CRSC · California Referenced Standards Code
Test apparatus and equipment for SFM 12-71-1
SFM 12-71-1 prescribes the standardized apparatus, flame-exposure method and reporting/classification rules used to test air (including grease) filters for California code compliance.
Last reviewed: July 6, 2026
Overview
SFM Standard 12-71-1 (Chapter 12-71) describes the required test apparatus, test method and classification/reporting requirements for air filters (including grease filters) used in jurisdictions under the State Fire Marshal’s standards . The standard sets out the physical test duct, burner arrangement, air velocity and observation requirements used to evaluate flame propagation and products of combustion during a standardized exposure.
This material matters because SFM 12-71-1 is explicitly referenced by the California Mechanical Code for grease-filter acceptance and installation (for example, Sections 509.2.3 and 509.2.3.4 require Class I performance when tested per SFM 12-71-1) and by other code provisions governing ventilation and exhaust systems . Practitioners use § 12-71-100 to find the apparatus dimensions (21 in. square duct, 13½ ft length), burner configuration, and the test procedure (clean filter exposure, 3‑minute flame application and downstream observations) when preparing or reviewing test reports .
Key referenced section: § 12-71-100 (Test apparatus and test method) contains the apparatus description (a), test method (b) and related classification/reporting requirements; Chapter 12-71 is indexed in the CRSC as the Air Filters standard and cross-referenced into the Mechanical and other codes for enforcement and listing purposes .
In this section
Code references
Grounded in the retrieved California Referenced Standards Code — click a citation to read the verbatim passage:
CRSC § 436.5. High relevance — show source text
DEPARTMENT OF HEALTH SERVICES
Authority: Sections 102, 208 and 25811.
Reference: Sections 102, 208 and 436.5.
ALL HEALING ARTS X-RAY INSTALLATIONS
Sec. 12-31C-101. All radiation shielding barriers in rooms and enclosures housing radiation machines shall comply with the mandatory standards and appendices in Report No. 35, “Dental X-RAY Protection”; Report 49, “Structural Shielding Design and Evaluation for Medical use of X-rays and Gamma Rays of Energies up to 10 MeV”; and Report No. 51, “Radiation Protection Design Guidelines for 0.1-100 MeV Particle Accelerator Facilities.” Published by the National Council on Radiation Protection and Measurements, 7910 Woodmont Avenue, Bethesda, Maryland 20814.
2025 CALIFORNIA REFERENCED STANDARDS CODE 105
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
106 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
12-71 AIR FILTERS
STANDARD 12-71-1
STATE FIRE MARSHAL
DESCRIPTION OF TEST APPARATUS, METHOD AND CLASSIFICATION REQUIREMENTS FOR AIR FILTERS
Sec. 12-71-100.
(a) Test apparatus.
- The test duct, made of M.S. gage galvanized sheet metal reinforced with angle irons, is 21 inches square (13 548 mm [2] ) and 13 [1] / 2 feet (4114 mm) long.
- One end of the duct is tapered to the discharge of a variable-speed blower and the other end is open to discharge. A metal filter frame is provided near the middle of the length of the duct to receive one 20 by 20 inches (508 mm by 508 mm) (nominal) filter unit. Two tightfitting doors, located to permit access to the filter frame, are each provided with a mica window to permit observation of both faces of the filter and conditions in the duct downstream from the filter.
- Two 1-inch (25 mm) pipe elbows, about 18 inches (457 mm) from the base of the test filter, form gas burner outlets adjusted to provide yellow, wavering flames. The burners consume approximately 4 cubic feet (approximately 1,000 Btu/cubic feet) of gas per minute.
- With the filter in place the air velocity is adjusted to approximately 200 linear feet per minute as measured at the discharge end of the duct by an Alnor Velometer Anemometer.
(b) Test method.
- Filters are tested clean, that is, unused. The flames are applied for 3 minutes during which time observations are made of both faces of the filter as to the downstream travel of flame or sparks and the density, duration and character of the products of combustion.
CRSC § 12-10 High relevance — show source text
The report shall include the manufacturer’s installation instructions. The report shall be verified by the laboratory or fire protection engineer responsible for the conduct of the test. The test report and evidence of listing by an approved listing agency may be provided for the applicable portions of these endurance and performance test procedures. Test reports prepared for other governmental agencies may be utilized to the extent that the test procedures contained herein have been duplicated.
(c) Test latches or locks.
- Samples. Samples of the test latch or lock shall be selected by the testing agency or fire protection engineer at random from the manufacturer’s current production runs. The types tested shall be considered to represent, for purposes of approval and listing, all lock types of a series, except that when there are variations of basic mechanical design and/or materials for mechanical parts, each variation shall be tested for compliance with the minimum performance test procedures.
- Modifications in design or test procedure. Devices involving dead-locking bolts, lever handles, shear pins in the outside know or other variations in design may require modifications in the test procedure in order to simulate the intended inservice conditions. Requests for modifications in the design and test procedures shall be filed for evaluation and approval by the State Fire Marshal before proceeding with the test.
(d) Test equipment.
- Static loading. The static loading apparatus used for the torque loading, axial load, vertical load and releasing torque tests shall consist of frame, test door and test block as detailed in Figure 12-10-2-1. Except as shown, materials shall be of steel, welded or bolted. The test apparatus may be of alternate design and construction having equivalent or greater rigidity.
- Endurance test. Apparatus for the endurance test shall consist of frame and test door as shown in Figure 12-10-2-2. An alternate design having equivalent or greater rigidity may be utilized. Alternate designs utilizing components of greater dimensions or greater rigidity may affect details of the approval and listing.
- Test equipment. Torque wrenches, spring scales, hydraulic or pneumatic pressure scales, or other instruments shall be calibrated in an approved manner. (e) Torque loading test. Each latch or lock shall be installed in a 1 [3] / 4 -inch (44 mm) thick test block in accordance with the manufacturer’s installation instructions. The test block shall be installed in the static loading test fixture. The torque load shall be applied to the inside door knob or lever. The knob or lever shall be turned or depressed to fully retract the latch bolt or dead bolt before application of the torque load. The applied torque load shall be 300 inch-pounds. After removal of the torque load the latch shall automatically return to its latch position, the dead bolt shall be extended to its locked position.
78 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
EXITS
Subsequent hand turning of the knob or depressing the lever shall retract the latch or dead bolt. Three representative latches and/or locks shall be tested and there shall be no failures.
CRSC § 9.5 High relevance — show source text
The specimen shall be suspended vertically with its lower edge 2 inches (51 mm) above the top of a [3] / 8 inch (9.5 mm) diameter Bunsen Burner. The test shall be performed in a draft-free area.
The flames from the burner shall be 4 inches (101 mm) long and shall be adjusted with sufficient air supply to eliminate any yellow flame tips but without any distinct inner blue cone.
The specimen shall be exposed to the flame at each corner and at not less than one other point along the lower edge. Each exposure shall be of sufficient duration to determine if the material will ignite and continue to burn, but shall be not less than 20 seconds.
The criteria for acceptance shall be as follows: (A) There shall be not more than intermittent flaming appreciably beyond the area exposed to the test flame. (B) Flame shall not reach the top of the specimen. (C) On removing the test flame there shall be not more than 1 second of after flaming except there may be nonprogressive flaming of short duration in areas of accumulated char which were directly exposed to the test flame.
Section 12-7-502
(a) Framed rigid combustible decorative material. Rigid combustible decorative material and assemblies of materials not more than [1] / 4 inch (6 mm) in thickness used for folding doors, room dividers, decorative screens and similar applications, and which are installed with all edges protected, shall conform to the following:
All exposed edges shall be protected with frames of metal or other noncombustible material, or solid wood of minimum [1] / 4 inch (6 mm) dimension.
The total square foot area of the material shall not exceed ten percent of that of the floor area of the room in which the material is installed.
When tested as follows, flames shall not reach the top edge of the specimen. The test shall be conducted in a draft free area, on a specimen of the material 12 inches by 12 inches (305 mm by 305 mm) suspended at a 45-degree angle from the horizontal with the upper and lower edges in a horizontal plane. The test flame shall be 3 inches (76 mm) long from a Bunsen burner of approximately [1] / 2 -inch (13 mm) inside diameter with the air supply completely shut off. The burner shall be positioned so that its top is 1 inch (25 mm) vertically below a point on the lower surface of the test specimen, 1 inch (25 mm) up from its lower horizontal edge and midway between the inclined edges. The exposure to the test flame and the duration of test shall be for a period of 2 minutes.
2025 CALIFORNIA REFERENCED STANDARDS CODE 35
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
36 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
12-7A MATERIALS AND CONSTRUCTION METHODS
FOR EXTERIOR WILDFIRE EXPOSURE
EXTERIOR WALL SIDING AND SHEATHING
SFM STANDARD 12-7A-1
12-7A-1.1 Application. The minimum design, construction and performance standards set forth herein for exterior wall siding and sheathing are those deemed necessary to establish conformance to the provisions of these regulations. Materials and assemblies that meet the performance criteria of this standard are acceptable for use as defined in California Building Standards Code.
CRSC § 12-7 High relevance — show source text
12-7A-4.8 PART B. Burning brand exposure.
12-7A-4.8.1 Equipment.
- Wind tunnel. The wind tunnel shall have the capability of providing 12 mph (5.4 m/s) airflow over the deck assembly.
- Anemometer. Device for measuring airflow across the deck.
- Burner. Gas-fueled burner for brand ignition.
12-7A-4.8.2 Test system preparation. See Figure 2. The ASTM E108 “A” brand roof test apparatus is to be used, with the following modifications:
- Deck support. The deck shall be supported horizontally with the center 60 inches (150 mm) from the front opening of the wind tunnel and the joists parallel to the airflow and resting on two transverse metal supports. The top surfaces of these supports, no more than 3 inches (75 mm) wide, are at the same height as the floor of the wind tunnel.
- Fragments. Burning fragments shall be free to fall to the floor of the room.
12-7A-4.8.3 Conduct of tests.
- Number of tests. Conduct the test on three replicate assemblies.
- Moisture content. Measure the moisture content of the wooden members of the assembly using a moisture meter (ASTM D4444).
- Procedure. Adhere to ASTM E108 “Standard Test Methods for Fire Tests of Roof Coverings” (burning brand test, “A” brand), with apparatus modified as described above in “Test system preparation” and the following procedure: 3.1. The air velocity shall be calibrated using the 60-inch (1.5 m) framework spacing, with a smooth noncombustible calibration deck at a 5-inch (127 mm) per 12-inch (305 mm) horizontal incline positioned 60 inches (1.5 m) from the front opening of the wind tunnel. All other measurement details shall be followed as specified in Sections 4.4.2, 4.4.3 and 4.4.4 of ASTM E108. Although ASTM E108 specifies calibration to be conducted with the 33-inch (840-mm) framework spacing used for the intermittent flame test set up, tests have shown that at the nominal 12 mph
46 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR WILDFIRE EXPOSURE
setting, there was not difference in measured velocity between the 33- and 60-inch (838 mm and 1524 mm) framework spacing. 3.2. Mount the test specimen at a zero horizontal incline positioned 60 inches (1.5 m) from the front opening of the wind tunnel.
3.3. Ignite the “A” brands as specified in Section 9.4 of ASTM E108 as reprinted here:
- Each 12- x 12-inch (300 x 300 mm) face for 30 seconds.
- Each 2.25- x 12-inch (57 x 300 mm) edge for 45 seconds.
- Each 12- x 12-inch (300 x 300 mm) face again for 30 seconds. 3.4. Center the burning brand laterally on the deck with the front edge 2.5 inches (64 mm) from the entering air edge of the deck.
CRSC § 0.05 High relevance — show source text
B. Micro−ohm test on the main circuit breaker(s) at the POS.
C. Timing test showing the time from the trip initiation to the opening of the main poles. Proving insulation tests, as described below.
D. Proving Insulation
(1) Megger circuit breaker(s) at the POS operated by PG&E require relays (see Table 2 below).
094676 Page 6 of 16 Rev. #00: 3/25/2022
OH: Services UG: Services Primary Electric Service Requirements Greenbook
Table 2 Circuit Breaker Positions and Connections
Circuit Breaker Position Connection Circuit breaker open. Each pole to ground, pole 1 to 2, pole 3 to 4, pole 5 to 6 Circuit breaker closed. Pole 1–ground, pole 3–ground, pole 5–ground If the poles are in a common tank or cell. Pole 1 to 3, pole 3 to 5, pole 5 to 1 (2) Megger (phase−to−phase and phase−to−ground) all buses from the POS to the main breaker or fuses.
(3) The main circuit breaker(s) must have a dielectric test performed on the insulating medium (gas or oil). This test is not required for factory−sealed, circuit−switcher interrupters.
- Tests for Current Transformers and Current Circuits PS customers must perform the following tests for current transformers (CTs) and current circuits associated with PG&E−required relays:
A. Check the saturation on all CTs. If this is not possible, a manufacturer’s curve is acceptable.
B. Prove the ratio of all CTs by using current (primary to secondary) or voltage (secondary to primary).
C. Check the CTs for the proper polarity.
D. Check the CT circuits for the proper connections.
E. Check the continuity of the CTs by:
(1) Applying primary or secondary current at the CT block.
(2) Verifying that the proper current exists in each phase relay and the ground relay.
Customers must perform each test (primary or secondary) in all combinations prove that all phase relays and ground relays have proper connections.
PS customers must also ensure that no loose wiring or parallel current paths exist, by applying or injecting the current to achieve a secondary reading of 5 amperes (A) in each relay.
Check each phase of each current circuit feeding PG&E–required relays. Megger the total circuit with the ground wire lifted (to prove that only one ground exists).
- Relay and Fuse Tests
The testing requirements for relays/fuses include:
A. PS customers must field test the settings of PG&E required relays to verify the following items:
(1) The minimum operating point at which the relay picks up (minimum pickup).
(2) Time delays at three different current−test points, in integral multiples of the minimum pickup that closely characterize the relay time−current curve.
(3) Test results must be within the tolerances listed below:
(a) Current/Voltage/Time ± 10 %
(b) Impedance/Phase Angle ± 0.05 %
(c) Frequency ± 0.05 Hz
B. Check all fuses for continuity before energizing.
- Tests Recommended (But Not Required by PG&E) for the PS Customers
A. Transformer
CRSC § 509.2 High relevance — show source text
(2) Where a grease removal device is listed for separation distances less than those required in Section
509.2 and Section 509.2.1, the listing requirements shall be permitted. [NFPA 96:6.2.1.4]
(3) Grease removal devices supplied as part of listed hood assemblies shall be installed in accordance with the terms of the listing and the manufacturer’s instructions. [NFPA 96:6.2.1.5]
509.2.2 Grease Removal Device Protection. Where the distance between the grease removal device and the appliance flue outlet (heat source) is less than 18 inches (457 mm), grease removal devices shall be protected from combustion gas outlets and from direct flame impingement occurring during normal operation of cooking appliances producing high flue gas temperatures.
[NFPA 96:6.2.2.1]
509.2.2.1 Installation. This protection shall be permitted to be accomplished by the installation of a steel or stainless steel baffle plate between the heat source and the grease removal device. [NFPA 96:6.2.2.2]
509.2.2.2 Size and Location. The baffle plate shall be sized and located so that flames or combustion gases travel a distance not less than 18 inches (457 mm) from the heat source to the grease removal device. [NFPA 96:6.2.2.3]
509.2.2.3 Clearance. The baffle shall be located not less than 6 inches (152 mm) from the grease removal device. [NFPA 96:6.2.2.4]
509.2.3 Grease Filters. Grease filters shall be listed
and constructed of steel or other non-combustible material, and shall be of rigid construction that will not distort or crush under normal operation, handling, cleaning, or replacement. [SFM] For applications listed in Section 1.11.0 regulated by the Office of the State Fire Marshal, grease filters shall be Class I when tested in accordance with the test method in Title 24, Part 12, Chapter 12-71, SFM Standard 12-71-1.
509.2.3.1 Arrangement. Grease filters shall be arranged so that all exhaust air passes through the grease filters. [NFPA 96:6.2.3.4]
509.2.3.2 Accessibility. Grease filters shall be easily accessible for removal. [NFPA 96:6.2.3.5]
509.2.3.3 Angled Installation. Grease filters shall be installed at an angle not less than 45 degrees (0.79 rad) from the horizontal. [NFPA 96:6.2.3.6]
509.2.3.4 [DPH] Grease filters shall be Class I when tested in accordance with the test method in
SFM 12-71-1.
509.2.4 Grease Drip Trays. Grease filters shall be equipped with a grease drip tray beneath their lower edges. [NFPA 96:6.2.4.1]
CRSC § 509.2.3 High relevance — show source text
509.2.3 Grease Filters. Grease filters shall be listed
and constructed of steel or other non-combustible material, and shall be of rigid construction that will not distort or crush under normal operation, handling, cleaning, or replacement. [SFM] For applications listed in Section 1.11.0 regulated by the Office of the State Fire Marshal, grease filters shall be Class I when tested in accordance with the test method in Title 24, Part 12, Chapter 12-71, SFM Standard 12-71-1.
509.2.3.1 Arrangement. Grease filters shall be arranged so that all exhaust air passes through the grease filters. [NFPA 96:6.2.3.4]
509.2.3.2 Accessibility. Grease filters shall be easily accessible for removal. [NFPA 96:6.2.3.5]
509.2.3.3 Angled Installation. Grease filters shall be installed at an angle not less than 45 degrees (0.79 rad) from the horizontal. [NFPA 96:6.2.3.6]
509.2.3.4 [DPH] Grease filters shall be Class I when tested in accordance with the test method in
SFM 12-71-1.
509.2.4 Grease Drip Trays. Grease filters shall be equipped with a grease drip tray beneath their lower edges. [NFPA 96:6.2.4.1]
509.2.4.1 Size and Pitch. Grease drip trays shall be kept to the minimum size needed to collect grease. Grease drip trays shall be pitched to drain into an enclosed metal container having a capacity not exceeding 1 gallon (4 L). [NFPA 96:6.2.4.2, 6.2.4.3]
114 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
EXHAUST SYSTEMS
509.2.5 Grease Filter Orientation. Grease filters that require a specific orientation to drain grease shall be clearly so designated on the face of the filter as to be visible with the filter installed, or the hood or filter shall be constructed so that filters cannot be installed in the wrong orientation. [NFPA 96:6.2.5]
509.3 Solid-Fuel Grease Removal Devices. Where solid-fuel cooking equipment is provided with grease removal devices, these devices shall be in accordance with Section 517.0.
510.0 Exhaust Duct Systems.
510.1 General. Ducts shall not pass through fire walls.
[NFPA 96:7.1.1]
510.1.1 Fire Hazards. All ducts shall lead directly to the exterior of the building, so as not to unduly increase any fire hazard. [NFPA 96:7.1.2]
510.1.2 Interconnection. Duct systems shall not be interconnected with any other building ventilation or exhaust system. [NFPA 96:7.1.3]
CRSC § 12-16 High relevance — show source text
CALIFORNIA STANDARD FOR RESIDENTIAL EXCESS FLOW ACTUATED AUTOMATIC GAS SHUTOFF VALVES (SEE CCR TITLE 24, PART 5, CHAPTER 12) STANDARD 12-16-2
DIVISION OF THE STATE ARCHITECT
Authority: Sections 19200–19204, Health and Safety Code. Reference: Sections 19201.5 and 19202, Health and Safety Code.
DIVISION 1—CONSTRUCTION
SCOPE
Sec. 12-16-201. The American Society for Testing and Materials (ASTM) F2138-12(2017) Standard Specification for Excess Flow Valves for Natural Gas Service, and the American National Standards Institute (ANSI) Z21.93-2017/CSA 6.30-2017 Excess Flow Valves for Natural and LP Gas with Pressure up to 5 psig, shall be the applicable standards used by the Division of the State Architect for certification of these devices.
Sec. 12-16-201.1. Each installation of a customer-owned device that satisfies this standard shall be in accordance with the California Plumbing Code (CCR Title 24, Part 5).
2025 CALIFORNIA REFERENCED STANDARDS CODE 103
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
104 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
12-31C RADIATION SHIELDING STANDARDS
STANDARD 12-31C-1
DEPARTMENT OF HEALTH SERVICES
Authority: Sections 102, 208 and 25811.
Reference: Sections 102, 208 and 436.5.
ALL HEALING ARTS X-RAY INSTALLATIONS
Sec. 12-31C-101. All radiation shielding barriers in rooms and enclosures housing radiation machines shall comply with the mandatory standards and appendices in Report No. 35, “Dental X-RAY Protection”; Report 49, “Structural Shielding Design and Evaluation for Medical use of X-rays and Gamma Rays of Energies up to 10 MeV”; and Report No. 51, “Radiation Protection Design Guidelines for 0.1-100 MeV Particle Accelerator Facilities.” Published by the National Council on Radiation Protection and Measurements, 7910 Woodmont Avenue, Bethesda, Maryland 20814.
2025 CALIFORNIA REFERENCED STANDARDS CODE 105
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
106 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
12-71 AIR FILTERS
STANDARD 12-71-1
STATE FIRE MARSHAL
DESCRIPTION OF TEST APPARATUS, METHOD AND CLASSIFICATION REQUIREMENTS FOR AIR FILTERS
Sec. 12-71-100.
(a) Test apparatus.
- The test duct, made of M.S. gage galvanized sheet metal reinforced with angle irons, is 21 inches square (13 548 mm [2] ) and 13 [1] / 2 feet (4114 mm) long.
CRSC § 1313.1.6 High relevance — show source text
1313.1.6 Test Medium. The test medium shall be air, nitrogen, carbon dioxide, or an inert gas. Oxygen shall not be used as a test medium. [NFPA 54:8.1.2]
1313.2 Test Preparation. Test preparation shall comply with Section 1313.2.1 through Section 1313.2.6.
1313.2.1 Pipe Joints. Pipe joints, including welds, shall be left exposed for examination during the test.
Exception: Covered or concealed pipe end joints that have been previously tested in accordance with this code.
[NFPA 54:8.1.3.1]
1313.2.2 Expansion Joints. Expansion joints shall be provided with temporary restraints, if required, for the additional thrust load under test. [NFPA 54:8.1.3.2]
1313.2.3 Appliances and Equipment. Appliances and equipment that are not to be included in the test shall be either disconnected from the piping or isolated by blanks, blind flanges, or caps. Flanged joints at which blinds are inserted to blank off other equipment during the test shall not be required to be tested. [NFPA 54:8.1.3.3] 1313.2.4 Designed for Operating Pressures Less than Test Pressure. Where the piping system is connected to appliances or equipment designed for operating pressures of less than the test pressure, such appliances or equipment shall be isolated from the piping system by disconnecting them and capping the outlet(s). [NFPA 54:8.1.3.4]
1313.2.5 Designed for Operating Pressures Equal to or Greater than Test Pressure. Where the piping system is connected to appliances or equipment designed for operating pressures equal to or greater than the test pressure, such appliances or equipment shall be isolated from the piping system by closing the individual appliance or equipment shutoff valve(s). [NFPA 54:8.1.3.5] 1313.2.6 Safety. All testing of piping systems shall be performed in a manner that protects the safety of employees and the public during the test. [NFPA 54:8.1.3.6]
1313.3 Test Pressure. This inspection shall include an air, CO2, or nitrogen pressure test, at which time the gas piping shall stand a pressure of not less than 10 psi (69 kPa) gauge pressure. Test pressures shall be held for a length of time satisfactory to the Authority Having Jurisdiction but in no case less than 15 minutes with no perceptible drop in pressure. For welded piping, and for piping carrying gas at pressures in excess of 14 inches water column (3.5 kPa) pressure, the test pressure shall be not less than 60 psi (414 kPa) and shall be continued for a length of time satisfactory to the Authority Having Jurisdiction, but in no case for less than 30 minutes.
For CSST carrying gas at pressures in excess of 14 inches water column (3.5 kPa) pressure, the test pressure shall be 30 psi (207 kPa) for 30 minutes. These tests shall be made using air, CO2, or nitrogen pressure and shall be made in the presence of the Authority Having Jurisdiction. Necessary apparatus for conducting tests shall be furnished by the permit holder.
CRSC § 12-7 Medium relevance — show source text
40 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR WILDFIRE EXPOSURE
EXTERIOR WINDOWS
SFM STANDARD 12-7A-2
12-7A-2.1 Application. Exterior window assemblies that meet the performance criteria of this standard are acceptable for use as defined in the California Building Standards Code.
12-7A-2.2 Scope. This standard evaluates the performance of exterior windows used in structures when exposed to direct flames.
12-7A-2.3 Referenced documents.
- AAMA (for definitions) Training Manual, Residential & Light Commercial Window and Door Installation Training and Registration Program.
- CAWM 400-95, Standard Practice for Installation of Windows with Integral Mounting Flange in Wood Frame Construction.
12-7A-2.4 Definitions.
Frame (Jambs). This usually consists of two vertical members (side jambs) and two horizontal members (head and sill) that hold the sash. Frames and sash are typically made of steel, aluminum, vinyl, fiberglass, wood or a combination of these materials.
Glazing. The glass in a window. It may include layers of plastic as well as glass.
Sash. The fixed or movable parts of the window in which the panes of glass are set.
12-7A-2.5 Test apparatus.
- Wall assembly test module. The module is designed to permit rapid installation and removal of window/wall assemblies, and is designed to prevent edge penetration of fire at the margins. It includes two noncombustible side walls attached to a wall frame assembly, and a simulated soffit that is also noncombustible. The assembly permits a prefabricated 4 × 8 ft (1.2 × 2.4 m) wall section containing the test window to be inserted from the rear and sealed in such a way that the edges are protected from fire (see Figure 1).
- Burner. A 4 × 39 inch (100 × 1000 mm) diffusion burner shall be used. Natural gas, methane or propane shall be supplied to the burner through a metered control system. The gas supply to the burner shall produce a net heat output of 150 ± 4 kW throughout the flame exposure. Burner output can be determined from HRR or calculated from the gas flow rate, temperature and pressure.
- Burner location. The burner shall be positioned so that it is centered relative to the width of the wall assembly and against the wall. The distance from the floor to the top of the burner shall be 12 inches (300 mm).
12-7A-2.6 Test assembly.
- Window. The window width cannot exceed 3 feet (900 mm) due to the limitations of the test fixture. The burner’s flame shall cover the full width of the window sill. The distance from top of the burner to bottom of window will be 8 inches (200 mm).
CRSC § 4.4 Medium relevance — show source text
It shall not be tested until a large portion of its final strength has been attained, and if it contains moisture, until the excess has been removed to achieve an air-dry condition in accordance with the requirements given in Items 1 through 3. The testing equipment and sample undergoing the fire test shall be protected from any condition of wind or weather that might lead to abnormal results. The ambient air temperature at the beginning of the test shall be within the range of 50 to 90°F (10 to 32°C). The velocity of air across the unexposed surface of the sample, measured just before the test begins, shall not exceed 4.4 feet per second, as determined by an anemometer placed at right angles to the unexposed surface. If mechanical ventilation is employed during the test, an air stream shall not be directed across the surface of the specimen.
- Prior to the fire test, constructions shall be conditioned with the objective of providing, within a reasonable time, a moisture condition within the specimen approximately representative of that likely to exist in similar constructions in buildings. For purposes of standardization, this condition is to be considered as that which would be established at equilibrium resulting from drying in an ambient atmosphere of 50 percent relative humidity at 73°F (23°C). However, with some constructions, it may be difficult or impossible to achieve such uniformity within a reasonable period of time. Accordingly, where this is the case, specimens may be tested when the dampest portion of the structure, the portion at 6-inch (152 mm) depth below the surface of massive constructions, has achieved a moisture content corresponding to drying to equilibrium with air in the range of 50 to 75 percent relative humidity at 73 + 5°F. In the event that specimens dried in a heated building fail to meet these requirements after a 12-month conditioning period, or in the event that the nature of the construction is such that it is evident that drying of the specimen interior will be prevented by hermetic sealing, these requirements may be waived, except as to attainment of a large portion of final strength, and in the specimen tested in the condition in which it then exists.
14 2025 CALIFORNIA REFERENCED STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
FIRE-RESISTIVE STANDARDS
- Specimens shall be exposed to the controlled conditions outlined in Item 1 until the interior or dampest section of the assembly attains a relative humidity of 75 percent or less. If during the conditioning of the specimen it appears desirable or is necessary to use accelerated drying techniques, it is the responsibility of the laboratory conducting the test to avoid procedures which will significantly alter the structural or fire endurance characteristics of the specimen or both from those produced as the result of drying in accordance with procedures given in Item 1.
- Within 72 hours prior to the fire test, information on the actual moisture content and distribution within the specimen shall be obtained. This information shall be included in the test report.
TESTS OF BEARING WALLS AND PARTITIONS
Sec. 12-7-106.
(a) Size of sample. The area exposed to fire shall be not less than 100 square feet (9.3 m [2] ) with neither dimension less than 9 feet (2743 mm). The test specimen shall not be restrained on its vertical edges. The fire testing furnace, its arrangement and control during fire tests shall conform to SFM 12-7-3, Section 12-7-301 (a), Vertical Large-scale Wall Furnace.
CRSC § 416.2 Medium relevance — show source text
0_
414.0
415.0
416.0 – 416.2
416.3
416.4
417.0
418.0
419.0
Table 4-A
Table 4-B
Table 4-C
Table 402.1
Table 403.7_Notes 11 & 12_
|X|||||||X||||||||||||||||| |Adopting Agency
Adopt Entire Chapter
Adopt Entire Chapter as
amended (amended sections
listed below)
Adopt only those sections
that are listed below
Chapter/Section
401.1
401.3
401.3.1
402.1
402.1.2
402.2
402.3
403.0
403.7.2.1 – 403.7.2.4
405.3
406.0
407.0
408.0
409.0
410.0
411.0
412.0
413.0
414.0
415.0
416.0 – 416.2
416.3
416.4
417.0
418.0
419.0
Table 4-A
Table 4-B
Table 4-C
Table 402.1
Table 403.7_Notes 11 & 12_
||||X|X||||||||||||||||||||This state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
2025 CALIFORNIA MECHANICAL CODE 67
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
68 2025 CALIFORNIA MECHANICAL CODE
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CHAPTER 4
VENTILATION AIR
401.0 General.
401.1 Applicability. This chapter contains requirements for ventilation air supply, exhaust, and makeup air requirements for occupiable spaces within a building. [OSHPD 1, 1R, 2, 3, 4 & 5] See Sections 406.0 through 419.0. [SFM] Air filters shall comply with all requirements of Part 12, Title 24, Chap- ter 12-71, SFM Standard 12-71-1. Spaces within buildings, except those within a dwelling unit in residential occupancies where occupants are nontransient, shall comply with Section 402.0 through Section 404.0. Requirements for ventilation air rate for dwelling units in residential occupancies, where the occupants are nontransient, shall be in accordance with Section 405.0 or ASHRAE 62.2.
Frequently asked questions
What specifically does § 12-71-100 require for the test duct and burners?
§ 12-71-100(a) specifies a galvanized steel test duct 21 inches square and 13½ feet long, with a variable-speed blower, two burner outlets producing yellow wavering flames (about 4 cu ft/min each) positioned near the filter, and an air velocity of approximately 200 fpm at the duct discharge .
Do grease filters used in commercial hoods have to be tested to SFM 12-71-1?
Yes — the California Mechanical Code requires grease filters in certain regulated applications to be Class I when tested in accordance with SFM 12-71-1 (see Sections 509.2.3 and 509.2.3.4) and those test reports/listings are used for acceptance and listing purposes .
Can test reports from other agencies be used for approval?
Test reports and listings from approved listing agencies or from other governmental tests may be used where the procedures are duplicated; the CRSC describes report contents and verification requirements that laboratories or fire protection engineers must meet .
More in California Referenced Standards Code
- Administration and scope — CRSC Chapter 12 overview
- Air filter standards (Chapter 12‑71)
- Building and facility access / accessibility standards (Chapters 12‑11A, 12‑11B)
- Engineering regulations — quality and design of construction materials (12‑16 series)
- Exits and means of egress (Chapters 12‑10 series)
- Protective signaling systems and detectors (Chapters 12‑72‑1, ‑2, ‑3)
- Radiation shielding standards (Chapter 12‑31C)
- Referenced standards index / cross‑reference table (Part 12 listing of referenced standards)
- Releasing systems for security bars (egress-release standards)
- Standards for insulating materials (Chapter 12‑13)
Ask about the CRSC
Get cited, plain-English answers on the California Referenced Standards Code for your project — any code section, any scenario.
Start Free Trial