CWUIC · California Wildland-Urban Interface Code

Fire‑Smart Vegetation & Planting Rules

This hub summarizes CWUIC planting rules: mandatory fire‑smart vegetation, landscape plan contents, spacing/clearance limits, and ongoing defensible‑space obligations.

Last reviewed: July 6, 2026

Overview

This area of the California Wildland‑Urban Interface Code (CWUIC) governs selection, layout and ongoing maintenance of landscaping and fuels near buildings in fire‑hazard areas. It requires new plantings to be “fire‑smart,” defines fuel‑management zones, and sets planting limits and spacing to reduce ignition risk and ember pathways (see §603.1–603.4 and Appendix F) .

Key operational rules include landscape plan requirements (§603.3 and §603.3.1) — a plan must show 30‑ and 100‑foot fuel management zones, plant lists and irrigated areas — plus specific shrub and tree spacing and height limits in §603.4.1 and §603.4.2 to prevent ladder fuels and crown continuity . Appendix B explains vegetation management plan content for projects, and Appendix F summarizes characteristics used to identify fire‑smart plants .

Maintenance and defensible‑space obligations are enforced separately: Chapter 6 requires ongoing hazardous‑vegetation control and references defensible‑space law and clearance rules in §604, plus related rules on firewood storage (§607) and building siting/setbacks (§608) that affect planting choices and required clearances .

In this section

Code references

Grounded in the retrieved California Wildland-Urban Interface Code — click a citation to read the verbatim passage:

  • CWUIC § 603.2 High relevance — show source text

    603.2 Application. All new plantings of vegetation in State Responsibility Area (SRA) and Local Responsibility Areas (LRA) designated as a Fire Hazard Severity Zone shall comply with Sections 603.3 through 603.4.2.1.

    603.3 Landscape plans. Landscape plans shall be provided when required by the code official. The landscape plan shall include devel- opment and maintenance requirements for the vegetation management zone adjacent to structures and roadways, and provide significant fire hazard reduction benefits for public and firefighting safety.

    603.3.1 Contents. Landscape plans shall contain the following: 1. Delineation of the 30-foot (9144 mm) and 100-foot (30 480 mm) fuel management zones from all structures. 2. Identification of existing vegetation to remain and proposed new vegetation. 3. Identification of irrigated areas. 4. A plant legend with both botanical and common names, and identification of all plant material symbols. 5. Identification of ground coverings within the 30-foot (9144 mm) zone.

    603.4 Vegetation. All new vegetation shall be fire-smart vegetation in accordance with this section.

    Exception: Trees classified as nonfire-smart vegetation complying with Section 603.4.2.1.

    To be considered fire-smart vegetation, vegetation must meet at least one of the following: 1. Be identified as fire-smart vegetation in an approved book, journal or listing from an approved organization. 2. Be identified as fire-smart vegetation by a licensed landscape architect with supporting justification. 3. Plants considered fire-smart vegetation and approved by the local enforcing agency.

    603.4.1 Shrubs. All new plantings of shrubs shall comply with the following: 1. Shrubs shall not exceed 6 feet (1829 mm) in height. 2. Groupings of shrubs are limited to a maximum aggregate diameter of 10 feet (3048 mm). 3. Shrub groupings shall be separated from other groupings a minimum of 15 feet (4572 mm). 4. Shrub groupings shall be separated from structures a minimum of 30 feet (9144 mm). 5. Where shrubs are located below or within a tree’s drip line, the lowest tree branch shall be a minimum of three times the height of the understory shrubs or 10 feet (3048 mm), whichever is greater.

    603.4.2 Trees. Trees shall be managed as follows within the 30-foot zone (9144 mm) of a structure: 1. New trees shall be planted and maintained so that the tree’s drip line at maturity is a minimum of 10 feet (3048 mm) from any combustible structure. 2. The horizontal distance between crowns of new trees and crowns of adjacent trees shall not be less than 10 feet (3048 mm). 3. Existing trees shall be trimmed to provide a minimum separation of 10 feet (3048 mm) away from chimney and stovepipe outlets per California Code of Regulations, Title 14, Section 1299.03.

  • CWUIC § 603.4.1 High relevance — show source text

    603.4.1 Shrubs. All new plantings of shrubs shall comply with the following: 1. Shrubs shall not exceed 6 feet (1829 mm) in height. 2. Groupings of shrubs are limited to a maximum aggregate diameter of 10 feet (3048 mm). 3. Shrub groupings shall be separated from other groupings a minimum of 15 feet (4572 mm). 4. Shrub groupings shall be separated from structures a minimum of 30 feet (9144 mm). 5. Where shrubs are located below or within a tree’s drip line, the lowest tree branch shall be a minimum of three times the height of the understory shrubs or 10 feet (3048 mm), whichever is greater.

    603.4.2 Trees. Trees shall be managed as follows within the 30-foot zone (9144 mm) of a structure: 1. New trees shall be planted and maintained so that the tree’s drip line at maturity is a minimum of 10 feet (3048 mm) from any combustible structure. 2. The horizontal distance between crowns of new trees and crowns of adjacent trees shall not be less than 10 feet (3048 mm). 3. Existing trees shall be trimmed to provide a minimum separation of 10 feet (3048 mm) away from chimney and stovepipe outlets per California Code of Regulations, Title 14, Section 1299.03.

    603.4.2.1 Nonfire-smart vegetation. New trees not classified as fire-smart vegetation, such as conifers, palms, pepper trees and eucalyptus species, shall be permitted provided the tree is planted and maintained in accordance with one of the following: 1. The tree is planted so that the tree’s drip line at maturity is a minimum of 30 feet (9144 mm) from an applicable building. 2. The tree is planted so that the tree’s drip line at maturity is a minimum of 10 feet (3048 mm) from any combustible struc- ture, and is well pruned and maintained so as not to form a means of rapidly transmitting fire from other nearby vegetation to the structure or from the structure to nearby vegetation or to interrupt the advance of embers toward a

    structure.

    6-4 2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE PROTECTION REQUIREMENTS

    SECTION 604—MAINTENANCE OF DEFENSIBLE SPACE

    604.1 General. Hazardous vegetation and fuels shall be managed to reduce the severity of potential exterior wildfire exposure to build- ings and to reduce the risk of fire spreading to buildings as required by applicable laws and regulations.

    Defensible space shall be managed around all buildings and structures in State Responsibility Areas (SRA) as required in Public Resources Code 4291.

    604.2 Application. Buildings and structures located in the following areas shall maintain the required hazardous vegetation and fuel management: 1. All unincorporated lands designated as a State Responsibility Area (SRA). 2. Land designated as a Very High Fire Hazard Severity Zone by a city or local agency. 3. Land designated in a city or local agency ordinance as a wildland-urban interface (WUI) area.

  • CWUIC § 6-3 High relevance — show source text

    2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE 6-3

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE PROTECTION REQUIREMENTS

    602.3.2 Final fire protection plan. Final fire protection plan shall include items listed in Section 602.3.1 and the following: 1. A map identifying all proposed plants in the fuel modification zones with a legend that includes a symbol for each proposed plant species. The plan shall include specific information on each species proposed, including but not limited to: 1.1. The plant life-form;

    1.2. The scientific and common name; and

    1.3. The expected height and width for mature growth. 2. Identification of irrigated and nonirrigated zones. 3. Requirements for vegetation reduction around emergency access and evacuation routes. 4. Identification of points of access for equipment and personnel to maintain vegetation in common areas. 5. Legally binding statements regarding community responsibility for maintenance of fuel modification zones. 6. Legally binding statements to be included in covenants, conditions and restrictions regarding property owner responsibili- ties for vegetation maintenance.

    SECTION 603— VEGETATION PLAN

    603.1 General. Planting of vegetation for new landscaping shall be selected to reduce vegetation in proximity to a structure and to maintain vegetation as it matures.

    603.2 Application. All new plantings of vegetation in State Responsibility Area (SRA) and Local Responsibility Areas (LRA) designated as a Fire Hazard Severity Zone shall comply with Sections 603.3 through 603.4.2.1.

    603.3 Landscape plans. Landscape plans shall be provided when required by the code official. The landscape plan shall include devel- opment and maintenance requirements for the vegetation management zone adjacent to structures and roadways, and provide significant fire hazard reduction benefits for public and firefighting safety.

    603.3.1 Contents. Landscape plans shall contain the following: 1. Delineation of the 30-foot (9144 mm) and 100-foot (30 480 mm) fuel management zones from all structures. 2. Identification of existing vegetation to remain and proposed new vegetation. 3. Identification of irrigated areas. 4. A plant legend with both botanical and common names, and identification of all plant material symbols. 5. Identification of ground coverings within the 30-foot (9144 mm) zone.

    603.4 Vegetation. All new vegetation shall be fire-smart vegetation in accordance with this section.

    Exception: Trees classified as nonfire-smart vegetation complying with Section 603.4.2.1.

    To be considered fire-smart vegetation, vegetation must meet at least one of the following: 1. Be identified as fire-smart vegetation in an approved book, journal or listing from an approved organization. 2. Be identified as fire-smart vegetation by a licensed landscape architect with supporting justification. 3. Plants considered fire-smart vegetation and approved by the local enforcing agency.

  • CWUIC § 6-4 Medium relevance — show source text

    structure.

    6-4 2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE PROTECTION REQUIREMENTS

    SECTION 604—MAINTENANCE OF DEFENSIBLE SPACE

    604.1 General. Hazardous vegetation and fuels shall be managed to reduce the severity of potential exterior wildfire exposure to build- ings and to reduce the risk of fire spreading to buildings as required by applicable laws and regulations.

    Defensible space shall be managed around all buildings and structures in State Responsibility Areas (SRA) as required in Public Resources Code 4291.

    604.2 Application. Buildings and structures located in the following areas shall maintain the required hazardous vegetation and fuel management: 1. All unincorporated lands designated as a State Responsibility Area (SRA). 2. Land designated as a Very High Fire Hazard Severity Zone by a city or local agency. 3. Land designated in a city or local agency ordinance as a wildland-urban interface (WUI) area.

    604.3 Requirements. Hazardous vegetation and fuels around all buildings and structures shall be maintained in accordance with the following laws and regulations: 1. Public Resources Code, Section 4291.

    2. California Code of Regulations, Title 14, Division 1.5, Chapter 7, Subchapter 3, Article 3, Section 1299.03. 3. California Government Code, Section 51182.

    4. California Code of Regulations, Title 19, Division 1, Chapter 7, Subchapter 1, Section 3.07.

    604.4 Outbuildings. Outbuildings shall have a minimum clearance of 10 feet (3048 mm) down to bare mineral soil in all directions. Vege- tation more than 10 feet (3048 mm) but less than 20 feet (6096 mm) from outbuildings shall be fire-smart vegetation.

    604.5 Disposal of flammable vegetation and fuels. The disposal, including burning or removal to a site approved by the local jurisdic- tion in consultation with the fire authority, of flammable vegetation and fuels caused by site, road and driveway construction shall be in accordance with all applicable laws and regulations. [CCR T14 §1276.05]

    SECTION 605—SPARK ARRESTORS

    605.1 General. Chimneys serving fireplaces, barbecues, incinerators or decorative heating appliances in which solid or liquid fuel is used shall be provided with a spark arrestor. Spark arrestors shall be constructed of woven or welded wire screening of 12 USA standard gage wire (0.1046 inch) (2.66 mm) having openings not exceeding [1] / 2 inch (12.7 mm).

    605.2 Net free area. The net free area of the spark arrestor shall be not less than four times the net free area of the outlet of the chimney.

    SECTION 606—LIQUEFIED PETROLEUM GAS INSTALLATIONS

    606.1 General. The storage of liquefied petroleum gas (LP-gas) and the installation and maintenance of pertinent equipment shall be in accordance with the California Fire Code .

    606.2 Location of containers or tanks. LP-gas containers or tanks shall be located within the defensible space in accordance with the California Fire Code .

  • CWUIC § F101 Medium relevance — show source text

    SECTION F101—GENERAL

    F101.1 Characteristics of fire-smart vegetation. All plants will burn under extreme fire weather conditions, such as drought. However, plants burn at different intensities and rates of consumption. Fire-smart plants burn at a relatively low intensity, slow rates of spread and with short flame lengths. The following are characteristics of fire-smart vegetation:

    1. Growth with little or no accumulation of dead vegetation (either on the ground or standing upright).
    2. Nonresinous plants (willow, poplar or tulip trees).
    3. Low volume of total vegetation (for example, a grass area as opposed to a forest or shrub-covered land).
    4. Plants with high live fuel moisture (plants that contain a large amount of water in comparison to their dry weight).
    5. Drought-tolerant plants (deeply rooted plants with thick, heavy leaves).
    6. Stands without ladder fuels (plants without small, fine branches and limbs between the ground and the canopy of overtopping shrubs and trees).
    7. Plants requiring little maintenance (slow-growing plants that, when maintained, require little care).
    8. Plants with woody stems and branches that require prolonged heating to ignite.

    2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE APPENDIX F-3

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX F-4 2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CALIFORNIA WILDLAND-URBAN INTERFACE CODE – MATRIX ADOPTION TABLE

    APPENDIX G – VOLUNTARY HOME HARDENING RECOMMENDATIONS

    (Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

    Adopting Agency BSC BSC-
    CG
    SFM Col5 HCD Col7 Col8 DSA Col10 OSHPD Col12 Col13 Col14 Col15 Col16 BSCC DPH AGR DWR CEC CA SL SLC
    Adopting Agency BSC BSC-
    CG
    T-24 T-19* 1 2 1/AC AC SS 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
    Adopt Entire Chapter X
    Adopt Entire Chapter as
    amended (amended sections
    listed below)
    Adopt only those sections that
    are listed below
    [California Code of Regulations,
    Title 19, Division 1]
    Chapter / Section
  • CWUIC § 1.11. Medium relevance — show source text
    • The California Code of Regulations (CCR), Title 19, Division 1 provisions that are found in the California Wildland-Urban Interface Code are a reprint from the current CCR, Title 19, Division 1 text for the code user’s convenience only. The scope, applicability and appeals procedures of CCR, Title 19, Division I remain the same. The state agency does not adopt sections identified by the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.

    The California Code of Regulations (CCR), Title 14, Division 1.5 provisions that are found in the California Wildland-Urban Interface Code are not listed in the Matrix Adoption Tables as they are not within the State Fire Marshal’s authority to adopt. These provisions are a reprint from the current CCR, Title 14, Division 1.5 text for the code user’s convenience only and are identified in the body of the code by square brackets containing references to applicable Title 14 sections.

    2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE APPENDIX F-1

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX F-2 2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    F CHARACTERISTICS OF FIRE-SMART VEGETATION

    This appendix is for informational purposes and is not intended for adoption.

    User notes:

    About this appendix: Appendix F is an informational appendix provided for the convenience of the code user. It is simply a compilation of the eight characteristics of fire-smart vegetation that can be used effectively within wildland-urban interface areas to reduce the likelihood of fire spread through vegetation.

    SECTION F101—GENERAL

    F101.1 Characteristics of fire-smart vegetation. All plants will burn under extreme fire weather conditions, such as drought. However, plants burn at different intensities and rates of consumption. Fire-smart plants burn at a relatively low intensity, slow rates of spread and with short flame lengths. The following are characteristics of fire-smart vegetation:

    1. Growth with little or no accumulation of dead vegetation (either on the ground or standing upright).
    2. Nonresinous plants (willow, poplar or tulip trees).
    3. Low volume of total vegetation (for example, a grass area as opposed to a forest or shrub-covered land).
    4. Plants with high live fuel moisture (plants that contain a large amount of water in comparison to their dry weight).
    5. Drought-tolerant plants (deeply rooted plants with thick, heavy leaves).
    6. Stands without ladder fuels (plants without small, fine branches and limbs between the ground and the canopy of overtopping shrubs and trees).
    7. Plants requiring little maintenance (slow-growing plants that, when maintained, require little care).
    8. Plants with woody stems and branches that require prolonged heating to ignite.

    2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE APPENDIX F-3

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX F-4 2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE

  • CWUIC § 2-3 Medium relevance — show source text

    EXTERIOR WALL COVERING. A material or assembly of materials applied on the exterior side of exterior walls for the purpose of providing a weather-resisting barrier, insulation or for aesthetics, including but not limited to veneers, siding, exterior insulation and finish systems, rainscreen systems, architectural trim, and embellishments such as cornices, soffits, facias, gutters and leaders.

    [F] FIRE CHIEF. The chief officer or the chief officer’s authorized representative of the fire department serving the jurisdiction.

    2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE 2-3

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    DEFINITIONS

    FIRE CODE OFFICIAL. The fire chief or other designated authority charged with the administration and enforcement of the California Fire Code, or a duly authorized representative.

    FIRE FLOW CALCULATION AREA. The floor area, in square feet (square meters), used to determine the adequate water supply.

    FIRE HAZARD SEVERITY ZONES. Geographical areas designated pursuant to California Public Resources Codes, Sections 4201 through 4204 California Government Code, Sections 51175 through 51189.

    The map, approved by the Office of the State Fire Marshal, is hereby incorporated by reference and entitled “State Responsibility Area Fire Hazard Severity Zones,” dated September 29, 2023.

    FIRE PROTECTION PLAN. A document prepared for a specific project or development proposed for the wildland-urban interface area. It describes ways to minimize and mitigate potential for loss from wildfire exposure.

    FIRE WEATHER. Weather conditions favorable to the ignition and rapid spread of fire. In wildfires, this generally includes high temperatures combined with strong winds and low humidity. See “Critical fire weather.”

    FIRE-RESISTANCE-RATED CONSTRUCTION. The use of materials and systems in the design and construction of a building or structure to safeguard against the spread of fire within a building or structure and the spread of fire to or from buildings or structures to the wildland-urban interface area.

    FIRE-SMART VEGETATION. Plants, shrubs, trees and other vegetation that exhibit properties, such as high moisture content, little accu- mulation of dead vegetation and low sap or resin content, that make them less likely to ignite or contribute heat or spread flame in a fire than native vegetation typically found in the region.

    ( Note: The following sources contain examples of types of vegetation that can be considered as fire-smart vegetation: Fire-resistant Plants for Home Landscapes, A Pacific Northwest Extension publication; Home Landscaping for Fire, University of California Division of Agriculture and Natural Resources; Sunset Western Garden Book.)

    [BG] FLAME SPREAD INDEX. A comparative measure, expressed as a dimensionless number, derived from visual measurements of the spread of flame versus time for a material tested in accordance with ASTM E84 or UL 723.

    FUEL. Any combustible material, including petroleum-based products, cultivated landscape plants, grasses, weeds and wildland vegetation.

    FUEL BREAK (applicable to CCR, Title 14 provisions only). A strategically located area where the volume and arrangement of vegetation has been managed to limit fire intensity, fire severity, rate of spread, crown fire potential and/or ember production. [CCR Title 14 §1270.01(n)]

  • CWUIC § 1299.04 Medium relevance — show source text

    of defensible space clearance shall be maintained in two distinct “Zones” as follows: “Zone 1” extends thirty_ feet (30 ft.) out from each “Building or Structure,” or to the property line, whichever comes first; “Zone 2” extends from thirty feet (30 ft.) to one hundred feet (100 ft.) from each “Building or Structure,” but not beyond the property line. The vegetation treatment requirements for Zone 1 are more restrictive than for Zone 2, as provided in (a) and (b) below. The Department of Forestry and Fire Protection's “Prop- erty Inspection Guide, 2000 version, April 2000,” provides additional guidance on vegetation treatment within Zone 1 and Zone 2, but is not mandatory and is not intended as a substitute for these regulations. (a) Zone 1 Requirements: (1) Remove all dead or dying grass, plants, shrubs, trees, branches, leaves, weeds, and pine needles from the Zone whether such vegetation occurs in yard areas around the “Building or Structure,” on the roof or rain gutters of the “Building or Structure,” or any other location within the Zone. (2) Remove dead tree or shrub branches that overhang roofs, below or adjacent to windows, or which are adjacent to wall surfaces, and keep all branches a minimum of ten feet (10 ft.) away from chimney and stovepipe outlets. (3) Relocate exposed firewood piles outside of Zone 1 unless they are completely covered in a fire resistant material. (4) Remove flammable vegetation and items that could catch fire which are adjacent to or under combustible decks, balco- nies and stairs.

    (b) Zone 2 Requirements: (1) In this zone create horizontal and vertical spacing among shrubs and trees using the “Fuel Separation” method, the “Continuous Tree Canopy” method or a combination of both to achieve defensible space clearance requirements. Further guidance regarding these methods is contained in the State Board of Forestry and Fire Protection's, “General Guidelines for Creating Defensible Space, February 8, 2006,” incorporated herein by reference, and the “Property Inspec- tion Guide” referenced elsewhere in this regulation. (2) In both the Fuel Separation and Continuous Tree Canopy methods the following standards apply: (A) Dead and dying woody surface fuels and aerial fuels shall be removed. Loose surface litter, normally consisting of fallen leaves or needles, twigs, bark, cones, and small branches, shall be permitted to a maximum depth of three inches (3 in.). (B) Cut annual grasses and forbs down to a maximum height of four inches (4 in.). (C) All exposed wood piles must have a minimum of ten feet (10 ft.) of clearance, down to bare mineral soil, in all directions.

    (c) For both Zones 1 and 2: (1) “Outbuildings” and Liquid Propane Gas (LPG) storage tanks shall have the following minimum clearance: ten feet (10 ft.) of clearance to bare mineral soil and no flammable vegetation for an additional ten feet (10 ft.) around their exterior. (2) Protect water quality. Do not clear vegetation to bare mineral soil and avoid the use of heavy equipment in and around streams and seasonal drainages. Vegetation removal can cause soil erosion, especially on steep slopes. Keep soil distur- bance to a minimum on steep slopes.

    1299.04 Additional clearance.

  • CWUIC § 102.4 Medium relevance — show source text

    The chapter includes mitigation strategies to reduce the hazards of fire originating within a structure spreading to wildland and fire originating in wildland spreading to structures.

    Chapter 7 Referenced Standards.

    Chapter 7 lists all of the product and installation standards and codes that are referenced throughout Chapters 1 through 6 and includes identification of the promulgators and the section numbers in which the standards and codes are referenced. As stated in Section 102.4, these standards and codes become an enforceable part of the code (to the prescribed extent of the reference) as if printed in the body of the code.

    Appendix A General Requirements.

    Appendix A, while not part of the code, can become part of the code when specifically included in the adopting ordinance. Its purpose is to provide fire-protection measures supplemental to those found in Chapter 6 to reduce the threat of wildfire in a wildland-urban interface area and improve the capability for controlling such fires. This appendix includes detailed requirements for vegetation control; the code official’s authority to close wildland-interface areas in times of high fire danger; control of fires, fireworks usage and other sources of ignition; storage of hazardous materials and combustibles; bans on the dumping of waste materials and ashes and coals in wildlandurban interface areas; protection of pumps and water supplies; and limits on temporary uses within the wildland-urban interface area.

    Appendix B Vegetation Management Plan.

    Appendix B, while not part of the code, can become part of the code when specifically included in the adopting ordinance. Its purpose is to provide criteria for submitting vegetation management plans, specifying their content and establishing a criterion for considering vegetation management as being a fuel modification.

    Appendix C Community Wildland-Urban Interface (WUI) Fire Hazard Evaluation Framework.

    Appendix C contains a preliminary Community WUI Fire Hazard Evaluation Framework as a suggested methodology to begin to support communities at risk in the identification of their unique hazards and to provide common metrics for comparisons between communities. This preliminary framework includes information on community size, population and fuels; on notification and evacuation; and on the community infrastructure and firefighting response potential. Aspects of this framework may already be included in various community- level documents, such as Community Wildfire Protection Plans or evacuation plans. Development of a standard framework will (1) consolidate relevant WUI fire hazard and planning information in one place, and (2) allow for cross-community comparisons.

    The evaluation required to implement this framework will support prefire hazard assessment and during-fire response operations. An increased understanding of fire evacuation, fire structural response and fire defensive action relationships is needed to assess the over- all community WUI fire hazard. The quantification of these relationships will enable communities to optimize the community-level response to WUI fire hazards in a more integrated approach and result in increased life safety and reduced losses.

    Appendix D Model Ordinance for Fire Hazard Severity Zone Adoption.

    Appendix D is an informational appendix that is a sample ordinance designed as guidance for a city, county, city and county, or fire district to establish and designate fire hazard severity zones within their jurisdiction.

    Appendix E Reserved.

    Appendix F Characteristics of Fire-Smart Vegetation.

    Appendix F is an informational appendix provided for the convenience of the code user. It is simply a compilation of the eight characteristics of fire-smart vegetation that can be used effectively within wildland-urban interface areas to reduce the likelihood of fire spread through vegetation.

    **App

  • CWUIC § B101 Medium relevance — show source text

    SECTION B101—GENERAL

    B101.1 Scope. Vegetation management plans shall be submitted to the code official for review and approval as part of the plans required for a permit.

    B101.2 Plan content. Vegetation management plans shall describe all actions that will be taken to prevent a fire from being carried toward or away from the building. A vegetation management plan shall include the following information:

    1. A copy of the site plan.
    2. Methods and timetables for controlling, changing or modifying areas on the property. Elements of the plan shall include removal of slash, snags, vegetation that may grow into overhead electrical lines, other ground fuels, ladder fuels and dead trees, and the thinning of live trees.
    3. A plan for maintaining the proposed fuel-reduction measures.

    B101.3 Fuel modification. To be considered a fuel modification for purposes of this code, continuous maintenance of the clearance is required.

    2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE APPENDIX B-3

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX B-4 2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CALIFORNIA WILDLAND-URBAN INTERFACE CODE – MATRIX ADOPTION TABLE APPENDIX C – COMMUNITY WILDLAND-URBAN INTERFACE (WUI) FIRE HAZARD EVALUATION FRAMEWORK

    (Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

    (Not adopted by the State Fire Marshal)

    Adopting Agency BSC BSC-
    CG
    SFM Col5 HCD Col7 Col8 DSA Col10 OSHPD Col12 Col13 Col14 Col15 Col16 BSCC DPH AGR DWR CEC CA SL SLC
    Adopting Agency BSC BSC-
    CG
    T-24 T-19* 1 2 1/AC AC SS 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
    Adopt Entire Chapter
    Adopt Entire Chapter as
    amended (amended sections
    listed below)
    Adopt only those sections that
    are listed below
    [California Code of Regulations,
    Title 19, Division 1]
    Chapter / Section

Frequently asked questions

What counts as “fire‑smart” vegetation?

Fire‑smart vegetation is plant material with characteristics that reduce fire intensity and spread (high live‑fuel moisture, low dead‑fuel accumulation, low resin content, limited ladder fuels). Appendix F lists those characteristics and sources for recommended plant lists .

How close can I plant shrubs and trees to a house?

The code caps new shrub height and grouping/spacing in §603.4.1 and requires tree drip lines at maturity be kept a minimum distance from combustible structures (typically 10 ft; non‑fire‑smart trees may require larger setbacks or special maintenance per §603.4.2/§603.4.2.1) .

When is a landscape or vegetation management plan required?

A landscape or vegetation management plan is required when the code official so directs for projects in SRAs or designated fire‑hazard zones; plans must map fuel‑management zones, identify species, irrigated areas and maintenance responsibilities as described in §603.3.1 and Appendix B (vegetation management plan criteria) .