Chapter 13.04 — FIRE REGULATIONS1
Aliso Viejo Municipal Code § 10.1 Fire REGULATIONS1
Aliso Viejo Municipal Code · 2026-09 edition · updated 2026-09-30 · Aliso Viejo
Cite as: Aliso Viejo Municipal Code § 10.1 · Text as of 2026-09-30
10.1.5 All ferrous pipe and joints shall be polyethylene encased per AWWA C150, Method A, B, or C.¶
All fittings shall be protected with a loose 8-mil polyethylene tube or sheet. The ends of the tube or sheet
shall extend past the joint by a minimum of 12 inches and be sealed with 2-inch-wide tape approved for underground use. Galvanizing does not meet the requirements of this section.
Exception: 304 or 316 Stainless Steel pipe and fittings.
Section 10.4.1.1 is hereby revised as follows: