CMC · California Mechanical Code

Machinery rooms, ventilation & detection

This hub summarizes CMC requirements for refrigerating machinery rooms: room construction, mechanical and emergency ventilation, detector performance and alarm/shutdown actions.

Last reviewed: July 6, 2026

Overview

This area of the California Mechanical Code (CMC) governs refrigeration and machinery rooms where refrigerants or other special hazards may be present — focusing on room construction, ventilation (normal and emergency), detector performance, alarms, and emergency shutdown/controls. Key requirements include emergency ventilation sizing and rates (see §1106.2.9) and continuous or detector-activated mechanical ventilation with specified exhaust/makeup arrangements (see §1106.11.11 and §1106.11.6.1) .

Detection and alarm requirements set detector set points, response times and alarm/ventilation actions (see §1106.11.8–§1106.11.11 and Table 1106.11.10.2), and require detectors to automatically de-energize compressors, pumps and other ignition sources at specified concentrations (see §1106.11.9 and §1106.11.6.2) file. The CMC also covers combustion-air separation, makeup-air intakes, room dimensions, access, and special machinery-room rules (see §1106.5, §1106.6, §1106.9 and §1107.1) to protect occupants and responders and to coordinate with electrical and fire-code provisions (e.g., emergency shutoff and remote controls) file.

In this section

Code references

Grounded in the retrieved California Mechanical Code — click a citation to read the verbatim passage:

  • CMC § 1106.11.10.1 High relevance — show source text

    1106.11.10.1 Visual and Audio. The alarm shall

    have visual and audible annunciation inside the refrigerating machinery room and outside each entrance to the refrigerating machinery room.

    [ASHRAE 15:8.13.10.1] 1106.11.10.2 Detector Activation. The refrigerant detector set points shall activate an alarm in accordance with the type of reset in Table 1106.11.10.2. Manual reset type alarms shall have the reset located inside the refrigerating machinery room. [ASHRAE 15:8.13.10.2]

    TABLE 1106.11.10.2 REFRIGERANT DETECTOR SET POINTS, RESPONSE TIMES, ALARMS, AND VENTILATION LEVELS

    [ASHRAE 15: TABLE 8-1]

    LIMIT VALUE RESPONSE TIME
    (seconds)
    ALARM TYPE ALARM RESET TYPE VENTILATION RATE VENTILATION
    RESET TYPE
    Set point≤ OEL ≤300 Trouble Alarm Automatic Level 1 Automatic
    Set point≤ RCL ≤15 Emergency Alarm Manual Level 2 Manual

    2025 CALIFORNIA MECHANICAL CODE 235

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    REFRIGERATION

    1106.11.10.3 Alarm Levels. Alarms set at levels

    other than Table 1106.11.10.2 (such as IDLH) and automatic reset alarms are permitted in addition to those required by Section 1106.11.10. The meaning of each alarm shall be clearly marked by signage near the annunciators. [ASHRAE 15:8.13.10.3]

    1106.11.10.4 Emergency. In the event of a failure during a refrigerant detector self-test in accordance with Section 1106.11.9(5), a trouble alarm signal shall be transmitted to an approved monitored location. [ASHRAE 15:8.13.10.4]

    1106.11.11 Mechanical Ventilation. Machinery rooms, in accordance with Section 1106.11, shall be vented to the outdoors, using mechanical ventilation in accordance with Section 1106.11.11.1, Section 1106.11.11.2, and Section 1106.11.11.3. [ASHRAE 15:8.13.11]

    1106.11.11.1 Mechanical Ventilation Require- ments. Mechanical ventilation referred to in Sec tion 1106.11.11 shall be in accordance with all of

    the following:

    (1) Include one or more power-driven fans capable of exhausting air from the machinery room; multispeed fans shall be permitted.

    (2) Electric motors driving fans shall not be placed inside ducts; fan rotating elements shall be nonferrous or non-sparking, or the casing shall consist of or be lined with such material.

    (3) Include provision to supply make-up air to replace that being exhausted; ducts for supply to and exhaust from the machinery room shall serve no other area; the makeup air supply locations shall be positioned relative to the exhaust air locations to avoid short circuiting.

  • CMC § 1107.1.7.1 High relevance — show source text

    1107.1.7.1 Mechanical Ventilation. The mechanical ventilation system in the machinery room is run continuously in accordance with Section 1106.11.6.1 and failure of the mechanical ventilation system actuates an alarm, or the mechanical ventilation system in the machinery room is activated by one or more refrigerant detectors, in accordance with the requirements of Section 1106.11.11.

    1107.1.7.2 Refrigeration Detectors. For the refrigerant detection required in Section 1106.2.5, detection of refrigerant concentration that exceeds 25 percent of the LFL or the upper detection limit of the refrigerant detector, whichever is lower, shall automatically de-energize the following equipment in the machinery room:

    (1) refrigerant compressors

    (2) refrigerant pumps

    (3) normally-closed automatic refrigerant valves

    1107.1.7.3 Machinery Rooms. The machinery room shall comply with Section 1106.11. 1107.1.8 Group A2, A3, B2, or B3 Refrigerants. Where any refrigerant of Groups A2, A3, B2, or B3 are used, the machinery room shall comply with Class 1, Division 2, of of the California Electrical Code .

    1107.1.9 Refrigeration Systems. As part of the mechanical ventilation system in accordance with Section 1106.2.8, refrigeration systems that contain more

    than 110 pounds (50 kg) of any Group A2L, A2, A3, B2L, B2, or B3, refrigerant shall have not less than one exhaust air inlet located adjacent to each system not more than 9 feet (3 m) away.

    1107.1.10 Remote Control. Remote control of the

    mechanical equipment in the refrigeration machinery room shall be provided immediately outside the machinery room door solely for the purpose of shutting down the equipment in an emergency. Ventilation fans shall be on a separate electrical circuit and have a control switch located immediately outside the machinery room door.

    1108.0 Refrigeration Machinery Room Equipment and Controls.

    1108.1 General. Equipment, piping, ducts, vents, or similar devices that are not essential for the refrigeration process, maintenance of the equipment, or for the illumination, ventilation, or fire protection of the room shall not be placed in or pass through a refrigeration machinery room.

    1108.2 Electrical. Electrical equipment and installations shall comply with California Electrical Code . The refrigeration machinery room shall not be classified as a hazardous location except as provided in Section 1107.1.7 or Section 1107.1.8.

    1108.3 Emergency Shutoff. A clearly identified emergency shutoff switch of the break-glass type or with an approved tamper-resistant cover shall be provided immediately adjacent to and outside of the principal refrigeration machinery room entrance. The switch shall provide off-only control of refrigerant compressors, refrigerant pumps, and normally-closed automatic refrigerant valves located in the machinery room. For other than A1 and B1 refrigerants, emergency shutoff shall be automatically activated by refrigerant Alarm 2 in accordance with Section 1106.2.5.

  • CMC § 1106.2.5 High relevance — show source text

    (1) Combustion air shall be ducted from outside the machinery room and sealed in such a manner as to prevent refrigerant leakage from entering the combustion chamber.

    (2) A refrigerant detector, that is in accordance with Section 1106.2.5, shall be installed to automatically shut down the combustion process in the event of refrigerant leak age.

    Exception: Machinery rooms where carbon dioxide (R-744) or water (R-718) is the refrigerant.

    1106.6 Ventilation Intake. Makeup air intakes to replace the exhaust air shall be provided to the refrigeration machinery room directly from outside the building. Intakes shall be located as required by other sections of the code and fitted with backdraft dampers or other approved flow-control means to prevent reverse flow. Distribution of makeup air shall be arranged to provide thorough mixing within the refrigeration machinery room to prevent short circuiting of the makeup air directly to the exhaust.

    234 2025 CALIFORNIA MECHANICAL CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    REFRIGERATION

    1106.11.6.1 Mechanical Ventilation. The machinery room shall have a mechanical ventilation system in accordance with Section 1106.11.11. The mechanical ventilation system shall:

    (1) Run continuously, and failure of the mechanical ventilation system actuates an alarm, or

    (2) Be activated by one or more refrigerant detectors, conforming to requirements of Section 1106.11.8. [ASHRAE 15:8.13.6.1] 1106.11.6.2 Detection System. Detection of refrigerant concentration that exceeds 25 percent of the LFL or the upper detection limit of the refrigerant detector, whichever is lower, shall automatically de-energize the following equipment in the machin ery room:

    (1) Refrigerant compressors

    (2) Refrigerant pumps

    (3) Normally closed automatic refrigerant valves

    (4) Other unclassified electrical sources of ignition with apparent power rating greater than 1 kVA, where the apparent power is the product of the circuit voltage and current rating. [ASHRAE 15:8.13.6.2] 1106.11.7 Mechanical Equipment Control. Remote control of the mechanical equipment in the refrigerating machinery room shall be provided immediately outside the machinery room door solely for the purpose of shutting down the equipment in an emergency. Ventilation fans shall be on a separate electrical circuit and have a control switch located immediately outside the machinery room door. [ASHRAE 15:8.13.7] 1106.11.8 Refrigerant Detectors. Each refrigerating machinery room in accordance with Section 1106.11 shall contain one or more refrigerant detectors in accordance with Section 1106.11.9. The detector(s) sensing element shall be located in areas where refrigerant from a leak will concentrate, with one or more set points that activate responses in accordance with Section 1106.11.10 for alarms and Section 1106.11.11 for mechanical ventilation. Multiport-type devices shall be prohibited. {ASHRAE 15:8.13.8} 1106.11.9 Refrigerant Detectors Requirements. Refrigerant detectors required by Section 1106.11 shall meet all of the following conditions:

  • CMC § 608.7 High relevance — show source text

    608.7 Testing of equipment. Refrigeration equipment and systems having a refrigerant circuit containing more than 220 pounds (100 kg) of Group A1 or 30 pounds (14 kg) of any other group refrigerant shall be subject to periodic testing in accordance with Section 608.7.1. Records of tests shall be maintained. Tests of emergency devices or systems required by this chapter shall be conducted by persons trained and qualified in refrigeration systems.

    6-10 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    BUILDING SERVICES AND SYSTEMS

    608.7.1 Periodic testing. The following emergency devices or systems shall be periodically tested in accordance with the manufacturer’s instructions and as required by the fire code official.

    1. Treatment and flaring systems.
    2. Valves and appurtenances necessary to the operation of emergency refrigeration control boxes.
    3. Fans and associated equipment intended to operate emergency ventilation systems.
    4. Detection and alarm systems.

    608.8 Emergency signs. Refrigeration units or systems having a refrigerant circuit containing more than 220 pounds (100 kg) of Group A1 or 30 pounds (14 kg) of any other group refrigerant shall be provided with approved emergency signs, charts and labels in accordance with NFPA 704. Hazard signs shall be in accordance with the California Mechanical Code for the classification of refrigerants listed therein.

    608.9 Refrigerant detection. Machinery rooms shall be provided with a refrigerant detector with an audible and visible alarm. Where ammonia is used as the refrigerant, detection shall comply with IIAR 2. For refrigerants other than ammonia, refrigerant detection shall comply with Section 608.9.1.

    608.9.1 Refrigerants other than ammonia. A detector, or a sampling tube that draws air to a detector, shall be provided at an approved location where refrigerant from a leak is expected to accumulate. The system shall be designed to initiate audible and visible alarms inside of and outside each entrance to the refrigerating machinery room and transmit a signal to an approved location where the concentration of refrigerant detected exceeds the lesser of the following:

    1. The corresponding TLV-TWA values shown in the California Mechanical Code for the refrigerant classification.
    2. Twenty-five percent of the lower flammable limit (LFL).

    Detection of a refrigerant concentration exceeding the upper detection limit or 25 percent of the lower flammable limit (LFL), whichever is lower, shall stop refrigerant equipment in the machinery room in accordance with Section 608.10.1.

    608.10 Remote controls. Where flammable refrigerants are used and compliance with Section 1106 of the California Mechanical Code is required, remote control of the mechanical equipment and appliances located in the machinery room as required by Sections 608.10.1 and 608.10.2 shall be provided at an approved location immediately outside the machinery room and adjacent to its principal entrance.

    608.10.1 Refrigeration system emergency shutoff. A clearly identified switch of the break-glass type or with an approved tamperresistant cover shall provide off-only control of refrigerant compressors, refrigerant pumps and normally closed automatic refrigerant valves located in the machinery room. Additionally, this equipment shall be automatically shut off when the refrigerant vapor concentration in the machinery room exceeds the vapor detector’s upper detection limit or 25 percent of the LEL, whichever is lower.

  • CMC § 1106.11.11.4 High relevance — show source text

    1106.11.11.4 Level 2 Ventilation Rate. When required by Section 1106.11.11.3, the total airflow for Level 2 ventilation shall be not less than the airflow rate determined by Figure 1106.11.11.4.

    [ASHRAE 15:8.13.11.4]

    1107.0 Machinery Room, Special Requirements.

    1107.1 General. In cases specified in the rules of Section 1106.1, a refrigeration machinery room shall comply with the special requirements in accordance with Section 1107.1.1 through Section 1107.1.10, in addition to Section 1106.2.

    236 2025 CALIFORNIA MECHANICAL CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    REFRIGERATION

    1107.1.1 Flame-Producing Devices. There shall be no flame-producing device or continuously operating hot surface over 800°F (427°C) permanently installed in the room.

    1107.1.2 Doors. Doors communicating with the building shall be approved, self-closing, tight-fitting fire doors.

    1107.1.3 Walls, Floors, and Ceilings. Walls, floor, and ceiling shall be tight and of noncombustible construction. Walls, floor, and ceiling separating the refrigeration machinery room from other occupied spaces shall be not less than one-hour fire-resistive construction.

    1107.1.4 Machinery Rooms. The refrigeration machinery room shall have a door that opens directly to the outdoors or through a vestibule equipped with selfclosing, tight-fitting doors. 1107.1.5 Exterior Openings. Exterior openings, where present, shall not be under a fire escape or an open stair way. 1107.1.6 Sealing. All pipes piercing the interior walls, ceiling, or floor of such rooms shall be tightly sealed to the walls, ceiling, or floor through which they pass. 1107.1.7 Group A2L and B2L Refrigerants. Where refrigerant of Groups A2L or B2L are used, the requirements of Class 1, Division 2, of the California Electrical Code, shall not apply to the machinery room provided that the conditions in Section 1107.1.7.1 through Section 1107.1.7.3 are met.

    1107.1.7.1 Mechanical Ventilation. The mechanical ventilation system in the machinery room is run continuously in accordance with Section 1106.11.6.1 and failure of the mechanical ventilation system actuates an alarm, or the mechanical ventilation system in the machinery room is activated by one or more refrigerant detectors, in accordance with the requirements of Section 1106.11.11.

    1107.1.7.2 Refrigeration Detectors. For the refrigerant detection required in Section 1106.2.5, detection of refrigerant concentration that exceeds 25 percent of the LFL or the upper detection limit of the refrigerant detector, whichever is lower, shall automatically de-energize the following equipment in the machinery room:

    (1) refrigerant compressors

    (2) refrigerant pumps

    (3) normally-closed automatic refrigerant valves

  • CMC § 8.13.6 High relevance — show source text

    [ASHRAE 15:8.13.6]

    »

    (1) Operated, where occupied, to supply not less than 0.5 CFM/ft [2] [2.54 L/(s•m [2] )] of machinery room area or 20 cubic feet per minute (9.44 L/s) per person.

    (2) Operable, where occupied at a volume required to not exceed the higher of a temperature rise of 18°F (10°C) above inlet air temperature or a maximum temperature of 122°F (50°C).

    1106.4 Natural Ventilation. When a refrigerating system is located outdoors more than 20 feet (6096 mm) from building openings and is enclosed by a penthouse, lean-to, or other open structure, natural or mechanical ventilation shall be provided. The requirements for such natural ventilation shall be in accordance with the following:

    (1) The free-aperture cross section for the ventilation of a machinery room shall be not less than as determined in accordance with Equation 1106.4.

    F = √ G (Equation 1106.4)

    Where:

    F = The free opening area, ft [2] (m [2] ).

    G = The mass of refrigerant in the largest system, any part of which is located in the machinery room, pounds.

    For SI units: 1 square foot = 0.0929 m [2], 1 pound = 0.453 kg

    (2) Locations of the gravity ventilation openings shall be based on the relative density of the refrigerant to air.

    [ASHRAE 15:8.14]

    1106.5 Combustion Air. No open flames that use combustion air from the machinery room shall be installed where refrigerant is used. Combustion equipment shall not be installed in the same machinery room with refrigerant-containing equipment except under one of the following conditions:

    (1) Combustion air shall be ducted from outside the machinery room and sealed in such a manner as to prevent refrigerant leakage from entering the combustion chamber.

    (2) A refrigerant detector, that is in accordance with Section 1106.2.5, shall be installed to automatically shut down the combustion process in the event of refrigerant leak age.

    Exception: Machinery rooms where carbon dioxide (R-744) or water (R-718) is the refrigerant.

    1106.6 Ventilation Intake. Makeup air intakes to replace the exhaust air shall be provided to the refrigeration machinery room directly from outside the building. Intakes shall be located as required by other sections of the code and fitted with backdraft dampers or other approved flow-control means to prevent reverse flow. Distribution of makeup air shall be arranged to provide thorough mixing within the refrigeration machinery room to prevent short circuiting of the makeup air directly to the exhaust.

    234 2025 CALIFORNIA MECHANICAL CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    REFRIGERATION

    1106.11.6.1 Mechanical Ventilation. The machinery room shall have a mechanical ventilation system in accordance with Section 1106.11.11. The mechanical ventilation system shall:

    (1) Run continuously, and failure of the mechanical ventilation system actuates an alarm, or

  • CMC § 1106.2.9 High relevance — show source text

    1106.2.9 Emergency Ventilation-Required Air- flow. An emergency ventilation system shall be required to exhaust an accumulation of refrigerant due to leaks or a rupture of the system. The emergency ventilation required shall be capable of removing air from the machinery room in not less than the airflow quantity in Section 1106.2.9.1. Where multiple refrigerants are present, then the highest airflow quantity shall apply.

    1106.2.9.1 Ventilation - A1, A2, A3, B1, B2 and B3 Refrigerants. The emergency ventilation for A1, A2, A3, B1, B2 and B3 refrigerants shall have the capacity to provide mechanical exhaust at a rate as determined in accordance with Equation 1106.2.9.1.

    Q = 100 G (Equation 1106.2.9.1)

    Where:

    Q = Air flow rate, CFM.

    G = Refrigerant mass in largest system, pounds.

    For SI units: 1 pound = 0.453 kg, 1 cubic foot per minute =

    0.0283 m [3] /min, 1 cubic foot per minute = 0.4719 L/s

    1106.3 Normal Operation. A part of the refrigeration machinery room mechanical ventilation shall be in accordance with the following:

    «

    «

    «

    «

    2025 CALIFORNIA MECHANICAL CODE 233

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    REFRIGERATION

    «

    «

    «

    «

    1106.7 Maximum Temperature. Ventilation or mechanical cooling systems shall be provided to maintain a temperature of not more than 104°F (40°C) in the refrigerant machinery room under design load and weather conditions. 1106.8 Refrigerant Parts in Air Duct. Joints and refrigerant-containing parts of a refrigerating system located in an air duct carrying conditioned air to and from an occupied space shall be constructed to withstand a temperature of 700°F (371°C) without leakage into the airstream. [ASHRAE 15:8.8]

    1106.9 Dimensions. Refrigeration machinery rooms shall be of such dimensions that system parts are readily accessible with approved space for maintenance and operations. An unobstructed walking space not less than 36 inches (914 mm) in width and 80 inches (2032 mm) in height shall be maintained throughout, allowing free access to not less than two sides of moving machinery and approaching each stop valve. Access to refrigeration machinery rooms shall be restricted to authorized personnel and posted with a permanent sign. 1106.10 Exits. Exits shall comply with the building code for special hazards. 1106.11 Machinery Room, A2L and B2L. When required by Section 1106.1, machinery rooms shall comply with Section 1106.11.1 through Section 1106.11.6. [ASHRAE 15:8.13]

  • CMC § 1106.11.1 High relevance — show source text

    1106.11.1 Flame-Producing Device. There shall be no flame-producing device or hot surface over 1290°F (700°C) in the room, other than that used for maintenance or repair, unless installed in accordance with Section 1106.5. [ASHRAE 15:8.13.1] 1106.11.2 Communicating Spaces. Doors communicating with the building shall be approved, self-closing, tight-fitting fire doors. [ASHRAE 15:8.13.2]

    1106.11.3 Noncombustible Construction. Walls, floor, and ceiling shall be tight and of noncombustible construction. Walls, floor, and ceiling separating the refrigerating machinery room from other occupied spaces shall be of at least one-hour fire-resistive construction. [ASHRAE 15:8.13.3] 1106.11.4 Exterior Openings. Exterior openings, if present, shall not be under any fire escape or any open stairway. [ASHRAE 15:8.13.4] 1106.11.5 Pipe Penetrations. All pipes piercing the interior walls, ceiling, or floor of such rooms shall be tightly sealed to the walls, ceiling, or floor through which they pass. [ASHRAE 15:8.13.5] 1106.11.6 Machinery Room Designation. When any refrigerant of Groups A2, A3, B2, or B3 are used, the machinery room shall be designated as Class I, Division 2 hazardous (classified) electrical location in accordance with NFPA 70. When the only flammable refrigerants used are from Group A2L or B2L, the machinery room shall comply with both Section 1106.11.6.1 for ventilation and Section 1106.11.6.2 for refrigerant detection, or shall be designated as Class I, Division 2 hazardous (classified) electrical location in accordance with NFPA 70.

    [ASHRAE 15:8.13.6]

    »

    (1) Operated, where occupied, to supply not less than 0.5 CFM/ft [2] [2.54 L/(s•m [2] )] of machinery room area or 20 cubic feet per minute (9.44 L/s) per person.

    (2) Operable, where occupied at a volume required to not exceed the higher of a temperature rise of 18°F (10°C) above inlet air temperature or a maximum temperature of 122°F (50°C).

    1106.4 Natural Ventilation. When a refrigerating system is located outdoors more than 20 feet (6096 mm) from building openings and is enclosed by a penthouse, lean-to, or other open structure, natural or mechanical ventilation shall be provided. The requirements for such natural ventilation shall be in accordance with the following:

    (1) The free-aperture cross section for the ventilation of a machinery room shall be not less than as determined in accordance with Equation 1106.4.

    F = √ G (Equation 1106.4)

    Where:

    F = The free opening area, ft [2] (m [2] ).

    G = The mass of refrigerant in the largest system, any part of which is located in the machinery room, pounds.

    For SI units: 1 square foot = 0.0929 m [2], 1 pound = 0.453 kg

  • CMC § 1106.2.6. High relevance — show source text

    (1) The space(s) containing the machinery is (are) separated from other occupancies by tight construction with tightfitting doors.

    (2) Access is restricted to authorized personnel.

    (3) Refrigerant detectors are installed with the sensing location and alarm level as required in refrigeration machinery rooms in accordance with Section 1106.2.6.

    (4) Open flames and surfaces exceeding 800°F (427°C) shall not be permitted where a Group A2, B2, A3, or B3 refrigerant, is used.

    (5) Electrical equipment that is in accordance with Class 1, Division 2, of NFPA 70 where the quantity of a Group A2, B2, A3, or B3 refrigerant in an independent circuit is capable of exceeding 25 percent of the lower flammability limit (LFL) upon release to the space based on the volume determined in accordance with Section 1104.2.1 through Section 1104.2.3.

    (6) Refrigerant containing parts in systems exceeding 100 horsepower (74.6 kW) compressor drive power, except evaporators used for refrigeration or dehumidification, condensers used for heating, control and pressure-relief valves for either, low-probability pumps, and connecting piping, are located in a machinery room or outdoors.

    [ASHRAE 15:7.2.2]

    1104.5 Flammable Refrigerants. The total of Group A2, B2, A3, and B3 refrigerants, other than Group A2L and B2L refrigerants shall not exceed 1100 pounds (498.9 kg) without approval by the Authority Having Jurisdiction. Institutional Occupancies shall comply with Section 1104.3. Machinery rooms required in accordance with Section 1106.0 based on flammability shall be constructed and maintained in accordance with Section 1106.2.1 through Section 1106.2.6 and Section 1106.11 for Group A2L and B2L refrigerants. 1104.6 Group A2L Refrigerants for Human Comfort. High-probability systems using Group A2L refrigerants for human comfort applications shall comply with this section.

    [ASHRAE 15:7.6]

    1104.6.1 Refrigerant Concentration Limits. Occupied spaces shall comply with the releasable charge limitations of the equipment listing and ASHRAE 15. Unoccupied spaces with refrigerant containing equipment, not including continuous piping or tubing, shall comply with the releasable charge limitations of the equipment listing or Section 1104.6.4. {ASHRAE 15:7.6.1-7.6.1.2}

    1104.6.2 Listing and Installation Requirements. Refrigeration systems shall be listed and shall be installed in accordance with listing, the manufacturer’s instructions, and any markings on the equipment restricting the installation. [ASHRAE 15:7.6.2]

    1104.6.2.1 Nameplate. The nameplate required by Section 1115.5 shall include a symbol indicating that a flammable refrigerant is used, as specified by the product listing. [ASHRAE 15:7.6.2.1]

    1104.6.2.2 Labeling. A label indicating a flammable refrigerant is used shall be placed adjacent to service ports and other locations where service involving components containing refrigerant is performed, as specified by the product listing.

  • CMC § 8.13.6.2 Medium relevance — show source text

    (1) Refrigerant compressors

    (2) Refrigerant pumps

    (3) Normally closed automatic refrigerant valves

    (4) Other unclassified electrical sources of ignition with apparent power rating greater than 1 kVA, where the apparent power is the product of the circuit voltage and current rating. [ASHRAE 15:8.13.6.2] 1106.11.7 Mechanical Equipment Control. Remote control of the mechanical equipment in the refrigerating machinery room shall be provided immediately outside the machinery room door solely for the purpose of shutting down the equipment in an emergency. Ventilation fans shall be on a separate electrical circuit and have a control switch located immediately outside the machinery room door. [ASHRAE 15:8.13.7] 1106.11.8 Refrigerant Detectors. Each refrigerating machinery room in accordance with Section 1106.11 shall contain one or more refrigerant detectors in accordance with Section 1106.11.9. The detector(s) sensing element shall be located in areas where refrigerant from a leak will concentrate, with one or more set points that activate responses in accordance with Section 1106.11.10 for alarms and Section 1106.11.11 for mechanical ventilation. Multiport-type devices shall be prohibited. {ASHRAE 15:8.13.8} 1106.11.9 Refrigerant Detectors Requirements. Refrigerant detectors required by Section 1106.11 shall meet all of the following conditions:

    (1) A refrigerant detector shall be capable of detecting each of the specific refrigerant designations in the machinery room.

    (2) The refrigerant detector shall activate responses within a time not to exceed a limit specified in Section 1106.11.10 and Section 1106.11.11 after exposure to refrigerant concentration exceeding a limit value specified in Section 1106.11.10 and Section 1106.11.11.

    (3) The refrigerant detector shall have a set point not greater than the applicable Occupational Exposure Limit (OEL) value in accordance with Table 1102.3. The applicable OEL value shall be the lowest OEL value for any refrigerant designation in the machinery room. For refrigerants that do not have an OEL value in Table 1102.3, use a value determined in accordance with the OEL as defined by ASHRAE 34 where approved by the Authority Having Jurisdiction.

    (4) The refrigerant detector shall have a set point not more than the applicable Refrigerant Concentration Limit (RCL) value in accordance with Table 1102.3. The applicable RCL value shall be the lowest RCL value for any refrigerant designation in the machinery room. For refrigerants that do not have a RCL value in Table 1102.3, use a value determined in accordance with the RCL as defined by ASHRAE 34 where approved by the Authority Having Jurisdiction.

    (5) The refrigerant detector shall provide a means for automatic self-testing and shall be in accordance with Section 1106.11.10.4. The refrigerant detector shall be tested during installation and annually thereafter in accordance with the fire code, or at an interval not exceeding the manufacturer’s installation instructions, whichever is less. Testing shall verify compliance with the alarm set points and response times per Section 1106.11.10 and Section 1106.11.11. [ASHRAE 15:8.13.9]

  • CMC § 53-9 Medium relevance — show source text

    2025 CALIFORNIA FIRE CODE 53-9

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    COMPRESSED GASES

    5307.4.3 Gas detection system. A gas detection system complying with Section 916 shall be provided in rooms or indoor areas in which the carbon dioxide enrichment process is located, in rooms or indoor areas in which container systems are located, and in other areas where carbon dioxide is expected to accumulate. Carbon dioxide sensors shall be provided within 12 inches (305 mm) of the floor in the area where the gas is expected to accumulate or leaks are most likely to occur. The system shall be designed as follows:

    1. Activates a low-level alarm upon detection of a carbon dioxide concentration of 5,000 ppm (9000 mg/m [3] ).
    2. Activates a high-level alarm upon detection of a carbon dioxide concentration of 30,000 ppm (54 000 mg/m [3] ).

    5307.4.3.1 System activation. Activation of the low-level gas detection system alarm shall automatically:

    1. Stop the flow of carbon dioxide to the piping system.
    2. Activate the mechanical exhaust ventilation system.
    3. Activate an audible and visible supervisory alarm signal at an approved location within the building.

    Activation of the high-level gas detection system alarm shall automatically:

    1. Stop the flow of carbon dioxide to the piping system.
    2. Activate the mechanical exhaust ventilation system.
    3. Activate an audible and visible evacuation alarm both inside and outside of the carbon dioxide enrichment area, and the area in which the carbon dioxide containers are located.

    5307.4.4 Pressurization and ventilation. Rooms or indoor areas in which carbon dioxide enrichment is provided shall be maintained at a negative pressure in relation to the surrounding areas in the building. A mechanical ventilation system shall be provided in accordance with the California Mechanical Code that complies with all of the following:

    1. Mechanical ventilation in the room or area shall be at a rate of not less than 1 cfm per square foot [0.00508 m [3] /(s × m [2] )].
    2. When activated by the gas detection system, the mechanical ventilation system shall remain on until manually reset.
    3. The exhaust system intakes shall be taken from points within 12 inches (305 mm) of the floor.
    4. The ventilation system shall discharge to the outdoors in an approved location.

    5307.4.5 Signage. Hazard identification signs shall be posted at the entrance to the room and indoor areas where the carbon dioxide enrichment process is located, and at the entrance to the room or indoor area where the carbon dioxide containers are located. The sign shall be not less than 8 inches (200 mm) in width and 6 inches (150 mm) in height and indicate:

    CAUTION—CARBON DIOXIDE GAS

    VENTILATE THE AREA BEFORE ENTERING. A HIGH CARBON DIOXIDE (CO 2 ) GAS CONCENTRATION

    IN THIS AREA

    CAN CAUSE ASPHYXIATION.

    5307.4.6 Seismic and structural design. Carbon dioxide system containers and piping shall comply with the seismic design requirements in Chapter 16 of the California Building Code and shall not exceed the floor loading limitation of the building.

    5307.4.7 Container refilling. Carbon dioxide containers located indoors shall not be refilled unless filled from a remote connection located outdoors.

    53-10 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

  • CMC § 1105.0 Medium relevance — show source text

    1105.0 General Requirements . . . . . . . . . 231

    1105.1 Human Comfort . . . . . . . . . . . . . . 231

    1105.2 Supports and Anchorage . . . . . . . 231

    1105.3 Access . . . . . . . . . . . . . . . . . . . . . 231

    1105.4 Illumination and Service

    Receptacles . . . . . . . . . . . . . . . . . 231

    1105.5 Ventilation of Rooms

    Containing Condensing Units . . . . 231

    1105.6 Prohibited Locations . . . . . . . . . . . 232

    1105.7 Condensate . . . . . . . . . . . . . . . . . 232

    1105.8 Defrost . . . . . . . . . . . . . . . . . . . . . 232

    1105.9 Overflows . . . . . . . . . . . . . . . . . . . 232

    1105.10 Condensate, Defrost, and Overflow Disposal. . . . . . . . . . . . . 232

    1105.11 Refrigerant Port Protection . . . . . . 232

    1105.12 Storage . . . . . . . . . . . . . . . . . . . . . 232

    1106.0 Refrigeration Machinery Rooms . . 232

    1106.1 Where Required . . . . . . . . . . . . . . 232

    1106.2 Refrigeration Machinery Room, General Requirements . . . . . . . . . 232

    1106.3 Normal Operation . . . . . . . . . . . . . 233

    1106.4 Natural Ventilation . . . . . . . . . . . . 234

    1106.5 Combustion Air . . . . . . . . . . . . . . . 234

    1106.6 Ventilation Intake . . . . . . . . . . . . . 234

    1106.7 Maximum Temperature . . . . . . . . 234

    1106.8 Refrigerant Parts in Air Duct. . . . . 234

    1106.9 Dimensions. . . . . . . . . . . . . . . . . . 234

    1106.10 Exits . . . . . . . . . . . . . . . . . . . . . . . 234

    1106.11 Machinery Room, A2L and B2L . . 234

    Table 1106.11.10.2 Refrigerant Detector Set Points, Response Times, Alarms, and Ventilation Levels . . . . . . . . . . . . . 235

    Table 1106.11.11.2 Level 1 Ventilation Rate for

    Class 2L Refrigerants . . . . . . . . . . . 236

    1107.0 Machinery Room, Special Requirements . . . . . . . . . . . . . . . . 236

    1107.1 General. . . . . . . . . . . . . . . . . . . . . 236

    1108.0 Refrigeration Machinery Room Equipment and Controls . . . . . . . . 237

    1108.1 General. . . . . . . . . . . . . . . . . . . . . 237

Frequently asked questions

When is a refrigeration machinery room required?

A machinery room is required where the rules in §1106.1 trigger it (for example, when refrigerant quantities, locations or types make enclosure necessary); see the CMC refrigeration chapter headings for the scope and thresholds in §1106.0 through §1108.0 .

What must refrigerant detectors do in a machinery room?

Detectors must be located where leaks concentrate, meet set‑point and response-time limits, provide self‑testing, initiate alarms per Table 1106.11.10.2, activate ventilation levels, and automatically de‑energize compressors/pumps and certain ignition sources when specified concentration limits are exceeded (see §1106.11.8–§1106.11.11 and §1106.11.9) file.

Do machinery rooms need mechanical ventilation to the outdoors?

Yes — machinery rooms must be vented to outdoors with mechanical exhaust and makeup arrangements that prevent short‑circuiting; emergency ventilation capacities are specified for different refrigerant groups (see §1106.11.11, §1106.6 and §1106.2.9) filefile.

More in California Mechanical Code

Ask about the CMC

Get cited, plain-English answers on the California Mechanical Code for your project — any code section, any scenario.

Start Free Trial

Related in the CMC