The lease for a former shop is signed, and the seating plan shows 60 chairs. Under the California Building Code, an assembly tenant space stays Group B only while its occupant load is less than 50; at or above that line a restaurant is Group A-2. Group A-2 has its own sprinkler triggers, counted per fire area, and the California Existing Building Code carries them into the old building.
Key numbers
| Figure | Governs | Section |
|---|---|---|
| Less than 50 persons | Assembly tenant space classified as Group B | CBC 303.1.1 |
| 15 net | Square feet per occupant, tables and chairs | CBC Table 1004.5 |
| 100 or more | Group A-2 fire-area occupant load that requires sprinklers | CBC 903.2.1.2 |
| 5,000 square feet | Group A-2 fire-area size that requires sprinklers | CBC 903.2.1.2 |
| 12,000 square feet | Group M fire-area size that requires sprinklers | CBC 903.2.7 |
The 50-person line decides the group
Section 303.1.1 reads: "A building or tenant space used for assembly purposes with an occupant load of less than 50 persons shall be classified as a Group B occupancy."
Section 303.3 names the use: "Group A-2 occupancy includes assembly uses intended for food and/or drink consumption, including but not limited to:" and the list includes "Restaurants, cafeterias and similar dining facilities (including associated commercial kitchens)".
Section 303.1.2 is a separate rule for a room "accessory to another occupancy". A café that is the whole tenant space is the subject of 303.1.1.
The occupant load comes from the floor area
Section 202 defines the term: "OCCUPANT LOAD. The number of persons for which the means of egress of a building or portion thereof is designed."
Section 1004.5 sets the number: "For areas without fixed seating, the occupant load shall be not less than that number determined by dividing the floor area under consideration by the occupant load factor".
Table 1004.5 lists "Unconcentrated (tables and chairs)" at 15 net, and note a reads "Floor area in square feet per occupant." As arithmetic, 1,500 net square feet of tables and chairs divides to 100. The 1004.5 Exception permits a lower actual count, "although less than those determined by calculation," only "Where approved by the building official".
Group A-2 brings its own sprinkler line
Section 903.2.1.2 requires a system "throughout stories containing Group A-2 occupancies" where one listed condition exists. The conditions include "The fire area exceeds 5,000 square feet", "The fire area has an occupant load of 100 or more." and "The fire area is located on a floor other than a level of exit discharge serving such occupancies." A fourth item, in italics as a California amendment, covers a structure over 5,000 square feet with more than one Group A-2 fire area, separated by 4-hour fire walls.
For the prior retail use, Section 903.2.7 starts at "A Group M fire area exceeds 12,000 square feet".
The existing building is reached through the CEBC
Section 903.2 opens with "Approved automatic sprinkler systems in new buildings and structures". The California Existing Building Code makes the link for an existing one. Section 1011.2.1 reads: "The installation of an automatic sprinkler system shall be required where there is a change of occupancy classification and Chapter 9 of the current California Building Code requires an automatic sprinkler system based on the new occupancy". It sets the extent: "The installation of the automatic sprinkler system shall be required within the area of the change of occupancy and areas of the building not separated by a fire wall from the change of occupancy."
What to check on the drawings
- The net floor area of the dining area, divided by 15, and each other function figured separately (1004.3).
- The fire-area boundaries and the total area they enclose.
- The café floor relative to the level of exit discharge.
- The nearest fire wall, because 1011.2.1 reaches every area not separated by one.
Currency
The building code pages print "2025 edition · updated 2026-10-24". The existing building code pages print "2025 edition · updated 2026-10-19" and cite that edition as "Effective January 1, 2026". No cited section prints a history line. Confirm which edition applies to the permit.
Frequently asked questions
Does a café with 49 chairs stay Group B?
Section 303.1.1 turns on the occupant load, and 1004.5 sets that load at "not less than" the floor area divided by the table factor. Its exception permits a lower actual count only "Where approved by the building official".
Does Group A-2 always need sprinklers?
No. Section 903.2.1.2 applies "where one of the following conditions exists", and lists fire-area size, fire-area occupant load and a floor other than a level of exit discharge.
Does the sprinkler stop at the tenant line?
Section 1011.2.1 names a different boundary: "areas of the building not separated by a fire wall from the change of occupancy."
Ask your own project's question in GoCodebook — your first answer is free: https://gocodebook.com/chat?utm_source=blog&utm_medium=article&utm_campaign=v4-05
Sources
- California Building Code 202 — definitions: https://gocodebook.com/library/us/ca/ca-building-code/chapter-2-definitions/section-202-definitions#202
- California Building Code 303.1.1 and 303.3: https://gocodebook.com/library/us/ca/ca-building-code/chapter-3-occupancy-classification-and-use/section-303-assembly-group-a#303.1.1
- California Building Code 1004.5 and Table 1004.5: https://gocodebook.com/library/us/ca/ca-building-code/chapter-10-means-of-egress/section-1004-occupant-load#1004.5
- California Building Code 903.2.1.2 and 903.2.7: https://gocodebook.com/library/us/ca/ca-building-code/chapter-9-fire-protection-and-life-safety-systems/section-903-automatic-sprinkler-systems#903.2.1.2
- California Existing Building Code 1011.2.1: https://gocodebook.com/library/us/ca/ca-existing-building-code/chapter-10-change-of-occupancy/section-1011-change-of-occupancy-classification#1011.2.1
Code text quoted as published in GoCodebook's library on 2026-11-17. This article does not replace permit review or professional judgment.