Chapter 10 — CHANGE OF OCCUPANCY

Section 1011 — CHANGE OF OCCUPANCY CLASSIFICATION

2025 California Existing Building Code (Title 24, Part 10) · 2025 edition · ingested 2026-07-07 · California

Full text via GoCodebook AI

We have the complete 2025 text of this code. Ask a question and get the exact controlling section with a citation.

Ask about this chapter

1011.1 General.

1011.1 General. The provisions of this section shall apply to buildings or portions thereof undergoing a change of occupancy classification. This includes a change of occupancy classification within a group as well as a change of occupancy classification from one group to a different group. The provisions of this section shall also apply where there is a change of occupancy within a building or portion thereof and there is a different fire protection system threshold requirement in Chapter 9 of the current California Building Code than exists in the current building or space. Such buildings…

1011.2 Fire protection systems.

1011.2 Fire protection systems. Fire protection systems shall be provided in accordance with Sections 1011.2.1 and 1011.2.2. 1011.2.1 Automatic sprinkler system. The installation of an automatic sprinkler system shall be required where there is a change of occupancy classification and Chapter 9 of the current California Building Code requires an automatic sprinkler system based on the new occupancy or where there is a change of occupancy within the space where there is a different fire protection system threshold requirement in Chapter 9 of the current California Building Code than exists in…

1011.3 Interior finish.

1011.3 Interior finish. In areas of the building undergoing the change of occupancy classification, the interior finish of walls and ceilings shall comply with the requirements of the California Building Code for the new occupancy classification.

1011.4 Enhanced classroom acoustics.

1011.4 Enhanced classroom acoustics. In Group E occupancies, where the work area is a Level 3 alteration, enhanced classroom acoustics shall be provided in all classrooms with a volume of 20,000 cubic feet (565 m [3] ) or less. Enhanced classroom acoustics shall comply with the reverberation time in Section 808 of ICC A117.1. on Jul 18, 2025 11:14 AM (CDT) THEREUNDER. � � � � � CHANGE OF OCCUPANCY

1011.5 Means of egress, general.

1011.5 Means of egress, general. Hazard categories in regard to life safety and means of egress shall be in accordance with Table 1011.5. TABLE 1011.5—MEANS OF EGRESS HAZARD CATEGORIESCol2 ------ RELATIVE HAZARDOCCUPANCY CLASSIFICATIONS 1 (Highest Hazard)H (Not Allowed) 2I-2; I-3; I-4(Not Allowed) 3A; E; M; R-1; R-2; R-4 4B; F-1; R-3; R-4, S-1 5 (Lowest Hazard)F-2; S-2; U 1011.5.1 Means of egress for change to a higher-hazard category. Where a change of occupancy classification is made to a higher-hazard category (lower number) as shown in Table 1011.5, the means of egress shall comply with…

1011.6 Heights and areas.

1011.6 Heights and areas. Hazard categories in regard to height and area shall be in accordance with Table 1011.6. TABLE 1011.6—HEIGHTS AND AREAS HAZARD CATEGORIESCol2 ------ RELATIVE HAZARDOCCUPANCY CLASSIFICATIONS 1 (Highest Hazard)H 2A-1; A-2; A-3; A-4; I; R-1; R-2; R-4, Condition 2 3E; F-1; S-1; M 4 (Lowest Hazard)B; F-2; S-2; A-5; R-3; R-4, Condition 1; U 1011.6.1 Height and area for change to a higher-hazard category. Where a change of occupancy classification is made to a higher-hazard category as shown in Table 1011.6, heights and areas of buildings and structures shall comply with…

1011.7 Exterior wall fire-resistance ratings.

1011.7 Exterior wall fire-resistance ratings. Hazard categories in regard to fire-resistance ratings of exterior walls shall be in accordance with Table 1011.7. TABLE 1011.7—EXPOSURE OF EXTERIOR WALLS HAZARD CATEGORIESCol2 ------ RELATIVE HAZARDOCCUPANCY CLASSIFICATION 1 (Highest Hazard)H 2F-1; M; S-1 3A; B; E; I; R 4 (Lowest Hazard)F-2; S-2; U on Jul 18, 2025 11:14 AM (CDT) THEREUNDER. � � CHANGE OF OCCUPANCY 1011.7.1 Exterior wall rating for change of occupancy classification to a higher-hazard category. Where a change of occupancy classification is made to a higher hazard category as shown…

1011.8 Enclosure of vertical shafts.

1011.8 Enclosure of vertical shafts. Enclosure of vertical shafts shall be in accordance with Sections 1011.8.1 through 1011.8.4. 1011.8.1 Minimum requirements. Vertical shafts shall be designed to meet the California Building Code requirements for atriums or the requirements of this section. 1011.8.2 Stairways. Where a change of occupancy classification is made to a higher-hazard category as shown in Table 1011.5, interior stairways shall be enclosed as required by the California Building Code . Exceptions: 1. In other than Group I occupancies, an enclosure shall not be required for openings…