CRSC · California Referenced Standards Code

What must be included in laboratory test reports for control units?

For homeowners: the lab report for any alarm control unit must show the engineering, wiring, manuals, photos and the tests done to prove the unit meets California rules — including listing details for any listed parts and proof the unit’s electrical rating is correct, per § 12-72-101.

Last reviewed: July 6, 2026

What the code requires — 2-4 sentences

The laboratory test report for a control unit must include engineering data, an analysis comparing the design to § 12-72-102 (a) through (u), wiring diagrams, operating manuals, photographs, a clear statement of the tests performed and the results (performed per § 12-72-103 (a) through (g)), and verification of the electrical rating required by § 12-72-107. This set of required contents is specified in § 12-72-101 (a) of the California Referenced Standards Code.

The single most important rule: the report must demonstrate—by engineering data, test results and documentation—that the control unit’s design and electrical rating meet the CRSC performance and construction requirements in the referenced sections. § 12-72-101 (a).


Requirements in detail

Below are the decision-relevant report elements the CRSC requires, with the controlling code references and short notes on what to include for each.

Key elements (summary table)

Item Required content (what to include) Decision‑relevant values / examples Code Reference
Engineering data Analysis, drawings, calculations, component lists used to support design Material specs; component ratings; rationale showing compliance with performance clauses § 12-72-101 (a)
Design comparison Point‑by‑point analysis vs. § 12-72-102 (a)–(u) Show where the design meets each item (or explain deviation + equivalency) § 12-72-101 (a) referencing § 12-72-102 (a)–(u)
Wiring diagrams Complete installation and internal wiring diagrams called out in test procedures Installation wiring that forms the system combination used during testing § 12-72-101 (a); see § 12-72-102 (a) Items 5 & 6
Operating & installation manuals Draft or final instructions used during testing and intended for the installer/owner Include any special instructions, limitations, or required equipment § 12-72-101 (a); § 12-72-102 (a) Items 5 & 6
Photographs Photos of the sample(s) as tested and key details (internal construction, nameplates, connections) Show actual tested configuration, serial/model markings § 12-72-101 (a)
Tests performed & results List tests executed per § 12-72-103 (a)–(g) and full results/data Include test conditions (voltage, frequency), pass/fail data, graphs, instrumentation used § 12-72-101 (a); tests defined by § 12-72-103 (a)–(g)
Electrical rating verification Statement and supporting data verifying the unit’s rated voltage/current/power per § 12-72-107 Example: show rated voltage and measured behavior at rated frequency/voltage § 12-72-101 (a); verify per § 12-72-107
Listed component documentation For any listed parts, include catalog number, listing agency name, laboratory test report number and date Identifiers must be clear and match catalog/markings on the part § 12-72-101 (b)
Combination suitability testing When listed components are used in combination, include performance tests showing suitability in the assembled control unit Demonstrate components operate correctly in the final assembly § 12-72-101 (b)

Notes on "engineering data" and the design comparison

  • The code expects an engineering-level analysis demonstrating conformance to each applicable design and construction requirement in § 12-72-102 (a)–(u) — do not submit only a checklist; provide evidence and rationale for each referenced item. § 12-72-101 (a).
  • Where departures exist, document how the alternate construction is equivalent or why additional tests were sufficient to establish compliance. § 12-72-101 (f) addresses differing constructions and consultation with the State Fire Marshal.

Exceptions & special cases

  • Listed parts already tested/listed by an approved listing agency need not be retested individually, but the test report must include the catalog number, listing agency, and the laboratory test report number and date; and the assembled combination still must be performance‑tested to demonstrate suitability in the control unit. § 12-72-101 (b).
  • Control units designed to fully comply with the NFPA/UL listing program may be investigated and tested in accordance with U.L. 864, provided the investigation and report incorporate the provisions of the California Electrical Code as required by § 12-72-101 (c).
  • Compliance with the listed test standards does not guarantee approval; the State Fire Marshal may require additional tests or refuse approval for cause (unusual constructions or features that impair intent). § 12-72-101 (d), (f).
  • The standard applies to protective signaling systems as defined in the California Electrical Code; it does not cover manual stations, automatic detectors, or separately listed bells that are not part of the control unit. § 12-72-101 (e).

Common mistakes

  • Omitting the required listed‑component identifiers (catalog number, listing agency name, lab report number/date) — explicitly required by § 12-72-101 (b).
  • Submitting only a checklist or statement of compliance without engineering data and a point‑by‑point comparison to § 12-72-102 (a)–(u) as required by § 12-72-101 (a).
  • Forgetting to include wiring and installation diagrams or photographs that document the as‑tested configuration (these are specifically required by § 12-72-101 (a) and referenced items in § 12-72-102).
  • Assuming that because subcomponents are listed they require no testing in the assembled unit — listed components still must be subjected to the performance standard tests in combination with the unit (see § 12-72-101 (b)).
  • Not verifying or reporting the electrical rating (voltage/classification) per § 12-72-107 — the report must verify the correctness of the electrical rating. § 12-72-101 (a).

Worked example — concrete scenario applying the rule

Scenario: Manufacturer submits a laboratory report for Control Unit Model CU‑500 intended for indoor proprietary signaling use and marked "110–125 V".

What the report should contain (illustrative entries tied to the code):

  • Cover / ID

    • Laboratory name, lab report number and date, sample ID (CU‑500), manufacturer. (General good practice; cover information supports traceability required in reports — see overall test report expectations in § 12-72-101 (a)).
  • Engineering data and design comparison

    • A table that lists each item in § 12-72-102 (a)–(u) and a short explanation with cross‑references to drawings or calculation pages showing compliance. (Required per § 12-72-101 (a).)
  • Wiring diagrams, manuals, photographs

    • Include the installation wiring diagram used for testing, the draft installation/operation manual, and photographs of the assembled CU‑500 showing the nameplate and internal layout. (Required by § 12-72-101 (a) and § 12-72-102 references.)
  • Tests performed and results

    • State: “Tests run per § 12-72-103 (a)–(g) (normal operation, endurance, electrical supervision, jarring, temperature, etc.).” Provide test conditions and results.
    • Example supported numeric item: For test voltage, the laboratory reports that the unit was tested at 120 volts (the field for units marked 110–125 V is considered 120 V for test purposes per § 12-72-103 (a) Item 4) and at rated frequency; include instrumentation and measured values.
  • Electrical rating verification

    • Report includes measurements demonstrating the unit operates correctly at the tested 120 V and that nameplate ratings correspond to measured performance). This verifies the correctness of the electrical rating per § 12-72-101 (a) and § 12-72-107.
  • Listed components documentation

    • If CU‑500 uses a listed transformer and listed relay modules, include for each: catalog number, listing agency name, and the lab test report number and date for that component. State that the assembled CU‑500 then underwent combination performance tests to verify suitability as required by § 12-72-101 (b).

Important caveat: the CRSC text provided requires these items but does not specify a mandated sample size or a single required format for the report cover pages. If you need a specific laboratory report template or required sample counts for control units, that requirement is not specified in § 12-72-101 in the retrieved text; lab practice should follow the laboratory’s reporting standards and any additional requirements from the State Fire Marshal.


Related provisions

  • § 12-72-102 — Investigation—Report and items to be compared (design requirements, items (a)–(u)).
  • § 12-72-103 — Performance test headings and test conditions (tests to be performed).
  • § 12-72-107 — Electrical rating verification referenced by test reports.
  • § 12-72-101 (b) — Listed devices: required documentation for listed components in the test report.
  • § 12-72-101 (c) — Use of U.L. 864 procedures where applicable, with incorporation of the California Electrical Code.
  • § 12-72-101 (d), (f) — Rejection for cause and differing constructions (State Fire Marshal authority and equivalency).

Code references

Grounded in the retrieved California Referenced Standards Code — click a citation to read the verbatim passage:

  • CRSC § 12-72 High relevance — show source text

    purposes.

    (c) Control unit. A control unit covered by this standard consists of a unit assembly of electrical parts having provisions for the connection of power-supply circuits routed through the control unit equipment by a prescribed scheme of circuitry; signal initiating circuits extended to separate devices by which the operating parts of the control unit are actuated for signals, and to incorporated or separate devices by which the signals are transmitted or indicated to form a coordinated combination system for definite signaling service.

    TEST REPORTS

    Sec. 12-72-101.

    (a) Test report contents. The report shall include engineering data, and an analysis comparing the design against Section 12-72102 (a) through (u); it shall include wiring, diagrams, operating manuals and photographs as set forth in Section 12-72-102 (a), Items 5 and 6; it shall set forth the tests performed in accordance with Sections 12-72-103 (a) through (g) and the results thereof; and shall verify the correctness of the electrical rating required by Section 12-72-107.

    (b) Listed devices. Electrical wiring, material, devices, combination of devices, fittings, appliances and equipment which have been tested and listed by an approved listing agency for the intended purpose and use need not be individually retested.

    The report shall include the catalog number or other readily identifiable marking, the name of the approved listing agency, the laboratory test report number and date. Such individually tested and listed component parts and devices when installed in combination with other devices in a control unit or in a circuit extended from such control unit shall be subjected to the performance standard tests to determine its suitability for use in combination with other component parts, devices, circuits or equipment.

    (c) Listed control units. Control units which by their design are intended to fully comply with the Standard for the Installation, Maintenance and Use of Proprietary, Auxiliary, Remote Station and Local Protective Association may be investigated and tested in accordance with the Standards for Safety established by Underwriters’ Laboratories, Inc., U.L. 864, provided such investigation, test and report incorporates the provisions of the California Electrical Code.

    (d) Rejection for cause. Compliance with these standards will not necessarily mean approval and listing, if, when examined and tested, it is found to have other features which may impair the result intended by these regulations. Unusual constructions may require application of additional performance tests. The State Fire Marshal may refuse to approve any item for cause.

    (e) Systems only. The standard applies to protective signaling systems as defined in the California Electrical Code, and systems or systems components for which application for approval and listing has been filed under the provisions of the California Electrical Code.

    This standard does not cover manual stations, automatic detectors, automatic transmitters or other actuating devices; nor does it cover separately listed bells, registers or other indicating devices which are not provided as a part of the control unit or matched against the output of sound-reproducing equipment.

    (f) Differing constructions. A control unit having materials or forms of construction differing from this standard may be investigated and tested according to the intent of this standard, and if found to be substantially equivalent may be given recognition for approval and listing. The office of the State Fire Marshal shall be consulted for general requirements and performance standards.

    2025 CALIFORNIA REFERENCED STANDARDS CODE 109

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    PROTECTIVE SIGNALING SYSTEMS

    GENERAL

    Sec. 12-72-102.

    (a) **Investigation—Report.

  • CRSC § 12-72 High relevance — show source text

    2025 CALIFORNIA REFERENCED STANDARDS CODE 107

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    108 2025 CALIFORNIA REFERENCED STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    12-72-1 PROTECTIVE SIGNALING SYSTEMS

    STANDARD TEST PROCEDURES

    STANDARD 12-72-1

    STATE FIRE MARSHAL

    SCOPE

    Sec. 12-72-100.

    (a) Basic. This standard represents the minimum basic requirements for the construction and performance of the protective signaling systems to be listed under this classification. The minimum design, construction and performance standards set forth herein are those deemed as minimum necessary to establish conformance to the regulations of the State Fire Marshal as set forth in the California Electrical Code, and when applicable shall be reported on in their entirety by the approved testing laboratory.

    (b) Systems. This standard covers electrically operated devices and control units designed to transmit and sound alarms, supervisory and trouble signals to be employed in ordinary indoor locations in accordance with the Standards of the National Fire Protection Association for the Installation, Maintenance and Use of Proprietary, Auxiliary and Local Protective Signaling Systems, Remote Station, Nos. 72A, 72B, 72C and 72D, and the California Electrical Code. This includes combination protective signaling systems employing nonsupervised sounding circuits; combination fire alarm-communication, -program and -clock systems (hereinafter referred to as combination signaling systems); and audible devices used for both alarm and program or communication

    purposes.

    (c) Control unit. A control unit covered by this standard consists of a unit assembly of electrical parts having provisions for the connection of power-supply circuits routed through the control unit equipment by a prescribed scheme of circuitry; signal initiating circuits extended to separate devices by which the operating parts of the control unit are actuated for signals, and to incorporated or separate devices by which the signals are transmitted or indicated to form a coordinated combination system for definite signaling service.

    TEST REPORTS

    Sec. 12-72-101.

    (a) Test report contents. The report shall include engineering data, and an analysis comparing the design against Section 12-72102 (a) through (u); it shall include wiring, diagrams, operating manuals and photographs as set forth in Section 12-72-102 (a), Items 5 and 6; it shall set forth the tests performed in accordance with Sections 12-72-103 (a) through (g) and the results thereof; and shall verify the correctness of the electrical rating required by Section 12-72-107.

    (b) Listed devices. Electrical wiring, material, devices, combination of devices, fittings, appliances and equipment which have been tested and listed by an approved listing agency for the intended purpose and use need not be individually retested.

    The report shall include the catalog number or other readily identifiable marking, the name of the approved listing agency, the laboratory test report number and date. Such individually tested and listed component parts and devices when installed in combination with other devices in a control unit or in a circuit extended from such control unit shall be subjected to the performance standard tests to determine its suitability for use in combination with other component parts, devices, circuits or equipment.

  • CRSC § 0.5 High relevance — show source text

    is referenced, a copy of the specification is to be provided for review. A failure rate of 0.5 failure per million hours for nonsupervised components would be acceptable. 4. The data required in the preceding paragraph shall include the following: A. Component fault analysis. Effect of failure, open and short, particularly of capacitors, on operation of a detector. B. A description of any component screening and burn-in test, if available. C. Amount of derating of components under normal standby and alarm conditions. A derating of 50 percent or more is acceptable for all components except for electrolytic capacitors. See also Table 12-72-3F. D. Component failure rate data at rated values and derated values. This may be in the form of a reference to a MilSpec. handbook or equivalent. E. Maximum ratings for components. F. Any other data, not included above, which will provide an equivalent reliability analysis.

    DETECTOR RATED VOLTAGE, NAMEPLATE TEST VOLTAGE
    110 to 120 120
    220 to 240 240
    Other Marked Rating
    1. Unless specifically specified otherwise, the test voltage for each test of a detector shall be as follows at rated frequency:
    2. The following samples are used to perform the tests of this standard: A. At least 20 assembled detectors fully representative of production units. B. One additional unassembled detector fully representative of production units. C. Five additional samples of detectors employing a radioactive source. These may be partial assemblies illustrating the radioactive source installation.

    D. Three control units and/or power supplies if the detectors are intended specifically to be employed with a specific unit or power supply. E. The monitoring instrument or reference to a commonly available meter intended to monitor sensitivity of a detector.

    (b) Normal operation.

    1. A detector shall be capable of operating for all conditions of its intended performance at all sensitivity settings when employed in conjunction with any related power supply or control unit with which it is intended to be employed and indicating devices to form the system combination covered by the installation wiring diagram and any supplementary information provided.

    2. The test voltage shall be in accordance with Section 12-72-303 (a), Item 5, and the combustion products detector shall be in the normal circuit supervisory standby condition and prepared for normal signaling operation when it is connected to related devices and circuits.

    3. The introduction of combustion products into the detector chamber such as produced by a smoldering cotton lamp wick, rope or equivalent, shall result in the operation of the detector in its intended manner. Section 12-72-303 (p), Item 2.

    (c) Power input and output. The input or output current of each circuit of a combustion products detector shall not exceed the marked rating by more than 10 percent when the detector is operated under the conditions of normal use and with the detector connected to a source of supply in accordance with Section 12-72-303 (a), Item 5.

    (d) Electrical supervision.

    1. All nonreliable components such as electronic tube heaters, blower motors, capacitors, functional heating elements, etc., the failure of which may result in an open or shorted condition shall be electrically supervised. See Sections 12-72-302 (e); 12-72-303 (a), Item 3; 12-72-303 (e) and 12-72-303 (s).
  • CRSC § 12-72 High relevance — show source text

    PROTECTIVE SIGNALING SYSTEMS

    TABLE 12-72-1D—ENDURANCE TEST Col2 Col3
    NORMAL SIGNALING PERFORMANCE OF DEVICE TOTAL NUMBER OF
    CYCLES DEVICE TO BE
    TESTED
    CYCLES PER
    MINUTE
    Continuous noncode signal for each operation of alarm signal initiating device 6,000 6
    A number of coded or noncode impulses for each operation of alarm signal initiating device 40,000 60
    Preliminary coded or noncode signal impulses followed by continuous signal impulses after
    each operation of alarm signal initiating device
    40,000
    resetting of device after
    each group of 40 impulses

    60
    Relays 40,000 60

    122 2025 CALIFORNIA REFERENCED STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    12-72-2 PROTECTIVE SIGNALING SYSTEMS

    SINGLE- AND MULTIPLE-STATION FIRE ALARM DEVICES MECHANICALLY OPERATED TYPE

    STANDARD 12-72-2

    STATE FIRE MARSHAL

    SCOPE

    Sec. 12-72-200.

    (a) Basic. This standard represents the minimum basic requirements for the construction and performance of single- and multiple-station fire alarm devices intended for indoor installation, and to be listed under this classification. The minimum design, construction and performance standards set forth herein are those deemed as minimum necessary to establish conformance to the regulations of the State Fire Marshal.

    (b) Definitions. For the purpose of this standard, the following definitions shall apply:

    1. Fire alarm device, multiple station. Two or more gas-operated single station units interconnected by metal tubing to one or more remote alarm-sounding devices.

    2. Fire alarm device, single station. A self-contained fire alarm system comprising a heat detector, an alarm- sounding device and a stored energy source incorporated in one integral package. The basic types are gas- operated units and springwound units.

    3. Gas-operated type. A device having a temperature-sensitive eutectic element; compressed gas, usually in a liquid state in a cylinder; and a sounding means, such as a horn or whistle. When the eutectic element melts, the compressed gas is released in a gaseous state through the alarm-sounding device.

    4. Spring-wound type. A device having a temperature-sensitive bimetal or eutectic element and a spring-wound type mechanism with clapper mounted within a bell housing. The snap action of the bimetal or melting of the eutectic element releases the spring mechanism resulting in a bell-type sound.

    TEST REPORTS

    Sec. 12-72-201.

    (a) Test Report contents. The report shall include engineering data, and an analysis comparing the design against Sections 1272-201(b) through 12-72-202(g); it shall include operating manuals and photographs. The report shall set forth the tests performed in accordance with this standard and the results thereof.

    (b) Instructions and drawings. A copy of the operating and installation instructions and any related drawings is to be furnished with the sample submitted for investigation to be used as a guide in the examination and test of the unit and for this purpose they need not be in final printed form.

  • CRSC § 12-72 High relevance — show source text

    (b) Definitions. For the purpose of this standard, the following definitions shall apply:

    1. Fire alarm device, multiple station. Two or more gas-operated single station units interconnected by metal tubing to one or more remote alarm-sounding devices.

    2. Fire alarm device, single station. A self-contained fire alarm system comprising a heat detector, an alarm- sounding device and a stored energy source incorporated in one integral package. The basic types are gas- operated units and springwound units.

    3. Gas-operated type. A device having a temperature-sensitive eutectic element; compressed gas, usually in a liquid state in a cylinder; and a sounding means, such as a horn or whistle. When the eutectic element melts, the compressed gas is released in a gaseous state through the alarm-sounding device.

    4. Spring-wound type. A device having a temperature-sensitive bimetal or eutectic element and a spring-wound type mechanism with clapper mounted within a bell housing. The snap action of the bimetal or melting of the eutectic element releases the spring mechanism resulting in a bell-type sound.

    TEST REPORTS

    Sec. 12-72-201.

    (a) Test Report contents. The report shall include engineering data, and an analysis comparing the design against Sections 1272-201(b) through 12-72-202(g); it shall include operating manuals and photographs. The report shall set forth the tests performed in accordance with this standard and the results thereof.

    (b) Instructions and drawings. A copy of the operating and installation instructions and any related drawings is to be furnished with the sample submitted for investigation to be used as a guide in the examination and test of the unit and for this purpose they need not be in final printed form.

    The instructions and drawings shall include such directions and information as deemed by the manufacturer to be adequate for attaining proper and safe installation, operation and maintenance.

    (c) Rejection for cause. Compliance with these standards will not necessarily mean approval and listing, if, when examined and tested, it is found to have other features which may impair the result intended by these regulations. Unusual constructions may require application of additional performance tests. The State Fire Marshal may refuse to approve any item for cause. (See the Cali- fornia Electrical Code. )

    (d) Devices covered. This standard does not cover electrically operated single- or multiple-station fire alarm devices actuated by heat, smoke or combustion products.

    (e) Temperature classification. The temperature sensitive elements of single- and multiple-station fire alarm devices are to be identified as to their temperature of operation as follows:

    TEMPERATURE CLASSIFICATION RATING RANGE,
    °F (°C)
    MAXIMUM CEILING TEMPERATURE,
    °F (°C)
    Ordinary 135-174 (57-79) 100 (38)
    Intermediate 175-225 (79-107) 150 (66)

    The maximum rating of a fire alarm device is to be not more than 225°F (107°C).

    (f) Differing constructions. A control unit having materials or forms of construction differing from this standard may be investigated and tested according to the intent of this standard, and if found to be substantially equivalent may be given recognition for approval and listing. The office of the State Fire Marshal shall be consulted for general requirements and performance standards.

    2025 CALIFORNIA REFERENCED STANDARDS CODE 123

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

  • California Referenced Standards Code High relevance — show source text

    F. Customers must keep a full set of replacement fuses (PG&E must approve the size and type) onsite.

    G. Solid Blade cutouts are not fuses and therefore not acceptable as a fault−interrupting device.

    1. Replacement or Failure of Protective Equipment

    When the customer’s primary protection device malfunctions or fails to detect abnormal service conditions and trouble related to a PS customer’s equipment and the isolation of the condition and/or equipment within a reasonable time then PG&E may require the equipment to be replaced. Also, when protective equipment is repaired or replaced the equipment must meet all of the qualification and testing requirements in this document including passing inspection by PG&E personnel. If new equipment is installed it must be currently listed as PG&E approved.

    Section 9 Equipment Test Requirements

    The tests in this section apply only to the PG&E−required equipment at the POS; specifically, the breaker, the relays, and the tripping circuitry.

    The customer must complete the following requirements:

    � The equipment must pass all the tests described below.

    � The customer must submit two copies of the test reports to PG&E a minimum of 30 working days before energizing the PS facilities.

    � Each test report must identify the equipment tested and that identification must match that in the single−line or three−line diagrams.

    The customer must meet the above requirements and obtain PG&E approval of the test reports at least ten working days before PG&E energizes the PS. PG&E strongly recommends that the PS customer coordinate the test program with PG&E.

    1. Circuit Breaker Tests

    The PS customer must perform the following circuit breaker tests:

    A. Minimum−to−trip test at 70% or less of the nominal control voltage on all circuit breakers operated by PG&E−required relays.

    B. Micro−ohm test on the main circuit breaker(s) at the POS.

    C. Timing test showing the time from the trip initiation to the opening of the main poles. Proving insulation tests, as described below.

    D. Proving Insulation

    (1) Megger circuit breaker(s) at the POS operated by PG&E require relays (see Table 2 below).

    094676 Page 6 of 16 Rev. #00: 3/25/2022

    OH: Services UG: Services Primary Electric Service Requirements Greenbook

    Table 2 Circuit Breaker Positions and Connections

    Circuit Breaker Position Connection
    Circuit breaker open. Each pole to ground, pole 1 to 2, pole 3 to 4, pole 5 to 6
    Circuit breaker closed. Pole 1–ground, pole 3–ground, pole 5–ground
    If the poles are in a common tank or cell. Pole 1 to 3, pole 3 to 5, pole 5 to 1

    (2) Megger (phase−to−phase and phase−to−ground) all buses from the POS to the main breaker or fuses.

    (3) The main circuit breaker(s) must have a dielectric test performed on the insulating medium (gas or oil). This test is not required for factory−sealed, circuit−switcher interrupters.

    1. Tests for Current Transformers and Current Circuits PS customers must perform the following tests for current transformers (CTs) and current circuits associated with PG&E−required relays:

    A. Check the saturation on all CTs. If this is not possible, a manufacturer’s curve is acceptable.

  • CRSC § 6.8947 High relevance — show source text

    major gas for back-
    ground/minor gas for text|None| |Nonmedical air and dental air|––|Yellow and white diagonal stripe/black|None| |Nonmedical vacuum and dental
    vacuum|––|White and black diagonal stripe/black boxed|None| |Laboratory air|––|Yellow and white checkerboard/black|None| |Laboratory vacuum|––|White and black checkerboard/black boxed|None| |Instrument air|––|Red/white|50–185 psi|

    For SI units: 1 pound-force per square inch = 6.8947 kPa, 1 inch of mercury vacuum (HgV) = 3.386 kPa

    1305.2 Minimum Flow Rates. Medical gas and vacuum systems shall be capable of supplying the flow rates listed in Table 1305.2.

    1305.3 Minimum Station Outlets and Inlets. Station outlets and inlets for medical gas and vacuum systems shall be provided as listed in Table 1305.3.

    1306.0 System Certification. 1306.1 Certification. Prior to a medical gas or vacuum system being placed in service, such system shall be certified in accordance with Section 1306.2.

    1306.2 Certification Tests. Certification tests, verified and attested to by the certification agency, shall include the following:

    (1) Verifying in accordance with the installation requirements.

    (2) Testing and checking for leakage, correct zoning, and identification of control valves.

    (3) Checking for identification and labeling of pipelines, station outlets, and control valves.

    (4) Testing for cross-connection, flow rate, system pressure drop, and system performance.

    (5) Functional testing of pressure relief valves and safety valves.

    (6) Functional testing of sources of supply.

    (7) Functional testing of alarm systems, including accuracy of system components.

    (8) Purge flushing of system and filling with specific source

    gases.

    (9) Testing for purity and cleanliness of source gases.

    (10)Testing for specific gas identity at each station outlet. 1306.3 Report Items. A report that includes the specific items addressed in Section 1306.2, and other information required by this chapter, shall be delivered to the Authority Having Jurisdiction prior to acceptance of the system. 1306.4 Components. Functioning of alarm components shall be verified in accordance with the testing and monitoring requirements of the manufacturer and the Authority Having Jurisdiction.

    TABLE 1305.2

    MINIMUM FLOW RATES (cubic feet per minute)

    MEDICAL SYSTEM FLOW RATE

    Oxygen
    0.71 CFM per outlet1

    Nitrous Oxide
    0.71 CFM per outlet1

    Medical Compressed Air
    0.71 CFM per outlet1

    Nitrogen
    15 CFM free air per outlet

    Vacuum
    1 SCFM per inlet2

    Carbon Dioxide
    0.71 CFM per outlet1

    Helium
    0.71 CFM per outlet

    For SI units: 1 cubic foot per minute (CFM) = 0.47 L/s

  • CRSC § 12-72 High relevance — show source text
    1. The spaces within devices or assemblies which have been individually or as assemblies tested and listed by a nationally recognized testing agency for the intended use need not comply with the provisions of Table 12-72-1C and Section 12-72102 (t), Items 3 and 4. The report shall note such devices and assemblies by reference to the test report.
    2. If a short circuit between uninsulated live-metal parts of the same polarity would prevent the normal signaling operation of the control unit without simultaneously producing a trouble signal, the spacings between such parts shall be not less than those indicated for “other parts” in Table 12-72-1C except in the case of the special devices mentioned in Footnote 2 to the table, the spacing between uninsulated live-metal parts of the same polarity, for any potential of 0-300 volts, shall be not less than [1] / 32 inch (0.8 mm) through air, and the spacing over surface shall be not less than [1] / 16 inch (1.6 mm) unless the smaller over-surface spacings permitted in Footnotes 3 and 4 of Table 12-72-1C.
    3. Spacings may be reduced provided a barrier or liner of suitable moisture-resistant insulating material of sufficient mechanical strength to withstand operation of equipment and arcing is used, and is reliably held in place.

    (u) Speakers—sound equipment. Speakers shall be of an approved type and designed with current capabilities for the intended function and purposes.

    2025 CALIFORNIA REFERENCED STANDARDS CODE 113

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    PROTECTIVE SIGNALING SYSTEMS

    PERFORMANCE

    Sec. 12-72-103.

    (a) General.

    1. The performance of a control unit or combination signaling system shall be investigated by subjecting a representative sample in commercial form to tests described in Sections 12-72-103 (b) through (q). Insofar as possible tests are to be made in the order indicated by the following test headings.

    2. A control unit shall be tested in the position in which it is designed to be installed for proper function.

    3. A combination signaling system console or rack is to be placed in a position simulating an actual installation against a vertical wood wall unless by its design, it is obviously intended for installation in the open. If ventilation openings are provided on the rear surfaces, it is to be spaced out 1 inch (25 mm) from the wall.

    4. Tests shall be made at rated frequency and voltage. The rated voltage for test purposes is considered to be 120 volts for units marked 110–125 volts, or 240 volts if marked 220–250 volts.

    5. Control units intended to be energized by trickle- charged batteries shall be tested at the rated trickle -charge of the battery except for over-and under-voltage tests.

    (b) Normal operation.

    1. A control unit or combination signaling system shall operate reliably and uniformly for all conditions of its intended performance when employed in conjunction with actuating devices, indicating devices and power supplies to form a combination type indicated by the wiring diagram and supplementary information supplied with it.
    2. To determine compliance, actuating devices, indicating devices optional equipment not necessary for transmission of a fire alarm signal, and power supplies are to be connected to the control unit to form a typical combination, and the control unit operated for each condition of its intended performance.
  • CRSC § 12-72 High relevance — show source text

    12-72-3 PROTECTIVE SIGNALING SYSTEMS

    SMOKE DETECTORS, COMBUSTION PRODUCTS TYPE

    STANDARD 12-72-3

    STATE FIRE MARSHAL

    SCOPE

    Sec. 12-72-300.

    (a) Basic. This standard represents the minimum basic requirements for the construction and performance of combustion products detectors of other than the photoelectric type to be employed in ordinary indoor locations and to be listed under this classification. The minimum design, construction and performance standards set forth herein are those deemed as minimum necessary to establish conformance to the regulations of the State Fire Marshal.

    (b) Definitions. For the purpose of this standard, the following definitions shall apply:

    1. Alarm signal. A signal intended to indicate an emergency fire condition.

    2. Annunciator. Integrally mounted or remotely connected visual indicating device intended to indicate an alarm or trouble condition.

    3. Ionization type detector. A device in which the presence of small combustion practices, often invisible to the eye, interfere with the normal ionization current resulting from radiation produced by a radioactive source in the detection chamber. A second chamber, employing a similar ionization source, may also be used to compensate for normal environmental ambient changes.

    4. Ionization-resistance bridge type detector. Employs both ionization and resistance bridge principles in one unit. Additive response from both detector elements is required for detector operation.

    5. Resistance-bridge type detector. Responds to an abnormal rate of increase of combustion products which change the impedance of second similar plate may be employed to compensate for normal ambient changes.

    6. Sensitivity. Relative degree of response of a detector. A high sensitivity denotes response to a lower concentration of combustion than a low sensitivity under identical fire test conditions.

    7. Trouble signal. A visual or audible signal intended to indicate a fault or trouble condition, such as an open or ground fault, occurring in the device or connected wiring.

    8. Voltage classification. A. Low voltage. A circuit classified as low voltage is one involving a potential of not more than 30 volts alternating current (42.4 peak) or direct current, and supplied from a circuit whose power is limited to a maximum of 100 volt

    amperes. B. High voltage. A circuit classified as high voltage is one having circuit characteristics in excess of those of a low-voltage circuit.

    TEST REPORTS

    Sec. 12-72-301.

    (a) The report shall include engineering data, and an analysis comparing the design against Sections 12-72-302 (a) through 12-72302 (t); it shall include wiring diagrams, operating manuals and photographs; it shall set forth the tests performed in accordance with this standard and the results thereof and shall verify the correctness of the electrical rating.

    (b) Listed components. Electrical wiring, material, devices, combination of devices, fittings, appliances and equipment which have been tested and listed by an approved listing agency for the intended purpose and use need not be individually retested.

    The report shall include the catalog number or other readily identifiable marking; the name of the approved listing agency, the laboratory test report number and date. Such individually tested and listed component parts and devices shall be subjected to the performance standard tests to determine its suitability for use in combination with other component parts, devices, circuits or equipment.

    (c) Listed detectors. Detectors which have been tested to any other acceptable test standard may be evaluated provided such test incorporates all features of this standard.

  • CRSC § 12-7 High relevance — show source text

    14 2025 CALIFORNIA REFERENCED STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE-RESISTIVE STANDARDS

    1. Specimens shall be exposed to the controlled conditions outlined in Item 1 until the interior or dampest section of the assembly attains a relative humidity of 75 percent or less. If during the conditioning of the specimen it appears desirable or is necessary to use accelerated drying techniques, it is the responsibility of the laboratory conducting the test to avoid procedures which will significantly alter the structural or fire endurance characteristics of the specimen or both from those produced as the result of drying in accordance with procedures given in Item 1.
    2. Within 72 hours prior to the fire test, information on the actual moisture content and distribution within the specimen shall be obtained. This information shall be included in the test report.

    TESTS OF BEARING WALLS AND PARTITIONS

    Sec. 12-7-106.

    (a) Size of sample. The area exposed to fire shall be not less than 100 square feet (9.3 m [2] ) with neither dimension less than 9 feet (2743 mm). The test specimen shall not be restrained on its vertical edges. The fire testing furnace, its arrangement and control during fire tests shall conform to SFM 12-7-3, Section 12-7-301 (a), Vertical Large-scale Wall Furnace.

    (b) Loading. During the fire endurance test, and fire and hose stream test, a superimposed lead shall be applied to the construction in a manner calculated to develop theoretically, as nearly as practicable, the working stresses contemplated by the design.

    (c) Conditions of acceptance. The test shall be regarded as successful if the following conditions are met:

    1. The wall or partition shall have sustained the applied load during the fire endurance test without passage of flame or gases hot enough to ignite conditioned cotton waste, for a period equal to that for which classification is desired.

    Note: Cotton waste shall be conditioned by drying in an oven at a temperature of 120°F (49°C) for a period of not less than 1 hour prior to the test. 2. The wall or partition shall have sustained the applied load during the fire and hose stream test as specified in Section 12-7105, without passage of flame, of gases hot enough to ignite cotton waste, or passage of the hose stream, and after cooling but within 72 hours after its completion shall sustain the dead lead of the test construction plus twice the superimposed load specified above. 3. Transmission of heat through the wall or partition during the fire endurance test shall not have been such as to raise the temperature on its unexposed surface more than 250°F (139°C) above its initial temperature. 4. Deflection of the wall or partition during the fire endurance test shall not exceed 6 inches (152 mm). The deflection of specimens varying from the dimensions given in Section 12-7-106 (a) shall be determined proportionately.

    TESTS OF NONBEARING WALLS AND PARTITIONS

    Sec. 12-7-107.

    (a) Size of sample. The area exposed to fire shall be not less than 100 square feet (9.3 m [2] ), with neither dimension less than 9 feet (2743 mm). The test specimen shall be restrained on all four edges. The fire testing furnace, its arrangement and control during fire tests shall conform to SFM 12-7-3, Section 12-7-301 (a), Vertical Large-scale Wall Furnace.

  • CRSC § 42.4 High relevance — show source text
    1. Trouble signal. A visual or audible signal intended to indicate a fault or trouble condition, such as an open or ground fault, occurring in the device or connected wiring.
    2. Voltage classification. A. Low voltage. A circuit classified as low voltage is one involving a potential of not more than 30 volts alternating current (42.4 peak) or direct current, and supplied from a circuit whose power is limited to a maximum of 100 volt

    amperes. B. High voltage. A circuit classified as high voltage is one having circuit characteristics in excess of those of a low-voltage circuit.

    TEST REPORTS

    Sec. 12-72-301.

    (a) The report shall include engineering data, and an analysis comparing the design against Sections 12-72-302 (a) through 12-72302 (t); it shall include wiring diagrams, operating manuals and photographs; it shall set forth the tests performed in accordance with this standard and the results thereof and shall verify the correctness of the electrical rating.

    (b) Listed components. Electrical wiring, material, devices, combination of devices, fittings, appliances and equipment which have been tested and listed by an approved listing agency for the intended purpose and use need not be individually retested.

    The report shall include the catalog number or other readily identifiable marking; the name of the approved listing agency, the laboratory test report number and date. Such individually tested and listed component parts and devices shall be subjected to the performance standard tests to determine its suitability for use in combination with other component parts, devices, circuits or equipment.

    (c) Listed detectors. Detectors which have been tested to any other acceptable test standard may be evaluated provided such test incorporates all features of this standard.

    (d) Rejection for cause. Compliance with these standards will not necessarily mean approval and listing, if when examined and tested, it is found to have other features which may impair the result intended by these regulations. Unusual constructions may require application of additional performance tests. The State Fire Marshal may refuse to approve any item for cause. (See the Cali- fornia Electrical Code .)

    (e) Smoke detectors only.

    1. A combustion products detector, as covered by these requirements consists of an assembly of electrical components arranged to detect one or more products of combustion. The products of combustion may consist of but are not necessarily

    2025 CALIFORNIA REFERENCED STANDARDS CODE 133

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    PROTECTIVE SIGNALING SYSTEMS

    limited to gaseous combustion products, water vapor and visible as well as invisible smoke particles. The detector includes provision for the connection to a source of power, signaling and optional remote control circuits. 2. These requirements cover the following types of detectors: A. Detectors intended for open area protection, intended for connection to a compatible power supply or control unit for operation as part of a fire alarm system. B. Detectors intended solely for control of releasing devices such as electromagnetic door holders, fire dampers, etc.

    C. Detectors suitable for Items A and B above.

    1. This standard does not cover the following: A. Detectors for monitoring the smoke density within flues or stacks.

    B. Duct detectors.

  • CRSC § 12-72 High relevance — show source text
    1. A limited-energy detector circuit shall conform to the following: A. The open-circuit voltage between any two wiring terminals and between any terminal and a grounded circuit part or noncurrent carrying metal part shall not exceed 50 volts when the control unit is connected to a power supply source of rated voltage and frequency. B. Overcurrent protection not in excess of 2 amperes shall be provided in such manner that each limited-energy circuit is protected. Current-limiting transformers may be substituted, provided that under condition of short circuit, current flow at the terminals will not exceed 2 amperes.

    (i) Jarring. The control unit or control equipment installed or supported in the position of its normal use connected to a power supply and in supervisory condition shall withstand jarring from impact or vibration such as may be experienced in service by striking the enclosure. Striking the enclosure shall not cause signaling operation of any part nor adversely affect any subsequent normal operation.

    (j) Temperature.

    1. Materials employed in the construction of a control unit or combination signaling system which have not been investigated and reported on by a nationally recognized testing laboratory as an assembly in the form intended for use shall be investigated and tested to determine temperature rises that may adversely affect the materials of construction, normal signaling operation of the equipment and fire hazard to building materials.
    2. A control unit shall be mounted on a wood panel representative of its manner of installation in service. It shall be connected to a power supply as indicated in Section 12-72-103 (a), Item 4, and operated under representative normal conditions liable to produce the highest temperatures.

    116 2025 CALIFORNIA REFERENCED STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    PROTECTIVE SIGNALING SYSTEMS

    1. A combination signaling system shall be set up representative of normal service conditions against a wood panel wall as specified in Section 12-72-103 (a), Item 3, connected to a supply circuit as indicated in Section 12-72-103 (c), Item 1, and operated under representative normal conditions liable to produce the highest temperatures.

    2. In control units equipped with time-limit cutouts which are not intended to limit the time of alarm-signal operation, the time-limit cutout shall be shunted out of the circuit for the duration of the test.

    3. A control unit or combination signaling system intended to provide impulse signals shall be operated by a testing device to provide one impulse per second, except that if the signal impulses are normally produced by a device which is a part of the control unit or equipment assembly, the test impulses are to be at the rate of normal operation of the device.

    4. Circuits shall be loaded representative of maximum load under normal service conditions. Resistors shall be adjusted for maximum wattage dissipation possible under conditions of normal service.

    5. Except for coils, temperature readings are to be preferably obtained by means of thermocouples. Temperatures are to be considered as constant when three successive readings taken at intervals of 10 percent of the previously elapsed duration of the test, but not less than 5 minute intervals, indicate no change. Temperature rise on coils may be determined by the resistance method or mercury thermometers.

    6. Horizontal screened or ventilation openings subject to accumulation of dust and lint shall be covered with loose cotton.

    7. Materials of construction and fire hazard to buildings shall be considered to be adversely affected if the temperature rise exceeds the limits shown in the following, based on an assumed ambient temperature of 25°C: A.

Frequently asked questions

Who must prepare the laboratory test report?

An approved testing laboratory (or approved agency) performing the investigation should prepare the report; it must document the engineering data, tests and results required by § 12-72-101 (a).

Do I need to retest every listed component inside a control unit?

No — components already tested and listed by an approved listing agency need not be retested individually, but the report must include their catalog number, listing agency, lab report number and date, and the assembled control unit must still be performance‑tested in combination to show suitability. § 12-72-101 (b).

Must the report prove the unit works at 120 V or 240 V?

The report must verify the correctness of the unit’s electrical rating. For test purposes, a unit marked 110–125 V is tested at 120 V, and one marked 220–250 V is tested at 240 V, per test‑voltage guidance in § 12-72-103 (a).

If my design differs from the standard, can a lab still get the unit approved?

Yes — differing constructions can be investigated and, if found substantially equivalent, may be given recognition; consult the State Fire Marshal for general requirements per § 12-72-101 (f).

Does compliance with the referenced test standards automatically guarantee listing?

No — compliance does not necessarily mean approval; the State Fire Marshal may refuse approval for cause or require additional tests for unusual constructions as noted in § 12-72-101 (d).

More in California Referenced Standards Code

Ask about the CRSC

Get cited, plain-English answers on the California Referenced Standards Code for your project — any code section, any scenario.

Start Free Trial

Related in the CRSC