CMC · California Mechanical Code

Exhaust systems, local exhaust and recirculation rules

This hub orients users to CMC requirements on exhaust, local exhaust, makeup/transfer air, and numerical/qualitative limits on recirculated air (notably §403.9 and Chapter 5).

Last reviewed: July 6, 2026

Overview

This hub covers California Mechanical Code requirements for exhaust systems, local (source) exhaust, makeup/transfer air, and limits on recirculating contaminated airstreams. Chapter 4 (Ventilation Air) and Chapter 5 (Exhaust Systems) set the baseline: Chapter 4 explains ventilation rates, classification of airstreams and recirculation limits (see §403.9), and Chapter 5 contains the exhaust-duct and commercial-kitchen hood rules and fire-safety provisions.

Key, commonly used provisions include the airstream classification and recirculation rules in §403.9 and its subsections (Class 1–4 limits and exemptions), the parking-garage continuous-exhaust and distribution rules in §403.7.2, and the kitchen/hood exhaust requirements and sizing guidance found in the Chapter 5/Appendix E provisions (for example E 503.5.11.2).

Practical compliance points emphasized by the Code include providing adequate makeup or transfer air for exhausted spaces, limiting recirculation based on the classified source air (with strict prohibition for the highest-risk Class 4), and demonstrating system performance by testing and balancing (see §403.10). These rules are often coordinated with Title 24 energy requirements for local exhaust controls in dwellings and commercial kitchens.

In this section

Code references

Grounded in the retrieved California Mechanical Code — click a citation to read the verbatim passage:

  • CMC § 403.7.2.3 High relevance — show source text

    403.7.2.3 Exhaust Inlet Distribution. [HCD 1 & 2] To ensure proper exhaust of contaminated air and fumes from parking garages, exhaust systems utilizing multiple exhaust inlets shall be designed so that exhaust inlets are distributed in such a manner

    that no portion of the parking garage is more than 50 feet (15 240 mm) from an exhaust inlet. Such exhaust inlets shall be installed so that the highest elevation of the exhaust inlet is no greater than 12 inches (305 mm) below the lowest ceiling level.

    Exception: Garage exhaust systems designed with- out distributed exhaust inlets may have their exhaust inlets designed based on the principles of engineering and mechanics and shall provide the minimum required exhaust rate in Table 403.7.

    403.7.2.4 Exhaust System Operation. [HCD 1 & 2] Exhaust systems shall operate continuously unless one of the exceptions to continuous operation of Section 403.7.2 is utilized.

    403.8 Dynamic Reset. The system shall be permitted to be designed to reset the outdoor air intake flow ( Vot ), the space or ventilation zone airflow ( Voz ) as operating conditions change, or both. [ASHRAE 62.1:6.2.6]

    403.9 Air Classification and Recirculation. Air shall be

    classified as shown in Table 402.1, Table 403.7, or Table 403.9, and its recirculation shall be limited in accordance with Section

    403.9.1 through Section 403.9.4. {ASHRAE 62.1:5.18} Recirculated air shall not be taken from prohibited locations in accordance with Section 311.3.

    Air (return, transfer, or exhaust air) leaving each space or location shall be designated at an expected air-quality classification not less than that shown in Table 402.1, Table 403.7, or Table 403.9 or as approved by the Authority Having Jurisdiction. Air leaving spaces or locations that are not listed in Table 402.1, Table 403.7, or Table 403.9 shall be designated with the same classification as air from the most similar space or location listed in terms of occupant activities and building construction.

    Exception: Air from spaces where environmental tobacco smoke (ETS) is present. (Classification of air from spaces where ETS is present is not addressed. Spaces that are expected to include ETS do not have a classification listed in Table 402.1.)

    [ASHRAE 62.1:5.18.1]

    TABLE 403.9

    AIRSTREAMS OR SOURCES DESCRIPTION AIR CLASS

    [ASHRAE 62.1: TABLE 6-3]

    DESCRIPTION AIR
    CLASS

    Kitchen grease hoods
    4
    Kitchen hoods other than grease
    3

    Diazo printing equipment discharge
    4

    Hydraulic elevator machine room
    2

    Laboratory hoods
    4
    Paint spray booths
    4
    Refrigerating machinery rooms 3

    403.9.1 Class 1 Air. Recirculation or transfer of Class 1 air to any space shall be permitted. [ASHRAE 62.1:5.18.3.1]

  • CMC § 62.1. High relevance — show source text

    (3) The mechanical exhaust flow minus the available transfer air from conditioned spaces or return air plenums on the same floor, not in different smoke or fire compartments, and that at their closest point are within 15 feet (4572 mm) of each other. Available transfer air is that portion of outdoor ventilation air that:

    (a) is not required to satisfy other exhaust needs,

    (b) is not required to maintain pressurization of other spaces, and

    (c) is transferable according to applicable codes and standards and to the class of air recirculation limitations in Chapter 4 or ASHRAE 62.1.

    Exceptions: (1) Biosafety level classified laboratories 3 or higher. (2) Vivarium spaces. (3) Spaces that are required by applicable codes and standards to be maintained at positive pressure relative to adjacent spaces. For spaces taking this exception, any transferable air that is not directly transferred shall be made available to the associated air-handling unit and shall be used whenever economizer or other options do not save more energy. (4) Spaces where the demand for transfer air may exceed the available transfer airflow rate and where the spaces have a required negative pressure relationship. For spaces taking this exception, any transferable air that is not directly transferred shall be made available to the associated air-handling unit and shall be used whenever economizer or other options do not save more energy. [ASHRAE 90.1:6.5.7.1] E 503.5.11.2 Kitchen Exhaust Systems. Replacement air introduced directly into the hood cavity of kitchen exhaust hoods shall not exceed 10 percent of the hood exhaust airflow rate. [ASHRAE 90.1:6.5.7.2.1]

    E 503.5.11.2.1 Exhaust Flow Rate. Where a kitchen or dining facility has a total kitchen hood exhaust airflow rate exceeding 5000 ft [3] /min (2.3597 m [3] /s), each hood shall have an exhaust rate in accordance with Table E 503.5.11.2.1.

    Where a single hood, or hood section, is installed over appliances with different duty ratings, the maximum allowable flow rate for the hood or

    hood section shall not exceed the values in Table E 503.5.11.2.1 for the highest appliance duty rating under the hood or hood section. Refer to ASHRAE 154 for definitions of hood type, appliance duty, and net exhaust flow rate. Exception: Seventy-five percent or more of the total replacement air is transfer air that would otherwise be exhausted. [ASHRAE 90.1:6.5.7.2.2] E 503.5.11.2.2 Kitchen or Dining Facility. Where a kitchen or dining facility has a total kitchen hood exhaust airflow rate more than 5000 ft [3] /min (2.3597 m [3] /s), then one of the following shall be provided:

    (1) Fifty percent or more of all replacement air is transfer air that would otherwise be

    exhausted.

    (2) Demand ventilation systems on 75 percent or more of the exhaust air. Such systems shall be capable of and configured to provide 50 percent or more reduction in exhaust and replacement air system airflow rates, including controls necessary to modulate airflow in response to appliance operation and to maintain full capture and containment of smoke, effluent, and combustion products during cooking and idle.

  • CMC § 403.9.2 High relevance — show source text

    403.9.2 Class 2 Air. Recirculation of Class 2 air within the space of origin shall be permitted. Recirculation or transfer of Class 2 air to other Class 2 or Class 3 spaces shall be permitted, provided that the other spaces are used for the same or similar purpose or task and involve the same or similar pollutant sources as the Class 2 space. Transfer of Class 2 air to toilet rooms shall be permitted. Recirculation or transfer of Class 2 air to Class 4 spaces shall be permitted. Class 2 air shall not be recirculated or transferred to Class 1 spaces.

    Exception: When using any energy recovery device, recirculation from leakage, carryover, or transfer from the exhaust side of the energy recovery device shall be permitted but shall not be counted as outdoor air. Exhaust air transfer ratio of Class 2 air shall not exceed 10 percent of the outdoor air intake flow. {ASHRAE 62.1:5.18.3.2 – 5.18.3.2.5}

    403.9.3 Class 3 Air. Recirculation of Class 3 air within the space of origin shall be permitted. Class 3 air shall not be recirculated or transferred to any other space.

    Exception: When using any energy recovery device, recirculation from leakage, carryover, or transfer from the exhaust side of the energy recovery device shall be permitted but shall not be counted as outdoor air. Exhaust air transfer ratio of Class 3 air shall not exceed 5 percent of the outdoor air intake flow. {ASHRAE 62.1:5.18.3.3 – 5.18.3.3.2}

    403.9.4 Class 4 Air. Class 4 air shall not be recirculated or transferred to any space or recirculated within the space of origin. [ASHRAE 62.1:5.18.3.4]

    403.10 Air Balance. All mechanical ventilation systems shall be tested, balanced, and operated to demonstrate that the installation and performance of the systems are in accordance with the design intent. All testing and balancing shall be performed by a technician certified by the Associated Air Balance Council (AABC), the National Environmental Balancing Bureau (NEBB), the Testing, Adjusting and Balancing Bureau (TABB), or other equivalent approved agencies.

    Exception: For single family residential, compliance with Section 403.10 shall not be required.

    2025 CALIFORNIA MECHANICAL CODE 75

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    VENTILATION AIR

    404.0 Alternative Procedure for Multiple-Zone Sys- tems Ventilation Efficiency.

    404.1 System Ventilation Efficiency. The system ventilation efficiency shall equal the lowest zone ventilation efficiency among the ventilation zones served by the air handler in accordance with Equation 404.1. [ASHRAE 62.1:A1.3] This section presents an alternative procedure for calculating the system ventilation efficiency ( Ev ) for multiple zone recirculating systems that shall be used when Section 403.5.1.3 is not used.

    Ev = minimum ( Evz ) (Equation 404.1)

    404.2 Average Outdoor Air Fraction. The average outdoor air fraction ( X s) for the ventilation system shall be determined in accordance with Equation 404.2.

  • CMC § 402.1 Medium relevance — show source text

    Air (return, transfer, or exhaust air) leaving each space or location shall be designated at an expected air-quality classification not less than that shown in Table 402.1, Table 403.7, or Table 403.9 or as approved by the Authority Having Jurisdiction. Air leaving spaces or locations that are not listed in Table 402.1, Table 403.7, or Table 403.9 shall be designated with the same classification as air from the most similar space or location listed in terms of occupant activities and building construction.

    Exception: Air from spaces where environmental tobacco smoke (ETS) is present. (Classification of air from spaces where ETS is present is not addressed. Spaces that are expected to include ETS do not have a classification listed in Table 402.1.)

    [ASHRAE 62.1:5.18.1]

    TABLE 403.9

    AIRSTREAMS OR SOURCES DESCRIPTION AIR CLASS

    [ASHRAE 62.1: TABLE 6-3]

    DESCRIPTION AIR
    CLASS

    Kitchen grease hoods
    4
    Kitchen hoods other than grease
    3

    Diazo printing equipment discharge
    4

    Hydraulic elevator machine room
    2

    Laboratory hoods
    4
    Paint spray booths
    4
    Refrigerating machinery rooms 3

    403.9.1 Class 1 Air. Recirculation or transfer of Class 1 air to any space shall be permitted. [ASHRAE 62.1:5.18.3.1]

    403.9.2 Class 2 Air. Recirculation of Class 2 air within the space of origin shall be permitted. Recirculation or transfer of Class 2 air to other Class 2 or Class 3 spaces shall be permitted, provided that the other spaces are used for the same or similar purpose or task and involve the same or similar pollutant sources as the Class 2 space. Transfer of Class 2 air to toilet rooms shall be permitted. Recirculation or transfer of Class 2 air to Class 4 spaces shall be permitted. Class 2 air shall not be recirculated or transferred to Class 1 spaces.

    Exception: When using any energy recovery device, recirculation from leakage, carryover, or transfer from the exhaust side of the energy recovery device shall be permitted but shall not be counted as outdoor air. Exhaust air transfer ratio of Class 2 air shall not exceed 10 percent of the outdoor air intake flow. {ASHRAE 62.1:5.18.3.2 – 5.18.3.2.5}

    403.9.3 Class 3 Air. Recirculation of Class 3 air within the space of origin shall be permitted. Class 3 air shall not be recirculated or transferred to any other space.

    Exception: When using any energy recovery device, recirculation from leakage, carryover, or transfer from the exhaust side of the energy recovery device shall be permitted but shall not be counted as outdoor air. Exhaust air transfer ratio of Class 3 air shall not exceed 5 percent of the outdoor air intake flow. {ASHRAE 62.1:5.18.3.3 – 5.18.3.3.2}

  • CMC § 90.1 Medium relevance — show source text

    [ASHRAE 90.1:6.5.6.2.1] E 503.5.10.2.2 Capacity. The required heat recovery system shall have the capacity to provide the smaller of:

    (1) Sixty percent of the peak heat-rejection load at design conditions or

    (2) Preheat of the peak service hot-water draw to 85°F (29°C).

    Exceptions:

    (1) Facilities that employ condenser heat recovery for space heating with a heat recovery

    444 2025 CALIFORNIA MECHANICAL CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    APPENDIX E

    TABLE E 503.5.11.2.1 MAXIMUM NET EXHAUST FLOW RATE, CFM PER LINEAR FOOT OF HOOD LENGTH

    [ASHRAE 90.1: TABLE 6.5.7.2.2]

    TYPE OF HOOD LIGHT DUTY
    EQUIPMENT
    MEDIUM DUTY
    EQUIPMENT
    HEAVY DUTY
    EQUIPMENT
    EXTRA HEAVY DUTY
    EQUIPMENT
    Wall-mounted canopy 140 210 280 385
    Single island 280 350 420 490
    Double island (per side) 175 210 280 385
    Eyebrow 175 175 Not allowed Not allowed
    Backshelf/ Pass-over 210 210 280 Not allowed

    For SI units: 1 foot = 304.8 mm, 1 cubic foot per minute = 0.00047 m [3] /s

    (3) The mechanical exhaust flow minus the available transfer air from conditioned spaces or return air plenums on the same floor, not in different smoke or fire compartments, and that at their closest point are within 15 feet (4572 mm) of each other. Available transfer air is that portion of outdoor ventilation air that:

    (a) is not required to satisfy other exhaust needs,

    (b) is not required to maintain pressurization of other spaces, and

    (c) is transferable according to applicable codes and standards and to the class of air recirculation limitations in Chapter 4 or ASHRAE 62.1.

    Exceptions: (1) Biosafety level classified laboratories 3 or higher. (2) Vivarium spaces. (3) Spaces that are required by applicable codes and standards to be maintained at positive pressure relative to adjacent spaces. For spaces taking this exception, any transferable air that is not directly transferred shall be made available to the associated air-handling unit and shall be used whenever economizer or other options do not save more energy. (4) Spaces where the demand for transfer air may exceed the available transfer airflow rate and where the spaces have a required negative pressure relationship. For spaces taking this exception, any transferable air that is not directly transferred shall be made available to the associated air-handling unit and shall be used whenever economizer or other options do not save more energy. [ASHRAE 90.1:6.5.7.1] E 503.5.11.2 Kitchen Exhaust Systems. Replacement air introduced directly into the hood cavity of kitchen exhaust hoods shall not exceed 10 percent of the hood exhaust airflow rate. [ASHRAE 90.1:6.5.7.2.1]

  • California Mechanical Code Medium relevance — show source text

    A mechanical code, as with any other code, is intended to be adopted as a legally enforceable document to safeguard health, safety, property, and public welfare. The code cannot be effective without satisfactory provisions for its administration and enforcement. The Authority Having Jurisdiction is to review the proposed and completed work and decide whether a mechanical system conforms to the code requirements. As a public servant, the Authority Having Jurisdiction enforces the code in an unbiased proper manner. The design professional is responsible for the design of a safe mechanical system. The contractor is responsible for installing the system in accordance with the plans.

    Chapter 2 Definitions. To maintain consistency and encourage the use of common terminology, Chapter 2 establishes definitions to provide clarity of terms and promote the use of a common language throughout the code. Understanding definitions within the context of their application enables greater collaboration, efficiency, standardization, and interpretation in applying and enforcing terms used throughout the code. Codes are technical documents, and every term can impact the meaning of the code text. Terms not defined have a normally accepted meaning.

    Chapter 3 General Regulations. Chapter 3 regulates the general requirements, not specific to other chapters, for installing mechanical systems. Many regulations are not specific mechanical requirements but relate to the overall mechanical system. This chapter contains safety requirements for appliance location and installation, appliance and system access, condensate disposal, clearances to combustibles, and return or outside air used in mechanical systems. Listing method of approval, based on applicable nationally recognized standards for the safe and proper installation of mechanical systems, is essential to ensure protection of public health, safety, and welfare. These safety requirements provide protection for piping, tubing, materials, and structures, including provisions for installation practices addressing stress and strain, sleeving, and hanger support. The building’s structural stability is protected by the regulations for cutting and notching of structural members.

    Chapter 4 Ventilation Air. Chapter 4 regulates the minimum requirements for ventilation air supply, exhaust, and makeup air for occupiable spaces within a building. Building ventilation is one important factor affecting the relationship between airborne transmission of respiratory infections and the health and productivity of workers. Ventilation air may be composed of mechanical or natural ventilation, infiltration, recirculated air, transfer air, or a suitable combination of these. Providing a comfortable and healthy indoor environment for building occupants is of primary concern. When determining ventilation rates, typical and unusual significant sources of indoor pollution need to be controlled. Areas such as kitchens, bathrooms, and laundries are all built to allow specific functions. These spaces produce pollutants such as moisture, odors, volatile organic compounds, particles, or combustion byproducts. The purpose of local exhaust is to control concentrates of these pollutants in the room into which they were emitted and to reduce the spread of pollutants into other parts of the occupancy. Local exhaust ventilation is the source control for pollution that is expected in certain rooms. Using local exhaust to extract contaminants before they mix with the indoor environment is essential.

    Chapter 5 Exhaust Systems. Chapter 5 regulates the minimum requirements for exhaust systems. Chapter 5 contains two parts: Part I provides exhaust requirements for environmental air ducts and product conveying systems; Part II provides exhaust requirements for commercial hoods and kitchen ventilation. Environmental air ducts include exhaust ducts used for transporting the air from domestic kitchens, bathrooms, shower rooms, lo

  • CMC § 402.2.1.6 Medium relevance — show source text

    402.2.1.6(A)(1) Single Openings . . . . . . . . . . . . . . . 71

    Table Minimum Openable Areas:

    402.2.1.6(A)(2) Two Vertically

    Spaced Openings . . . . . . . . . . . . . . 71

    402.3 Mechanical Ventilation . . . . . . . . . . 71

    402.4 Outdoor Air Intakes. . . . . . . . . . . . . 71

    Table 402.4.1 Air Intake Minimum

    Separation Distance . . . . . . . . . . . . 72

    403.0 Ventilation Rates . . . . . . . . . . . . . . 72

    403.1 General. . . . . . . . . . . . . . . . . . . . . . 72

    403.2 Zone Calculations. . . . . . . . . . . . . . 73

    403.3 Single-Zone Systems . . . . . . . . . . . 73

    403.4 One Hundred Percent Outdoor

    Air Systems . . . . . . . . . . . . . . . . . . 73

    403.5 Multiple-Zone Recirculating Systems . . . . . . . . . . . . . . . . . . . . . 73

    403.6 Design for Varying Operating Conditions. . . . . . . . . . . . . . . . . . . . 74

    403.7 Exhaust Ventilation. . . . . . . . . . . . . 74

    403.8 Dynamic Reset . . . . . . . . . . . . . . . . 75

    403.9 Air Classification and

    Recirculation. . . . . . . . . . . . . . . . . . 75

    Table 403.9 Airstreams or Sources

    Description Air Class . . . . . . . . . . . 75

    403.10 Air Balance . . . . . . . . . . . . . . . . . . . 75

    404.0 Alternative Procedure for

    Multiple-Zone Systems Ventilation Efficiency . . . . . . . . . . . 76

    xxx

    404.1 System Ventilation Efficiency . . . . . 76

    404.2 Average Outdoor Air Fraction. . . . . 76

    404.3 Zone Ventilation Efficiency . . . . . . . 76

    405.0 Ventilation for Residential

    Occupancies. . . . . . . . . . . . . . . . . . 77

    405.1 General. . . . . . . . . . . . . . . . . . . . . . 77

    405.2 Ventilation Air Rate. . . . . . . . . . . . . 77

    405.3 Bathroom Exhaust . . . . . . . . . . . . . 77

    405.4 Kitchen Exhaust . . . . . . . . . . . . . . . 77

    405.5 Ventilation Openings . . . . . . . . . . . 77

    406.0 Evaporative Cooling System for Health Care Facilities . . . . . . . . 78

    407.0 Ventilation System Details . . . . . . . 78

    407.1 General. . . . . . . . . . . . . . . . . . . . . . 78

    407.2 Outdoor Air Intakes and

  • CMC § 160.2 Medium relevance — show source text

    7. Design and control requirements for quantities of outdoor air . A. All mechanical ventilation and space-conditioning systems shall be designed with and have installed ductwork, dampers and controls to allow outside air rates to be operated at the minimum levels specified in Section 160.2(c)3 or the rate required for make-up of exhaust systems that are required for an exempt or covered process, for control of odors or for the removal of contaminants within the space. B. All variable air volume mechanical ventilation and space-conditioning systems shall include dynamic controls that maintain measured outside air ventilation rates within 10 percent of the required outside air ventilation rate at both full and reduced supply airflow conditions. Fixed minimum damper position is not considered to be dynamic and is not an allowed control strategy. C. Measured outdoor air rates of constant volume mechanical ventilation and space-conditioning systems shall be within 10 percent of the required outside air rate.

    8. Air classification and recirculation limitations. Air classification and recirculation limitations of air shall be based on the air classification as listed in Table 160.2-B or Table 160.2-D, in accordance with the following: A. Class 1 air is air with low contaminant concentration, low sensory-irritation intensity or inoffensive odor. Recirculation or transfer of Class 1 air to any space shall be permitted; [ASHRAE 62.1:5.13.3.1] B. Class 2 air is air with moderate contaminant concentration, mild sensory-irritation intensity or mildly offensive odor (Class 2 air also includes air that is not necessarily harmful or objectionable but that is inappropriate for transfer or recirculation to spaces used for different purposes). Recirculation or transfer of Class 2 air shall be permitted in accordance with Sections 160.2(c)8Bi through 160.2(c)8Bv: i. Recirculation of Class 2 air within the space of origin shall be permitted [ASHRAE 62.1:5.13.3.2.1]. ii. Recirculation or transfer of Class 2 air to other Class 2 or Class 3 spaces shall be permitted, provided that the other spaces are used for the same or similar purpose or task and involve the same or similar pollutant sources as the Class 2 space [ASHRAE 62.1:5.13.3.2.2]; or iii. Transfer of Class 2 air to toilet rooms [ASHRAE 62.1:5.13.3.2.3]; or

    iv. Recirculation or transfer of Class 2 air to Class 4 spaces [ASHRAE 62.1:5.13.3.2.4]. v. Class 2 air shall not be recirculated or transferred to Class 1 spaces. [ASHRAE 62.1:5.13.3.2.5]. Exception to Section 160.2(c)8Bv: When using any energy recovery device, recirculation from leakage, carryover or transfer from the exhaust side of the energy recovery device is permitted. Recirculated Class 2 air shall not exceed 10 percent of the outdoor air intake flow. C. Class 3 air is air with significant contaminant concentration, significant sensory-irritation intensity or offensive odor. Recirculation or transfer of Class 3 air shall be permitted in accordance with Sections 160.2(c)8Ci and 160.2(c)8Cii: i. Recirculation of Class 3 air within the space of origin shall be permitted.

  • CMC § 2025 Medium relevance — show source text

    The building’s structural stability is protected by the regulations for cutting and notching of structural members.

    Chapter 4 Ventilation Air. Chapter 4 regulates the minimum requirements for ventilation air supply, exhaust, and makeup air for occupiable spaces within a building. Building ventilation is one important factor affecting the relationship between airborne transmission of respiratory infections and the health and productivity of workers. Ventilation air may be composed of mechanical or natural ventilation, infiltration, recirculated air, transfer air, or a suitable combination of these. Providing a comfortable and healthy indoor environment for building occupants is of primary concern. When determining ventilation rates, typical and unusual significant sources of indoor pollution need to be controlled. Areas such as kitchens, bathrooms, and laundries are all built to allow specific functions. These spaces produce pollutants such as moisture, odors, volatile organic compounds, particles, or combustion byproducts. The purpose of local exhaust is to control concentrates of these pollutants in the room into which they were emitted and to reduce the spread of pollutants into other parts of the occupancy. Local exhaust ventilation is the source control for pollution that is expected in certain rooms. Using local exhaust to extract contaminants before they mix with the indoor environment is essential.

    Chapter 5 Exhaust Systems. Chapter 5 regulates the minimum requirements for exhaust systems. Chapter 5 contains two parts: Part I provides exhaust requirements for environmental air ducts and product conveying systems; Part II provides exhaust requirements for commercial hoods and kitchen ventilation. Environmental air ducts include exhaust ducts used for transporting the air from domestic kitchens, bathrooms, shower rooms, locker rooms, janitor’s closets, and clothes dryers. Systems that carry nonabrasive exhaust, such as smoke, moderate abrasives such as sawdust, and high abrasives such as manganese or acid vapors use product-conveying ducts. Part II provides the minimum fire safety requirements related to the design, installation, inspection, and maintenance of grease-type operations, such as cooking, for both fuel-gas and solid fuel. Cooking produces a significant amount of smoke, fumes, vapors, heat, and other pollutants. Therefore, acceptable kitchen ventilation is necessary to prevent fires from the build-up of grease and to provide the occupants protection from smoke, unpleasant odors, pollutants, and dangerous gases. There are two types of exhaust hoods (Type I and Type II) used in commercial kitchen applications.

    xiv 2025 CALIFORNIA MECHANICAL CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    FORMAT OF THE UNIFORM MECHANICAL CODE

    Type I hoods are intended to be installed above equipment or appliances that generate grease or smoke. Type II hoods are intended to be installed above equipment or appliances that generate steam, vapor, heat, or odors and do not generate grease or smoke.

    Chapter 6 Duct Systems. Chapter 6 regulates requirements for ducts and plenums that are portions of a heating, cooling, ventilation, or exhaust system. This chapter contains material and installation requirements for metal, gypsum, factory-made, flexible, and plastic ducts. It also contains provisions for duct insulation, dampers, fire protection, and automatic shutoff for the building’s air distribution system. It is worth noting that exhaust ducts are regulated by Chapter 5, and combustion air ducts are regulated by Chapter 7.

  • CMC § 120.1 Medium relevance — show source text

    **

    1. All mechanical ventilation and space-conditioning systems shall be designed with and have installed ductwork, dampers and controls that allow design minimum outside air rates to be operated at no less than the larger of (1) the minimum levels specified in Section 120.1(c)3; or (2) the rate required for make-up of exhaust systems that are required for a covered or noncovered process, for control of odors, or for the removal of contaminants within the space.
    2. All variable air volume mechanical ventilation and space-conditioning systems shall include dynamic controls that are capable of maintaining measured outside air ventilation rates within 10 percent of the design minimum outside air ventilation rate at both full and reduced supply airflow conditions. Fixed minimum damper position is not considered to be dynamic and is not an allowed control strategy.
    3. All mechanical ventilation and space-conditioning systems shall be tested to confirm their ability to operate within 10 percent of the design minimum outside air rate.

    (g) Air classification and recirculation limitations. Air classification and recirculation limitations of air shall be based on the air classification as listed in Table 120.1-A or Table 120.1-C, and in accordance with the requirements of Sections 120.1(g)1 through 4.

    Note: Air class definitions are taken directly from ASHRAE 62.1 and are duplicated here for convenience.

    1. Class 1 Air is air with low contaminant concentration, low sensory-irritation intensity or inoffensive odor. Recirculation or transfer of Class 1 air to any space shall be permitted; [ASHRAE 62.1:5.13.3.1]

    2025 CALIFORNIA ENERGY CODE 71

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL, HOTEL/MOTEL OCCUPANCIES, AND COVERED PROCESSES—MANDATORY REQUIREMENTS

    1. Class 2 Air is air with moderate contaminant concentration, mild sensory-irritation intensity or mildly offensive odors (Class 2 air also includes air that is not necessarily harmful or objectionable but that is inappropriate for transfer or recirculation to spaces used for different purposes). Recirculation or transfer of Class 2 air shall be permitted in accordance with Sections 120.1(g)2A through 120.1(g)2E: A. Recirculation of Class 2 air within the space of origin shall be permitted [ASHRAE 62.1:5.13.3.2.1]; B. Recirculation or transfer of Class 2 to other Class 2 or Class 3 spaces shall be permitted, provided that the other spaces are used for the same or similar purpose or task and involve the same or similar pollutant sources as the Class 2 space [ASHRAE 62.1:5.13.3.2.2]; or C. Transfer of Class 2 air to toilet rooms [ASHRAE 62.1:5.13.3.2.3]; or

    D. Recirculation or transfer of Class 2 air to Class 4 spaces [ASHRAE 62.1:5.13.3.2.4]; or E. Class 2 air shall not be recirculated or transferred to Class 1 spaces. [ASHRAE 62.1:5.13.3.2.5] Exception to Section 120.1(g)2E: When using any energy recovery device, recirculation from leakage, carryover, or transfer from the exhaust side of the energy recovery device is permitted.

  • CMC § 701.1 Medium relevance — show source text

    701.1, 701.1.1, 701.8, 701.10,

    802.6.3.1, 902.2, 902.12, 902.13

    Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . (see Ducts) Economizer . . . . . . . . . . . . . . . . . (see Economizer, air) Exhaust . . . . . . . . . . . . . . . . . . . . . . . (see Air, exhaust) Filters. . . . . . . . . . . . . . . . . . . . . . . . . . . (see Filters, air) Furnace . . . . . . . . . . . . . . . . . (see Furnaces, warm air) Heaters. . . . . . . . . . . . . . . . . . . . . . . . . (see Heater, air)

    Makeup . . . . . . . . . . . . . . . 203.0, 401.1, 403.7, 504.4.1,

    505.10, 511.3, 517.1.2, 517.1.3,

    517.6.1, 517.6.2, 519.6, 701.1,

    701.3, 930.5.4, 1106.2.8, 1106.6,

    1106.11.11.1, 1220.5, E 503.4.6.9,

    E 503.5.11.3, I 801.1.4

    Moving Systems . . . . . . . . . . . . . 203.0, 609.1, I 801.1.6, Outside 203.0, Table 310.3,

    311.1, 311.3, Chapter 4,

    908.3.2, 932.1, 1105.1,

    E 502.10.2, E 805.0

    Pollution control

    devices. . . . . . . . . . . . . . . . . . . 203.0, 512.3, 512.3.5,

    513.1.1, 513.3.3

    2025 CALIFORNIA MECHANICAL CODE 571

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    INDEX

    Recirculation. . . . . . . . . . . . . . . . . . 403.3, 403.5, 403.7,

    403.9, 404.3, 407.4.5, 512.3.5

    Replacement . . . . . . . . . . . . . . . . . . . (see Air, makeup)

    Return . . . . . . . . . . . . . 203.0, 311.0, 402.3, 403.2.2.1.2,

    403.2.2.2.2, 404.3.2, 517.1.2,

    604.4, 905.6, 1105.1, Appendix E

    Supply . . . . . . . . . . 203.0, Chapter 4, 914.5, 1104.2.3.2

  • CMC § 1.0 Medium relevance — show source text

    where:

    Q tot = total required ventilation rate, cfm. A floor = dwelling-unit floor area, ft [2] . N br = number of bedrooms (not to be less than 1). b. All dwelling units in a multifamily building shall use the same whole-dwelling unit ventilation system type. The dwelling unit shall comply with Subsections 1 and 2 below.

    1. Balanced or supply ventilation . A balanced or supply ventilation system shall provide the required whole-dwelling-unit ventilation airflow. Balanced systems with heat recovery or energy recovery that serve a single dwelling unit shall have a fan efficacy of ≤1.0 W/cfm; and
    2. Compartmentalization testing. The air leakage rate shall not exceed 0.3 cubic feet per minute at 50 Pa (0.2 inch water) per ft [2] of dwelling unit envelope surface area as confirmed by ECC-Rater field verification and diagnostic testing in accordance with the procedures specified in Reference Appendix RA3.8 or NA2.3 as applicable. In multifamily buildings with four or more habitable stories,

    202 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MULTIFAMILY BUILDINGS—MANDATORY REQUIREMENTS

    the field verification and diagnostic testing which requires an ECC-Rater may alternatively be performed by a certified Mechanical Acceptance Test Technician according to the requirements specified in Reference Appendix NA1.9. v. Multifamily building central ventilation system airflow rate tolerance. Multifamily building central ventilation systems that serve multiple dwelling units shall have airflow rates in each dwelling unit served that meet or exceed a design ventilation airflow rate specification. a. Designers shall specify a design ventilation airflow rate for each dwelling unit that is equal to or greater than the rate specified by Equation 160.2-B. b. The design ventilation airflow rate for each dwelling unit shall be stated on the building design plans approved by the enforcement agency. c. Airflow in each dwelling unit shall be no more than 20 percent greater than the specified design ventilation airflow rate. Ventilation systems shall utilize mechanical or software airflow control means to ensure each of the dwelling-unit airflows can be maintained at the design ventilation airflow within this tolerance at all times. System airflow control-means may include but are not limited to constant air regulation devices, orifice plates and variable speed central fans. vi. Local mechanical exhaust. A local mechanical exhaust system shall be installed in each kitchen and bathroom. Systems shall be rated for airflow in accordance with ASHRAE 62.2 Section 7.1. a. Nonenclosed kitchens shall have a demand-controlled mechanical exhaust system meeting the requirements of Section 160.2(b)2Avic. b. Enclosed kitchens and all bathrooms shall have either one of the following options 1 or 2:

    1. A demand-controlled mechanical exhaust system meeting the requirements of Section 160.2(b)2Avic; or
    2. A continuous mechanical exhaust system meeting the requirements of Section 160.2(b)2Avid. c. Demand-controlled mechanical exhaust. A local mechanical exhaust system shall be designed to be operated as needed.
    3. Control and operation. Demand-controlled mechanical exhaust systems shall be provided with at least one of the following controls: A. A readily accessible occupant-controlled ON-OFF control. B. An automatic control that does not impede occupant ON control.
    4. **Ventilation rate and capture efficiency.

Frequently asked questions

What are the CMC limits on recirculating exhaust air from different source types?

Recirculation is set by air class in §403.9: Class 1 may be recirculated to any space; Class 2 can be recirculated within the space and to like Class 2/3 spaces but not to Class 1 (with energy-recovery exceptions and a 10% transfer limit in some cases); Class 3 may be recirculated only within the origin space (with a 5% ERV exception); and Class 4 air must not be recirculated or transferred.

When is local (mechanical) exhaust required for kitchens and bathrooms?

The CMC’s Chapter 5 addresses commercial kitchen hoods and exhaust requirements; for dwelling units Title 24 (Energy) mandates local mechanical exhaust in each kitchen and bathroom and describes demand-controlled or continuous exhaust options and capture/flow criteria. Refer to Chapter 5 and the Title 24 local-exhaust provisions for the specific dwelling controls and flow rates.

Are there special rules for parking-garage exhaust systems?

Yes — enclosed parking garages have continuous ventilation requirements and specific inlet-distribution and minimum-rate rules (see §403.7.2), with limited exceptions for detector-controlled intermittent operation.

More in California Mechanical Code

Ask about the CMC

Get cited, plain-English answers on the California Mechanical Code for your project — any code section, any scenario.

Start Free Trial

Related in the CMC