CWUIC · California Wildland-Urban Interface Code
How must roof covering voids, underlayment and airspace be constructed?
If a roofing profile creates a space above a combustible deck, CWUIC requires either a 72‑lb mineral cap sheet (ASTM D3909) or a listed Class A underlayment (ASTM E108/UL 790) installed per its listing, plus bird stops at eaves and mudded hip/ridge caps. Exceptions allow 1" mineral wool board in lieu of the cap sheet or an FRT exterior‑rated sheathing to waive the Class A underlayment requirement; see **§ 504.2.1**, **§ 504.2.1.1**, and **§ 504.2.1.2**.
Last reviewed: July 6, 2026
What the code requires — plain English
When a roof covering creates a void or airspace over a combustible deck, the roof must either have a 72 lb. (32.7 kg) mineral-surfaced cap sheet installed over the deck or a listed, Class A roof underlayment installed as part of a tested Class A roof assembly. Also, bird stops at eaves and hip/ridge caps mudded in are required to reduce ember/debris entry. These requirements are set out in § 504.2.1, § 504.2.1.1 and § 504.2.1.2 of the California Wildland‑Urban Interface Code.
If a roofing profile leaves a space between roofing and a combustible roof deck, either protect the deck with the specified mineral cap sheet (or equivalent noncombustible board) or install a listed Class A underlayment — and keep bird stops and mudded hip/ridge caps in place to block embers.
Requirements in detail
When the roof covering creates an airspace (combustible deck + profile creates void)
- Install a 72 lb. (32.7 kg) cap sheet complying with ASTM D3909 over the roof deck. § 504.2.1.1.
- Exception: the cap sheet is not required where at least 1 inch of mineral wool board or other noncombustible material is located between the roofing and the wood framing or deck. § 504.2.1.1 (Exception).
- Install bird stops at the eaves where the profile fits, to prevent entry of debris at the eave. § 504.2.1.1.
- Hip and ridge caps shall be mudded in to prevent intrusion of fire or embers. § 504.2.1.1.
When using roof underlayment to address the void
- Install a listed and labeled roof underlayment that was tested as part of the roof assembly to ASTM E108 or UL 790 and shown to achieve a Class A fire classification. Install in accordance with the underlayment manufacturer’s installation instructions and listing. § 504.2.1.2.
- Bird stops at the eaves and mudded hip/ridge caps are also required when the profile fits. § 504.2.1.2.
- Exception: If the roof sheathing is fire-retardant‑treated (FRT) wood labeled for exterior use and it complies with Section 2303.2 of the California Building Code, the underlayment is not required to have a Class A classification. § 504.2.1.2 (Exception).
Quick-reference table (decision-relevant dimensions/values)
| Item | Value / Requirement | Code Reference |
|---|---|---|
| Cap sheet weight | 72 lb. (32.7 kg) mineral‑surfaced cap sheet; comply with ASTM D3909 | § 504.2.1.1 |
| Noncombustible board exception | Not less than 1 inch of mineral wool board or equivalent noncombustible material in lieu of cap sheet | § 504.2.1.1 (Exception) |
| Underlayment fire classification | Listed/labeled underlayment tested with the roof assembly to ASTM E108 or UL 790 for Class A | § 504.2.1.2 |
| Underlayment exception (FRT) | Fire-retardant-treated wood sheathing labeled for exterior use per CBC § 2303.2 — Class A underlayment not required | § 504.2.1.2 (Exception) |
| Eave protection | Bird stops at eaves where profile fits | § 504.2.1.1 and § 504.2.1.2 |
| Hip & ridge protection | Hip and ridge caps shall be mudded in to resist ember intrusion | § 504.2.1.1 and § 504.2.1.2 |
Exceptions & special cases
- The cap sheet requirement can be avoided if you provide a minimum 1‑inch layer of mineral wool board (or other noncombustible material) between roofing and the combustible deck (§ 504.2.1.1).
- The Class A underlayment requirement is waived when the roof sheathing is FRT wood labeled for exterior use and meeting CBC § 2303.2 — confirm labeling and compliance before relying on this exception (§ 504.2.1.2 Exception).
- The code does not state a minimum numeric thickness for the “airspace” itself or a minimum clearance dimension created by the roofing profile; it only triggers the cap‑sheet/underlayment requirements when such a void exists (§ 504.2.1). If you need a numeric clearance for structural/ventilation reasons, consult the roof‑covering manufacturer and the Building Code provisions that govern decks and ventilation.
Common mistakes
- Assuming any underlayment is acceptable — the underlayment must be listed and tested with the roof assembly to achieve Class A unless the FRT exception applies (§ 504.2.1.2).
- Installing a cap sheet lighter than 72 lb. AST M D3909 or using a nonconforming material in place of the specified cap sheet (§ 504.2.1.1).
- Forgetting bird stops at the eaves or failing to mudd hip/ridge caps — both are explicit ember‑ingress controls required by the sections. § 504.2.1.1 / § 504.2.1.2.
- Relying on a manufacturer’s general underlayment instructions but not verifying the listing showing testing with the roof assembly to ASTM E108 or UL 790. The listing is required by § 504.2.1.2.
Worked example
Scenario: You are reroofing a home in the WUI. The roof covering is a profiled metal shingle that leaves an airspace over a combustible wood structural deck.
- Because the roofing profile creates a void over a combustible deck, § 504.2.1 applies and you must comply with § 504.2.1.1 or § 504.2.1.2.
- Option A — cap sheet route: install a 72 lb. mineral‑surfaced cap sheet (ASTM D3909) over the wood deck (meets § 504.2.1.1). Add bird stops at the eaves where the profile fits and mud hip and ridge caps.
- Option B — underlayment route: install a listed Class A underlayment (tested as part of the roof assembly to ASTM E108 or UL 790) in accordance with the listing and manufacturer instructions; also install bird stops and mudded hip/ridge caps. Verify the underlayment’s listing specifically shows it as part of a Class A assembly with your roof covering. § 504.2.1.2.
- If the roof sheathing is FRT wood, labeled for exterior use and meeting CBC § 2303.2, you may choose Option B without requiring Class A underlayment — but only after verifying the sheathing labeling and applicability of the CBC section. § 504.2.1.2 (Exception).
Related provisions
- § 504.2.1 — Roof covering voids (general trigger for § 504.2.1.1 / 504.2.1.2).
- § 504.2.1.1 — Airspace under roof covering (cap sheet, 1" mineral wool exception, bird stops, mudded hip/ridge).
- § 504.2.1.2 — Roof underlayment (listed Class A underlayment requirement; FRT exception).
- § 504.2.2 — Roof valleys (valley flashing and mineral cap sheet requirement).
- § 504.3 — Protection of enclosed eaves (materials and performance options for underside protection).
Code references
Grounded in the retrieved California Wildland-Urban Interface Code — click a citation to read the verbatim passage:
CWUIC § 1.1 High relevance — show source text
For roof slopes of 4 units vertical in 12 units horizontal (4:12)
or greater, underlayment shall be one layer applied in the
following manner: underlayment shall be applied shingle
fashion, parallel to and starting from the eave and lapped 2
inches. End laps shall be 4 inches and shall be offset by 6 feet.
3. A single layer of self-adhering polymer modified bitumen
underlayment complying with ASTM D1970, installed in
accordance with the underlayment and roof covering manu-
facturer’s installation instructions for the deck material, roof
ventilation configuration and climate exposure of the roof
covering.|Underlayment shall be one of the following:
1. Two layers of mechanically fastened underlayment applied in
the following manner: Apply a strip of underlayment felt that is
half the width of a full sheet parallel to and starting at the
eaves, fastened sufficiently to hold in place. Starting at the
eave, apply full width sheets of underlayment, overlapping
successive sheets half the width of a full sheet plus 2 inches.
Distortionsin the underlayment shall not interferewith the abil-
ity of the shingles to seal. End laps shall be 4 inches and shall
be offset by 6 feet.
2. A minimum 4-inch-wide strip of self-adhering polymer modi-
fied bitumen underlayment complying with ASTM D1970,
installed in accordance with the manufacturer’s installation
instructions for the deck material, shall be applied over all
joints in the roof decking. An approved underlayment comply-
ing with Table R905.1.1(1) for the applicable roof covering shall
be applied over the entire roof over the 4-inch-wide
membrane strips.
3. A single layer of self-adhering polymer modified bitumen
underlayment complying with ASTM D1970, installed in accor-
dance
with
the
underlayment
and
roof
covering
manufacturer’s installation instructions for the deck material,
roof ventilation configuration and climate exposure of the roof
covering.| |Metal roof
shingles|R905.4|Apply in accordance with the manufacturer’s installation
instructions.|Underlayment shall be one of the following:
1. Two layers of mechanically fastened underlayment applied in
the following manner: Apply a strip of underlayment that is
half the width of a full sheet parallel to and starting at the
eaves, fastened sufficiently to hold in place. Starting at the
eave, apply full width sheets of underlayment, overlapping
successive sheets half the width of a full sheet plus 2 inches.
End laps shall be 4 inches and shall be offset by 6 feet.
2. A minimum 4-inch-wide strip of self-adhering polymer modified
bitumen underlayment complying with ASTM D1970, installed
in accordance with the manufacturer’s installation instructions
for the deck material, shall be applied over all joints in the roof
decking. An approved underlayment complying with Table
R905.1.1(1) for the applicable roof covering shall be applied
over the entire roof over the 4-inch-wide membrane strips.
3.CWUIC § 504.2.1.1 High relevance — show source text
504.2.1.1 Airspace under roof covering. Where the roof covering is installed over a combustible deck and the roofing profile creates an airspace under the roof covering, the installation shall comply with the following: 1. A 72 lb. (32.7 kg) cap sheet complying with ASTM D3909 Standard Specification for “Asphalt Rolled Roofing (Glass Felt) Surfaced with Mineral Granules,” shall be installed over the roof deck.
Exception: Cap sheet is not required where not less than 1 inch of mineral wool board or other noncombustible material is located between the roofing material and wood framing or deck. 2. Bird stops shall be used at the eaves where the profile fits, to prevent the entry of debris at the eave. 3. Hip and ridge caps shall be mudded in to prevent intrusion of fire or embers.
504.2.1.2 Roof underlayment. A listed and labeled roof underlayment that has been tested as part of the roof assembly in accor- dance with ASTM E108 or UL 790 for Class A fire classification shall be installed in accordance with the underlayment manufacturer’s installation instructions and listing. Bird stops shall be used at the eaves when the profile fits, to prevent the entry of debris at the eave. Hip and ridge caps shall be mudded in to prevent intrusion of fire or embers.
Exception: Where the roof sheathing is fire-retardant-treated wood labeled for exterior use and complies with Section 2303.2 of the California Building Code, the underlayment shall not be required to comply with a Class A fire classification.
504.2.2 Roof valleys. Where provided, valley flashings shall be not less than 0.019 inch (0.48 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal installed over a minimum 36-inch-wide (914 mm) underlayment consisting of one layer of 72-pound (32.4 kg) mineral-surfaced, nonperforated cap sheet complying with ASTM D3909 running the full length of the valley.
504.3 Protection of enclosed eaves. The exposed underside of enclosed roof eaves and soffits shall be protected on the exposed underside by one or more of the following:
1. Noncombustible materials.
2. Ignition-resistant building materials. 3. Materials approved for not less than 1-hour fire-resistance-rated construction on the exterior side, as tested in accordance with ASTM E119 or UL 263.
4. 2-inch (51 mm) nominal dimension lumber . 5. 1-inch (25 mm) nominal fire-retardant-treated lumber or [3] / 4 -inch (19.1 mm) nominal fire-retardant-treated plywood, identified for exterior use and complying with Section 2303.2 of the California Building Code . 6. Boxed-in roof eave soffit assemblies with an underside that meets the performance criteria in Section 504.7.2 when tested in accordance with the test procedures set forth in ASTM E2957. 7. Boxed-in roof eave soffit assemblies with an underside that meets the performance criteria in accordance with the test proce- dures set forth in SFM Standard 12-7A-3.
CWUIC § 504.1 High relevance — show source text
� SECTION 504—IGNITION-RESISTANT CONSTRUCTION
504.1 General. Ignition-resistant construction shall be in accordance with Sections 504.2 through 504.11.6 .
5-4 2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
SPECIAL BUILDING CONSTRUCTION REGULATIONS
504.2 Roof assembly. Roofs shall have a roof assembly that complies with a Class A fire classification when tested in accordance with ASTM E108 or UL 790.
Exceptions: The following assemblies are exempt from testing and shall be considered as equivalent to the Class A fire classification:
- Roof assemblies with coverings of brick, masonry or an exposed concrete roof deck.
- Roof assemblies with ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile or slate installed on noncombustible decks or ferrous, copper or metal sheets installed without a roof deck on noncombustible framing.
- Roof assemblies with minimum 16 oz/sq ft (0.0416 kg/m [2] ) copper sheets installed over combustible roof decks. 4. Roof assemblies of slate roof covering installed over ASTM D226, Type II underlayment over combustible decks.
504.2.1 Roof covering voids. Where there is a void under the roof covering it shall comply with Section 504.2.1.1 or 504.2.1.2.
504.2.1.1 Airspace under roof covering. Where the roof covering is installed over a combustible deck and the roofing profile creates an airspace under the roof covering, the installation shall comply with the following: 1. A 72 lb. (32.7 kg) cap sheet complying with ASTM D3909 Standard Specification for “Asphalt Rolled Roofing (Glass Felt) Surfaced with Mineral Granules,” shall be installed over the roof deck.
Exception: Cap sheet is not required where not less than 1 inch of mineral wool board or other noncombustible material is located between the roofing material and wood framing or deck. 2. Bird stops shall be used at the eaves where the profile fits, to prevent the entry of debris at the eave. 3. Hip and ridge caps shall be mudded in to prevent intrusion of fire or embers.
504.2.1.2 Roof underlayment. A listed and labeled roof underlayment that has been tested as part of the roof assembly in accor- dance with ASTM E108 or UL 790 for Class A fire classification shall be installed in accordance with the underlayment manufacturer’s installation instructions and listing. Bird stops shall be used at the eaves when the profile fits, to prevent the entry of debris at the eave. Hip and ridge caps shall be mudded in to prevent intrusion of fire or embers.
Exception: Where the roof sheathing is fire-retardant-treated wood labeled for exterior use and complies with Section 2303.2 of the California Building Code, the underlayment shall not be required to comply with a Class A fire classification.
CWUIC § 0.0134 High relevance — show source text
Mechanically fastened underlayment shall be
fastened using annular ring or deformed shank nails
with 1-inch diameter metal or plastic caps. Metal caps
shall have a thickness of not less than 32-gage (0.0134
inch) sheet metal. Power-driven metal caps shall have a
minimum thickness of 0.010 inch. Minimum thickness of
the outside edge of plastic caps shall be 0.035 inch. The
cap nail shank shall be not less than 0.083 inch. The cap
nail shank shall have a length sufficient to penetrate
through the roof sheathing or not less than3/4 inch into
the roof sheathing.
Self-adhering polymer modified bitumen underlayment
shall be installed in accordance with the underlayment
and roof covering manufacturers’ installation instruc-
tions for the deck material, roof ventilation
configuration and climate exposure of the roof
covering.| |Clay and concrete tile|1507.3|1507.3|1507.3| |BIPV roof coverings|1507.16|1507.16|1507.16| |Metal roof panels|1507.4|Manufacturer’s installation instructions|Mechanically fastened underlayment shall be fastened
with corrosion-resistant fasteners in a grid pattern of not
greater than 12 inches horizontally and vertically between
side laps with a 6-inch spacing at side and end laps.
Mechanically fastened underlayment shall be fastened
using annular ring or deformed shank nails with 1-inch
diameter metal or plastic caps. Metal caps shall have a
thickness of not less than 32-gage sheet metal. Power-
driven metal caps shall have a minimum thickness of
0.010 inch. Minimum thickness of the outside edge of
plastic caps shall be 0.035 inch. The cap nail shank shall
be not less than 0.083 inch. The cap nail shank shall have a
length sufficient to penetrate through the roof sheathing
or not less than3/4 inch into the roof sheathing.
Self-adhering polymer modified bitumen underlayment
shall be installed in accordance with the underlayment
and roof covering manufacturers’ installation instruc-
tions for the deck material, roof ventilation configuration
and climate exposure of the roof covering.| |Metal roof shingles|1507.5|1507.5|1507.5| |Mineral-surfaced roll
roofing|1507.6|1507.6|1507.6| |Slate shingles|1507.7|1507.7|1507.7| |Wood shingles|1507.8|1507.8|1507.8| |Wood shakes|1507.9|1507.9|1507.9| |For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s.|For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s.|For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s.|For SI: 1 inch = 25.4 mm, 1 mile per hour = 0.447 m/s.|CWUIC § 1.1 High relevance — show source text
Distortions
in the underlayment shall not interfere with the ability of the
shingles to seal. End laps shall be 4 inches and shall be offset
by 6 feet.
2. For roof slopes of 4 units vertical in 12 units horizontal (4:12)
or greater, underlayment shall be one layer applied in the
following manner: underlayment shall be applied shingle
fashion, parallel to and starting from the eave and lapped 2
inches. Distortions in the underlayment shall not interfere
with the ability of the shingles to seal. End laps shall be 4
inches and shall be offset by 6 feet.
3. A single layer of self-adhering polymer modified bitumen
underlayment complying with ASTM D1970, installed in
accordance with the underlayment and roof covering manu-
facturer’s installation instructions for the deck material, roof
ventilation configuration and climate exposure of the roof
covering.|Underlayment shall be one of the following:
1. Two layers of mechanically fastened underlayment applied in
the following manner: Apply a strip of underlayment that is
half the width of a full sheet parallel to and starting at the
eaves, fastened sufficiently to hold in place. Starting at the
eave, apply full-width sheets of underlayment, overlapping
successive sheets half the width of a full sheet plus 2 inches.
Distortions in the underlayment shall not interfere with the
ability of the shingles to seal. End laps shall be 4 inches and
shall be offset by 6 feet.
2. A minimum 4-inch-wide strip of self-adhering polymer modi-
fied bitumen underlayment complying with ASTM D1970,
installed in accordance with the manufacturer’s installation
instructions for the deck material, shall be applied over all
joints in the roof decking. An approved underlayment comply-
ing with Table R905.1.1(1) for the applicable roof covering shall
be applied over the entire roof over the 4-inch- wide
membrane strips.
3. A single layer of self-adhering polymer modified bitumen
underlayment complying with ASTM D1970, installed in accor-
dance
with
the
underlayment
and
roof
covering
manufacturer’s installation instructions for the deck material,
roof ventilation configuration and climate exposure of the roof
covering.| |Clay and
concrete tile|R905.3|Underlayment shall be one of the following:
1. For roof slopes from 21/2 units vertical in 12 units horizontal
(21/2:12), up to 4 units vertical in 12 units horizontal (4:12),
underlayment shall be two layers applied in the following
manner: apply a strip of underlayment that is half the width
of a full sheet parallel to and starting at the eaves, fastened
sufficiently to hold in place. Starting at the eave, apply full-
width sheets of underlayment, overlapping successive
sheets half the width of a full sheet plus 2 inches. End laps
shall be 4 inches and shall be offset by 6 feet.
2.CWUIC § 1507.1.1 High relevance — show source text
fastened
sufficiently to hold in place. Starting at the eaves,
apply full-width sheets of underlayment,
overlapping successful sheets half the width of a full
sheet plus 2 inches. Distortions in the underlayment
shall not interfere with the ability of the shingles to
seal. End laps shall be 4 inches and shall be offset by
6 feet.
2.
A strip not less than 4 inches in width of self-
adhering polymer modified bitumen underlayment
complying with ASTM D1970, installed in
accordance with the manufacturer’s installation
instructions for the deck material, shall be applied
over all joints in the roof decking. An approved
underlayment complying with Table 1507.1.1(1) for
the applicable roof covering and basic wind speed
shall be applied over the entire roof over the 4-inch-
wide membrane strips. Underlayment shall be
applied in accordance with this table using the
application requirements for where the maximum
basic wind speed is less than 130 mph.
3.
A single layer of self-adhering polymer modified
bitumen underlayment complying with ASTM
D1970, installed in accordance with the
underlayment and roof covering manufacurers’
installation instructions for the deck material, roof
ventilation configuration, and climate exposure of
the roof covering.| |Metal roof
shingles|1507.5|1507.5|1507.5| |Mineral-
surfaced
roll roofing|1507.6|1507.6|1507.6| |Slate
shingles|1507.7|1507.7|1507.7| |Wood
shingles|1507.8|1507.8|1507.8| |Wood
shakes|1507.9|1507.9|1507.9| |BIPV roof
coverings|1507.16|Underlayment shall be one of the following:
1.
For roof slopes from 3 units vertical in 12 units
horizontal (3:12) to 4 units vertical in 12 units
horizontal (4:12), underlayment shall be two layers
applied in the following manner: Apply a strip of
underlayment that is half the width of a full sheet
parallel to and starting at the eaves. Starting at the
eaves, apply full-width sheets of underlayment,
overlapping successive sheets half the width of a full
sheet plus 2 inches. End laps shall be 4 inches and
shall be offset by 6 feet. Distortions in the
underlayment shall not interfere with the ability of
the shingles to seal.
2.
For roof slopes of 4 units vertical in 12 units
horizontal (4:12) or greater, underlayment shall be
one layer applied as follows: Underlayment shall be
applied shingle fashion, parallel to and starting from
the eaves and lapped 2 inches. Distortions in the
underlayment shall not interfere with the ability of
the shingles to seal.CWUIC § 1507.5 High relevance — show source text
5|1507.5| |Mineral-
surfaced
roll roofing|1507.6|1507.6|1507.6| |Slate
shingles|1507.7|1507.7|1507.7| |Wood
shingles|1507.8|1507.8|1507.8| |Wood
shakes|1507.9|1507.9|1507.9| |BIPV roof
coverings|1507.16|Underlayment shall be one of the following:
1.
For roof slopes from 3 units vertical in 12 units
horizontal (3:12) to 4 units vertical in 12 units
horizontal (4:12), underlayment shall be two layers
applied in the following manner: Apply a strip of
underlayment that is half the width of a full sheet
parallel to and starting at the eaves. Starting at the
eaves, apply full-width sheets of underlayment,
overlapping successive sheets half the width of a full
sheet plus 2 inches. End laps shall be 4 inches and
shall be offset by 6 feet. Distortions in the
underlayment shall not interfere with the ability of
the shingles to seal.
2.
For roof slopes of 4 units vertical in 12 units
horizontal (4:12) or greater, underlayment shall be
one layer applied as follows: Underlayment shall be
applied shingle fashion, parallel to and starting from
the eaves and lapped 2 inches. Distortions in the
underlayment shall not interfere with the ability of
the shingles to seal. End laps shall be 4 inches and
shall be offset by 6 feet.
3.
A single layer of self-adhering polymer modified
bitumen underlayment complying with ASTM
D1970, installed in accordance with the
underlayment and roof covering manufacturers’
installation instructions for the deck material, roof
ventilation configuration, and climate exposure of
the roof covering.|Underlayment shall be one of the following:
1.
Two layers of mechanically fastened underlayment
applied in the following manner: Apply a strip of
underlayment that is half the width of a full sheet
parallel to and starting at the eaves, fastened
sufficiently to hold in place. Starting at the eaves,
apply full-width sheets of underlayment,
overlapping successive sheets half the width of a full
sheet plus 2 inches. Distortions in the underlayment
shall not interfere with the ability of the shingles to
seal. End laps shall be 4 inches and shall be offset by
6 feet.
2.
A strip not less than 4 inches in width of self-
adhering polymer modified bitumen underlayment
complying with ASTM D1970, installed in
accordance with the manufacturer’s installation
instructions for the deck material, shall be applied
over all joints in the roof decking. An approved
underlayment complying with Table 1507.1.1(1) for
the applicable roof covering and basic wind speed
shall be applied over the entire roof over the 4-inch-
wide membrane strips.CWUIC § 0.447 High relevance — show source text
447 m/s.|For SI: 1 mile per hour = 0.447 m/s.|For SI: 1 mile per hour = 0.447 m/s.|For SI: 1 mile per hour = 0.447 m/s.|
2025 CALIFORNIA RESIDENTIAL CODE 9-5
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ROOF ASSEMBLIES
TABLE R905.1.1(2)—UNDERLAYMENT APPLICATION Col2 Col3 Col4 ROOF
COVERINGSECTION AREAS WHERE WIND DESIGN IS NOT REQUIRED IN
ACCORDANCE WITH FIGURE R301.2.1.1AREAS WHERE WIND DESIGN IS REQUIRED IN
ACCORDANCE WITH FIGURE R301.2.1.1Asphalt
shinglesR905.2 Underlayment shall be one of the following:
1. For roof slopes from 2 units vertical in 12 units horizontal
(2:12), up to 4 units vertical in 12 units horizontal (4:12),
underlayment shall be two layers applied in the following
manner: apply a strip of underlayment that is half the width
of a full sheet parallel to and starting at the eaves, fastened
sufficiently to hold in place. Starting at the eave, apply full-
width sheets of underlayment, overlapping successive
sheets half the width of a full sheet plus 2 inches. Distortions
in the underlayment shall not interfere with the ability of the
shingles to seal. End laps shall be 4 inches and shall be offset
by 6 feet.
2. For roof slopes of 4 units vertical in 12 units horizontal (4:12)
or greater, underlayment shall be one layer applied in the
following manner: underlayment shall be applied shingle
fashion, parallel to and starting from the eave and lapped 2
inches. Distortions in the underlayment shall not interfere
with the ability of the shingles to seal. End laps shall be 4
inches and shall be offset by 6 feet.
3. A single layer of self-adhering polymer modified bitumen
underlayment complying with ASTM D1970, installed in
accordance with the underlayment and roof covering manu-
facturer’s installation instructions for the deck material, roof
ventilation configuration and climate exposure of the roof
covering.Underlayment shall be one of the following:
1. Two layers of mechanically fastened underlayment applied in
the following manner: Apply a strip of underlayment that is
half the width of a full sheet parallel to and starting at the
eaves, fastened sufficiently to hold in place. Starting at the
eave, apply full-width sheets of underlayment, overlapping
successive sheets half the width of a full sheet plus 2 inches.
Distortions in the underlayment shall not interfere with the
ability of the shingles to seal. End laps shall be 4 inches and
shall be offset by 6 feet.
2.CWUIC § 15-7 High relevance — show source text
2025 CALIFORNIA BUILDING CODE 15-7
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
TABLE 1507.1.1(2)—UNDERLAYMENT APPLICATION Col2 Col3 Col4 ROOF
COVERINGSECTION MAXIMUM BASIC WIND SPEED,****V < 130 MPH IN
HURRICANE-PRONE REGIONS ORV < 140 MPH
OUTSIDE HURRICANE-PRONE REGIONSMAXIMUM BASIC WIND SPEED,****V ≥ 130 MPH IN
HURRICANE-PRONE REGIONS ORV ≥ 140 MPH
OUTSIDE HURRICANE-PRONE REGIONSAsphalt
shingles1507.2 Underlayment shall be one of the following:
1.
For roof slopes from 2 units vertical in 12 units
horizontal (2:12) to 4 units vertical in 12 units
horizontal (4:12), underlayment shall be two layers
applied in the following manner: Apply a strip of
underlayment that is half the width of a full sheet
parallel to and starting at the eaves. Starting at the
eaves, apply full-width sheets of underlayment,
overlapping successive sheets half the width of a full
sheet plus 2 inches. End laps shall be 4 inches and
shall be offset by 6 feet. Distortions in the
underlayment shall not interfere with the ability of
the shingles to seal.
2.
For roof slopes of 4 units vertical in 12 units
horizontal (4:12) or greater, underlayment shall be
one layer applied as follows: Underlayment shall be
applied shingle fashion, parallel to and starting from
the eaves and lapped 2 inches. Distortions in the
underlayment shall not interfere with the ability of
the shingles to seal. End laps shall be 4 inches and
shall be offset by 6 feet.
3.
A single layer of self-adhering polymer modified
bitumen underlayment complying with ASTM
D1970, installed in accordance with the
underlayment and roof covering manufacturers’
installation instructions for the deck material, roof
ventilation configuration, and climate exposure of
the roof covering.Underlayment shall be one of the following:
1.
Two layers of mechanically fastened underlayment
applied in the following manner: Apply a strip of
underlayment felt that is half the width of a full
sheet parallel to and starting at the eaves, fastened
sufficiently to hold in place. Starting at the eaves,
apply full-width sheets of underlayment overlapping
successive sheets half the width of a full sheet plus 2
inches. Distortions in the underlayment shall not
interfere with the ability of the shingles to seal.CWUIC § 4.1 High relevance — show source text
For roof slopes of 3 units vertical in 12 units horizontal (25-percent slope) and greater, valley flashing shall have a 36-inch-wide (914 mm) underlayment of one layer of Type I underlayment running the full length of the valley, in addition to other required underlayment. In areas where the average daily temperature in January is 25°F (-4°C) or less, metal valley flashing underlayment shall be solid-cemented to the roofing underlayment for slopes less than 7 units vertical in 12 units horizontal (58-percent slope) or be of self-adhering polymer-modified bitumen sheet.
R905.4 Metal roof shingles. The installation of metal roof shingles shall comply with the provisions of this section.
R905.4.1 Sheathing requirements. Metal roof shingles shall be fastened to wood structural panels, solid lumber sheathing or closely fitted lumber sheathing, except where the roof covering is specifically designed to be applied to spaced lumber sheathing.
R905.4.2 Slope. Metal roof shingles shall not be installed on roof slopes below 3 units vertical in 12 units horizontal (25-percent slope).
R905.4.3 Underlayment. Underlayment shall comply with Section R905.1.1.
R905.4.3.1 Ice barrier. Where required, ice barriers shall comply with Section R905.1.2.
R905.4.4 Material standards. Metal roof shingle roof coverings shall comply with Table R905.10.3(1). The materials used for metal roof shingle roof coverings shall be naturally corrosion resistant or be made corrosion resistant in accordance with the standards and minimum thicknesses listed in Table R905.10.3(2).
R905.4.4.1 Wind resistance of metal roof shingles. Metal roof shingles fastened to wood structural panels, solid lumber sheathing or closely fitted lumber sheathing shall be tested in accordance with ASTM D3161, FM 4474, UL 580 or UL 1897. Metal roof shingles tested in accordance with ASTM D3161 shall meet the classification requirements of Table R905.4.4.1 for the appropriate maximum basic wind speed and the metal shingle packaging shall bear a label to indicate compliance with ASTM D3161 and the required classification in Table R905.2.4.1.
9-10 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ROOF ASSEMBLIES
CWUIC § 1507.1.1 High relevance — show source text
End laps shall be 4 inches and
shall be offset by 6 feet.
3.
A single layer of self-adhering polymer modified
bitumen underlayment complying with ASTM
D1970, installed in accordance with the
underlayment and roof covering manufacturers’
installation instructions for the deck material, roof
ventilation configuration, and climate exposure of
the roof covering.|Underlayment shall be one of the following:
1.
Two layers of mechanically fastened underlayment
applied in the following manner: Apply a strip of
underlayment that is half the width of a full sheet
parallel to and starting at the eaves, fastened
sufficiently to hold in place. Starting at the eaves,
apply full-width sheets of underlayment,
overlapping successive sheets half the width of a full
sheet plus 2 inches. Distortions in the underlayment
shall not interfere with the ability of the shingles to
seal. End laps shall be 4 inches and shall be offset by
6 feet.
2.
A strip not less than 4 inches in width of self-
adhering polymer modified bitumen underlayment
complying with ASTM D1970, installed in
accordance with the manufacturer’s installation
instructions for the deck material, shall be applied
over all joints in the roof decking. An approved
underlayment complying with Table 1507.1.1(1) for
the applicable roof covering and basic wind speed
shall be applied over the entire roof over the 4-inch-
wide membrane strips. Underlayment shall be
applied in accordance with this table using the
application requirements for where the maximum
basic wind speed is less than 130 mph.
3.
A single layer of self-adhering polymer modified
bitumen underlayment complying with ASTM
D1970, installed in accordance with the
underlayment and roof covering manufacturers’
installation instructions for the deck material, roof
ventilation configuration, and climate exposure of
the roof covering.| |For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.|2025 CALIFORNIA BUILDING CODE 15-9
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
CWUIC § 1507.1.1 High relevance — show source text
End laps shall be 4
inches and shall be offset by 6 feet.
3.
A single layer of self-adhering polymer modified
bitumen underlayment complying with ASTM
D1970, installed in accordance with the
underlayment and roof covering manufacturers’
installation instructions for the deck material, roof
ventilation configuration, and climate exposure of
the roof covering.|Underlayment shall be one of the following:
1.
Two layers of mechanically fastened underlayment
applied in the following manner: Apply a strip of
underlayment that is half the width of a full sheet
parallel to and starting at the eaves, fastened
sufficiently to hold in place. Starting at the eaves,
apply full-width sheets of underlayment,
overlapping successive sheets half the width of a full
sheet plus 2 inches. Distortions in the underlayment
shall not interfere with the ability of the shingles to
seal. End laps shall be 4 inches and shall be offset by
6 feet.
2.
A strip not less than 4 inches in width of self-
adhering polymer modified bitumen underlayment
complying with ASTM D1970, installed in
accordance with the manufacturer’s installation
instructions for the deck material, shall be applied
over all joints in the roof decking. An approved
underlayment complying with Table 1507.1.1(1) for
the applicable roof covering and basic wind speed
shall be applied over the entire roof over the 4-inch-
wide membrane strips. Underlayment shall be
applied in accordance with this table using the
application requirements for where the maximum
basic wind speed is less than 130 mph.
3.
A single layer of self-adhering polymer modified
bitumen underlayment complying with ASTM
D1970, installed in accordance with the
underlayment and roof covering manufacurers’
installation instructions for the deck material, roof
ventilation configuration, and climate exposure of
the roof covering.|15-8 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
TABLE 1507.1.1(2)—UNDERLAYMENT APPLICATION—continued Col2 Col3 Col4 ROOF
COVERINGSECTION MAXIMUM BASIC WIND SPEED,****V < 130 MPH IN
HURRICANE-PRONE REGIONS ORV < 140 MPH
OUTSIDE HURRICANE-PRONE REGIONSMAXIMUM BASIC WIND SPEED,****V ≥ 130 MPH IN
HURRICANE-PRONE REGIONS ORV ≥ 140 MPH
OUTSIDE HURRICANE-PRONE REGIONSMetal roof
panels1507.4 Apply in accordance with the manufacturer’s installa-
tion instructionsUnderlayment shall be one of the following:
1.
Frequently asked questions
What exactly is considered a "void" or "airspace" under § 504.2.1?
A "void" or "airspace" is created when the roof covering/profile does not sit directly on the combustible deck (i.e., a gap exists under the covering). The CWUIC triggers the protective measures when such a void exists but does not prescribe a numeric clearance dimension in the cited sections.
Can I use self‑adhering underlayment instead of the 72 lb. cap sheet?
Yes — but only if the underlayment is listed and labeled and tested as part of the roof assembly to ASTM E108 or UL 790 for Class A assembly performance, and it is installed per its listing and manufacturer instructions (see § 504.2.1.2).
When is the 1‑inch mineral wool board option acceptable?
The 1‑inch mineral wool board (or other noncombustible material) may replace the 72 lb. cap sheet where at least 1 inch of that material is located between the roofing material and wood framing or deck (see § 504.2.1.1 Exception).
Do bird stops and mudded hip/ridge caps apply even when I use a Class A underlayment?
Yes — both § 504.2.1.1 and § 504.2.1.2 require bird stops at eaves (where the profile fits) and mudding at hip/ridge caps to prevent ember/debris intrusion.
If my sheathing is fire‑retardant‑treated wood, do I still need a Class A underlayment?
If the sheathing is FRT wood labeled for exterior use and complies with CBC § 2303.2, the underlayment is not required to be Class A under § 504.2.1.2 (Exception) — but you must verify the sheathing’s labeling and compliance.
More in California Wildland-Urban Interface Code
- Administration and Definitions
- Board of Appeals, Administration & Enforcement (permits, code official duties, appeals process)
- Wildland‑Urban Interface Area Designation & Mapping
- Fire Service Access & Water Supply (fire apparatus roads, driveways, hydrants, draft sites, standby power)
- Wildland‑Urban Interface Area Requirements (access, water, premises identification, key boxes)
- Referenced Standards & Test Methods
- Special Building Construction Regulations (ignition‑resistant construction, roof/vent/assembly requirements)
- Appendices and Model Ordinances (vegetation plans, severity‑zone adoption, home‑hardening guidance)
- Fire Protection Requirements (fire protection plans, systems, safety element provisions)
- Referenced California Documents & Matrix (CCR/Title 14 & 19 cross‑references, statutory references)
- Vegetation Management & Defensible Space (vegetation plans, maintenance, fire‑smart characteristics)
Ask about the CWUIC
Get cited, plain-English answers on the California Wildland-Urban Interface Code for your project — any code section, any scenario.
Start Free Trial