipal Code § 10.4 · Text as of 2026-09-30

10.4.1.1 All bolted joint accessories shall be cleaned and thoroughly coated with…

Exception: Bolted joint accessories made from 304 or 316 stainless steel.

Section 10.4.1.1.1 is hereby added as follows:

10.4.1.1.1 All bolts used in pipe-joint assembly shall be 316 stainless steel.

Section 10.4.3.2 is hereby deleted and replaced as follows:

Exceptions & meaning →

10.4.3.2 Where fire service mains enter the building adjacent to the foundation, the…

center of the vertical pipe. The pipe under the building or building foundation shall be 304 or 316 stainless steel and shall not contain mechanical joints or it shall comply with 10.4.3.2.1 through 10.4.3.2.4.

[Ord. 2025-246 § 5 (Exh. B)].