CMC · California Mechanical Code
Can the authority having jurisdiction require special inspectors or final reports?
Last reviewed: July 6, 2026
What the code requires — plain English (controlling §)
- The designated controlling section §1405.3 was not found in the uploaded California Mechanical Code material, so I cannot quote or ground requirements directly to §1405.3. I state that plainly here.
- Absent text for §1405.3, the applicable, retrievable rules are: the Authority Having Jurisdiction (AHJ) has broad administrative powers to require inspections, submittals and documentation under the Mechanical Code (see §103.1 and §103.3) and the California Building Code sets explicit rules for when special inspectors and written final reports are required and who they must be submitted to (see §1704.2.4).
The AHJ may require special inspectors and final reports where the AHJ determines they are necessary to verify code compliance — the Building Code’s special-inspection/report rules are the operative place to look for the required content and recipients of those reports.
(First occurrences: §1405.3, Authority Having Jurisdiction, special inspectors, final report are shown bold above.)
Requirements in detail
1) Can the AHJ require special inspectors?
- Yes. The Mechanical Code authorizes the AHJ to adopt rules, require plans and information and to appoint inspectors — that administrative authority supports requiring additional inspections where needed (see §103.1 and §103.3).
- The California Green Building Standards Code explicitly contemplates that the enforcing agency (AHJ) can require the owner to employ special inspectors when needed for compliance; it also addresses special-inspector qualifications and independence. See §702.2.
2) What about requiring written reports or a final report?
- The California Building Code requires approved agencies / special inspectors to keep records and to submit reports of special inspections and tests to the building official at frequencies required by the approved construction documents or the building official. A final report documenting the required special inspections/tests and correction of any discrepancies must be submitted at an agreed time prior to the start of work or as required by the building official. See §1704.2.4.
3) Who must receive the reports?
- Reports must be submitted to the building official (the AHJ’s representative) and to the registered design professional in responsible charge, per §1704.2.4. The AHJ may set frequency and timing.
4) Qualifications and independence
- Special inspectors must demonstrate competence acceptable to the enforcing agency; the Green Code lists example certifications and requires independence (no financial interest in the materials or the project). See §702.2.
Decision-relevant dimensions (quick reference)
| Decision question | Values / who does it | Required documentation | Code reference |
|---|---|---|---|
| May AHJ require special inspectors? | Yes, where AHJ deems necessary | Name/qualifications of inspector; statement of special inspections (where applicable) | §103.1, §103.3, §702.2 |
| Must special-inspection reports be filed? | Yes — periodic and final as required | Inspection/test reports describing nature/extent and conformance; final report documenting corrections | §1704.2.4 |
| Who receives reports? | Building official and registered design professional | Copies of inspection/test reports; final verified report | §1704.2.4 |
| Are special-inspector qualifications required? | Yes — competence acceptable to enforcing agency | Written documentation of competence, certifications as applicable | §1704.2.1, §702.2 |
| Exceptions (minor work) | AHJ may waive for minor work | AHJ-approved exceptions | §1704 exceptions |
(Where the Mechanical Code text for §1405.3 is unavailable in the provided files, the above is grounded in the Code sections that are present in the uploaded materials.)
Exceptions & special cases
- The Building Code provides exceptions to special-inspection requirements: the building official (AHJ) may determine special inspections are not required for work of a minor nature or for certain accessory Group U occupancies, among other exceptions. See the exceptions to Section 1704.
- The Green Code notes that qualifications and the precise triggers for special inspection are subject to the enforcing agency’s determination (so local adoption and checklists matter). See §702.2.
- Boiler/pressure‑vessel programs in the Mechanical Code delegate certain inspection/reporting regimes (operating permits, periodic inspections, and approved company inspectors under AHJ approval). For program-specific reporting/inspection steps see the boilers/pressure-vessel sections in the CMC (see the operating-permit and inspection subsections).
Note: I could not find §1405.3 text in the uploaded files; if §1405.3 contains more specific or different rules, please upload that page or allow me to look it up so I can cite it directly.
Common mistakes
- Assuming the AHJ can never require third‑party special inspectors. In fact, the AHJ can require them where necessary to verify compliance; the AHJ also sets qualifications and submission timing. See §103.1 and §1704.2.4.
- Treating “special inspection” as identical across codes — the Building Code (Chapter 17) is the primary rulebook for special inspections; CALGreen adds green-specific inspector expectations. Don’t rely solely on general Mechanical Code administration text. See §1704.2.4 and §702.2.
- Forgetting to send the final report to both the building official and the registered design professional — the Building Code requires both recipients. See §1704.2.4.
Worked example — concrete scenario
Scenario: A developer is installing a multi‑zone HVAC system that the AHJ determines affects life-safety smoke-control functions and asks for continuous special inspection and a final verified report.
- AHJ action: Cites administrative authority to require additional inspections and specifies that an approved special-inspection agency do continuous observation of the critical ductwork and smoke-control dampers. Authority for requiring inspections comes from §103.1 / §103.3 (AHJ powers).
- Owner responsibility: Owner hires an approved agency whose inspectors meet competence criteria. The owner submits the inspector qualifications to the AHJ before work starts (per special‑inspector qualification practice in §1704.2.1 and §702.2).
- Reporting frequency & content (example numbers): AHJ requires weekly written progress reports and daily verified logs for the smoke-control sequences during commissioning; the final report must be a verified document certifying that required inspections/tests were done, listing discrepancies and confirming corrections. These reporting requirements are consistent with the Building Code’s rule that approved agencies shall submit reports at frequencies required by the approved construction documents or building official and that a final report be submitted documenting required special inspections and corrections. See §1704.2.4.
- Outcome: The AHJ will not release the final approval/occupancy sign‑off until the final verified report is received and accepted by the building official. This requirement follows the report/final-report practice in §1704.2.4.
Related provisions — quick list
- California Mechanical Code: §103.1 — Duties and powers of the Authority Having Jurisdiction (administrative authority to require information/inspections).
- California Mechanical Code: §103.3 — Applications and permits; AHJ may require submission of plans, specifications and other information.
- California Mechanical Code (boilers): §1013.2 — Operating permits and that equipment must be inspected and approved by the AHJ before operation (see boiler/pressure-vessel inspection program).
- California Building Code: §1704.2.4 — Approved agencies shall keep records and submit reports of special inspections and tests; final report requirements.
- California Building Code: §1704.2.1 — Special inspector qualifications and required documentation to the building official.
- California Green Building Standards Code: §702.2 — Special inspection when required by enforcing agency; qualifications and independence of special inspectors.
If you want, I can:
- Search the uploaded CMC file(s) again specifically for §1405.3 and paste any text found (so we can ground the answer in that exact section), or
- Draft a model language that an AHJ could include in a mechanical permit condition to require special inspectors and a final verified report (aligned to the Building Code language). Which would you prefer?
Code references
Grounded in the retrieved California Mechanical Code — click a citation to read the verbatim passage:
CMC § 7-1 High relevance — show source text
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 7-1
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
7-2 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
7 INSTALLER AND SPECIAL INSPECTOR QUALIFICATIONS
SECTION 701—GENERAL (RESERVED)
SECTION 702—QUALIFICATIONS
702.1 Installer training. HVAC system installers shall be trained and certified in the proper installation of HVAC systems including ducts and equipment by a nationally or regionally recognized training or certification program. Uncertified persons may perform HVAC installations when under the direct supervision and responsibility of a person trained and certified to install HVAC systems or contractor licensed to install HVAC systems. Examples of acceptable HVAC training and certification programs include but are not limited to the following:
- State certified apprenticeship programs.
- Public utility training programs.
- Training programs sponsored by trade, labor or statewide energy consulting or verification organizations.
- Programs sponsored by manufacturing organizations.
- Other programs acceptable to the enforcing agency.
702.2 Special inspection.
[HCD] When required by the enforcing agency, the owner or the responsible entity acting as the owner’s agent shall employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition to other certifications or qualifications acceptable to the enforcing agency, the following certifications or education may be considered by the enforcing agency when evaluating the qualifications of a special inspector:
- Certification by a national or regional green building program or standard publisher.
- Certification by a statewide energy consulting or verification organization, building performance contractors and home energy auditors.
- Successful completion of a third party apprentice training program in the appropriate trade.
- Other programs acceptable to the enforcing agency.
Note: Special inspectors shall be independent entities with no financial interest in the materials or the project they are inspecting for compliance with this code.
[BSC-CG] When required by the enforcing agency, the owner or the responsible entity acting as the owner’s agent shall employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition, the special inspector shall have a certification from a recognized state, national or international association, as determined by the local agency. The area of certification shall be closely related to the primary job function, as determined by the local agency.
Note: Special inspectors shall be independent entities with no financial interest in the materials or the project they are inspecting for compliance with this code.
SECTION 703—VERIFICATIONS
703.1 Documentation. Documentation used to show compliance with this code shall include but is not limited to, construction documents, plans, specifications, builder or installer certification, inspection reports or other methods acceptable to the enforcing agency which demonstrate substantial conformance. When specific documentation or special inspection is necessary to verify compliance, that method of compliance will be specified in the appropriate section or identified in the application checklist.
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 7-3
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CMC § 1014.0 High relevance — show source text
Where subject to corrosion and construction permits, they shall be subject to inspection internally biennially.
Inspection of boilers and pressure vessels covered by insurance shall be permitted to be made by employees of the insuring company holding commissions from the National Board of Boiler and Pressure Vessel Inspectors, subject to approval of the Authority Having Jurisdiction. Approved insuring company inspectors shall make reports on prescribed forms on inspections authorized by the Authority Having Jurisdiction. The reports shall be filed in the Authority Having Jurisdiction office. Company inspectors shall notify the Authority Having Jurisdiction of suspension of insurance because of dangerous conditions, new insurance in effect, and discontinuance of insurance
coverage.
1014.0 Operation and Maintenance of Boilers and Pressure Vessels.
1014.1 General. Boilers and pressure vessels shall be operated and maintained in accordance with requirements for pro
tection of the public established by the Authority Having Jurisdiction in accordance with nationally recognized standards.
The Authority Having Jurisdiction shall notify the owner or authorized representative of defects or deficiencies and properly corrected. Where such corrections are not made, or where the operation of the boiler or pressure vessel is deemed unsafe by the Authority Having Jurisdiction, they shall have the authority to revoke the permit to operate the boiler or pressure vessel. Where the operation of a boiler or pressure vessel is deemed by the Authority Having Jurisdiction to constitute an immediate danger, the pressure on such boiler or pressure vessel shall be permitted to be relieved at the owner’s cost and the boiler or pressure vessel shall not thereafter be operated without the approval of the Authority Having Jurisdiction.
2025 CALIFORNIA MECHANICAL CODE 221
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
BOILERS AND PRESSURE VESSELS
CONTROL AND LIMIT DEVICE SYSTEM DESIGN11 Col2 Col3 Required Required Required Required Required Required Required Required Required Per NFPA 85 Per NFPA 85 APPROVED
FUEL SHUT-
OFF10APPROVED
FUEL SHUT-
OFF10APPROVED
FUEL SHUT-
OFF10Not
RequiredNot
RequiredRequired Required Not
RequiredNot
RequiredNot
RequiredRequired Not
RequiredPer
NFPA 85Per
NFPA 85STEAM
PRESSURE
AND LOW
WATER
LIMIT CON-
TROLS9STEAM
PRESSURE
AND LOW
WATER
LIMIT CON-
TROLS9STEAM
PRESSURE
AND LOW
WATER
LIMIT CON-
TROLS9Required Required Required Required Required Required Required Required Required Per
ASME
Power
Boiler
Code,CMC § 1.5 High relevance — show source text
R109.1.5 Other inspections. In addition to inspections in Sections R109.1.1 through R109.1.4.2, the building official shall have the authority to make or require any other inspections to ascertain compliance with this code and other laws enforced by the building official.
R109.1.5.1 Fire-resistance-rated construction inspection. Where fire-resistance-rated construction is required between dwelling units or due to location on property, the building official shall require an inspection of such construction after lathing or gypsum panel products are in place, but before any plaster is applied, or before panel joints and fasteners are taped and finished. Protection of joints and penetrations in fire-resistance-rated assemblies shall not be concealed from view until inspected and approved.
R109.1.5.2 Special inspections. For special inspections, see California Building Code, Chapter 17.
R109.1.5.3 Weather-exposed balcony and walking surface waterproofing. Where balconies or other elevated walking surfaces are exposed to water from direct or blowing rain, snow or irrigation, and the structural framing is protected by an impervious moisture barrier, all elements of the impervious moisture barrier system shall not be concealed until inspected and approved.
Exception: Where special inspections are provided in accordance with California Building Code Section 1705.1.1, Item 3.
R109.1.6 Final inspection. Final inspection shall be made after the permitted work is complete and prior to occupancy.
R109.1.6.1 Elevation documentation. If located in a flood hazard area, the documentation of elevations required in Section R306.1.10 shall be submitted to the building official prior to the final inspection.
R109.1.6.2 Operation and maintenance manual. At the time of final inspection, a manual, compact disc, web-based reference or other media acceptable to the enforcing agency shall be placed in the building in accordance with the California Green Building Standards Code, Chapter 4, Division 4.4.
R109.2 Inspection agencies. The building official is authorized to accept reports of approved agencies, provided such agencies satisfy the requirements as to qualifications and reliability.
R109.3 Inspection requests. It shall be the duty of the permit holder or their agent to notify the building official that such work is ready for inspection. It shall be the duty of the person requesting any inspections required by this code to provide access to and means for inspection of such work.
R109.4 Approval required. Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the building official. The building official, upon notification, shall make the requested inspections and shall either indicate the portion of the construction that is satisfactory as completed, or shall notify the permit holder or an agent of the permit
1-24 2025 CALIFORNIA RESIDENTIAL CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
DIVISION II SCOPE AND ADMINISTRATION
holder wherein the same fails to comply with this code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the building official.
SECTION R110—CERTIFICATE OF OCCUPANCY
CMC § 103.2 High relevance — show source text
In accordance with the prescribed procedures and with the approval of the appointing authority, the Authority Having Jurisdiction shall be permitted to appoint such number of technical officers, inspectors, and other employees as shall be authorized from time to time. The Authority Having Jurisdiction shall be permitted to deputize such inspectors or employees as necessary to carry out the functions of the code enforcement agency.
The Authority Having Jurisdiction shall be permitted to request the assistance and cooperation of other officials of this jurisdiction so far as required in the discharge of the duties required by this code or other pertinent law or ordi nance.
103.2 Liability. The Authority Having Jurisdiction charged with the enforcement of this code, acting in good faith and without malice in the discharge of the Authority Having Jurisdiction’s duties, shall not thereby be rendered personally liable for damage that accrues to persons or property as a result of an act or by reason of an act or omission in the discharge of such duties. A suit brought against the Authority Having Jurisdiction or employee because of such act or omission performed in the enforcement of provisions of this code shall be defended by legal counsel provided by this jurisdiction until final termination of such proceedings.
103.3 Applications and Permits. The Authority Having Jurisdiction shall be permitted to require the submission of plans, specifications, drawings, and such other information in accordance with the Authority Having Jurisdiction, prior to the commencement of, and at a time during the progress of, work regulated by this code.
The issuance of a permit upon construction documents shall not prevent the Authority Having Jurisdiction from thereafter requiring the correction of errors in said construction documents or from preventing construction operations being carried on thereunder where in violation of this code or of other pertinent ordinance or from revoking a certificate of approval where issued in error.
103.3.1 Licensing. Provision for licensing shall be determined by the Authority Having Jurisdiction. 103.4 Right of Entry. Where it is necessary to make an inspection to enforce the provisions of this code, or where the Authority Having Jurisdiction has reasonable cause to believe that there exists in a building or upon a premises a condition or violation of this code that makes the building or premises
unsafe, insanitary, dangerous, or hazardous, the Authority Having Jurisdiction shall be permitted to enter the building or premises at reasonable times to inspect or to perform the duties imposed upon the Authority Having Jurisdiction by this code, provided that where such building or premises is occupied, the Authority Having Jurisdiction shall present credentials to the occupant and request entry. Where such building or premises is unoccupied, the Authority Having Jurisdiction shall first make a reasonable effort to locate the owner or other person having charge or control of the building or premises and request entry. Where entry is refused, the Authority Having Jurisdiction has recourse to every remedy provided by law to secure entry.
Where the Authority Having Jurisdiction shall have first obtained an inspection warrant or other remedy provided by law to secure entry, no owner, occupant, or person having charge, care or control of a building or premises shall fail or neglect, after a request is made as herein provided, to promptly permit entry herein by the Authority Having Jurisdiction for the purpose of inspection and examination pursuant to this code.
104.0 Permits.
CMC § 2.5 High relevance — show source text
All reports shall describe the nature and extent of inspections and tests, the location where the inspections and tests were performed, and indicate that work inspected or tested was or was not completed in conformance to approved construction documents . Discrepancies shall be brought to the immediate attention of the contractor for correction. If they are not corrected, the discrepancies shall be brought to the attention of the building official and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and tests, and correction of any discrepancies noted in the inspections or tests, shall be submitted at a point in time agreed upon prior to the start of work by the owner or the owner’s authorized agent to the building official.
1704 A .2.5 Special inspection of fabricated items. Where fabrication of structural, load-bearing or lateral load-resisting members or assemblies is being conducted on the premises of a fabricator’s shop, special inspections of the fabricated items shall be performed during fabrication.
1704 A .2.5.1 Fabricator approval. Not permitted by DSA-SS, DSA-SS/CC or OSHPD.
1704 A .3 Statement of special inspections. Where special inspections or tests are required by Section 1705 A, the registered design professional in responsible charge shall prepare a statement of special inspections in accordance with Section 1704 A .3.1 for submittal by the applicant in accordance with Section 1704 A .2.3.
Exception: The statement of special inspections is permitted to be prepared by a qualified person approved by the building official for construction not designed by a registered design professional.
[DSA-SS, DSA-SS/CC] The exception is not permitted by DSA.
1704 A .3.1 Content of statement of special inspections. The statement of special inspections shall identify the following:
The materials, systems, components and work required to have special inspections or tests by the building official or by the registered design professional responsible for each portion of the work.
The type and extent of each special inspection.
The type and extent of each test.
Additional requirements for special inspections or tests for seismic or wind resistance as specified in Sections 1705 A .12, 1705 A .13 and 1705 A .14.
For each type of special inspection, identification as to whether it will be continuous special inspection, periodic special inspection or performed in accordance with the notation used in the referenced standard where the inspections are defined.
Deferred submittal items that require a supplemental statement of special inspections.
1704 A .3.2 Seismic requirements in the statement of special inspections. Where Section 1705 A .13 or 1705 A .14 specifies special inspections or tests for seismic resistance, the statement of special inspections shall identify the equipment/components that require special seismic certification and seismic force-resisting systems that are subject to the special inspections or tests.
1704 A .3.3 Wind requirements in the statement of special inspections. Where Section 1705 A .12 specifies special inspection for wind resistance, the statement of special inspections shall identify the main windforce-resisting systems and wind-resisting components that are subject to special inspections.
2025 CALIFORNIA BUILDING CODE 17A-5
CMC § 1704A.2.4. High relevance — show source text
If they are not corrected, the discrepancies shall be brought to the attention of the building official and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and tests, and correction of any discrepancies noted in the inspections or tests, shall be submitted at a point in time agreed upon prior to the start of work by the owner or the owner’s authorized agent to the building official. [OSHPD 1R, 2 & 5] Report requirement shall be per 1704A.2.4.
1704.2.5 Special inspection of fabricated items. Where fabrication of structural, load-bearing or lateral load-resisting members or assemblies is being conducted on the premises of a fabricator’s shop, special inspections of the fabricated items shall be performed during fabrication, except where the fabricator has been approved to perform work without special inspections in accordance with Section 1704.2.5.1.
1704.2.5.1 Fabricator approval. [OSHPD 1R, 2 & 5] Not permitted by OSHPD. Special inspections during fabrication are not required where the work is done on the premises of a fabricator approved to perform such work without special inspection. Approval shall be based on review of the fabricator’s written fabrication procedures and quality control manuals that provide a basis for control of materials and workmanship, with periodic auditing of fabrication and quality control practices by an approved agency or the building official. At completion of fabrication, the approved fabricator shall submit a certificate of compliance to the owner or the owner’s authorized agent for submittal to the building official as specified in Section 1704.5 stating that the work was performed in accordance with the approved construction documents.
1704.3 Statement of special inspections. Where special inspections or tests are required by Section 1705, the registered design professional in responsible charge shall prepare a statement of special inspections in accordance with Section 1704.3.1 for submittal by the applicant in accordance with Section 1704.2.3.
Exception: The statement of special inspections is permitted to be prepared by a qualified person approved by the building official for construction not designed by a registered design professional.
1704.3.1 Content of statement of special inspections. The statement of special inspections shall identify the following:
The materials, systems, components and work required to have special inspections or tests by the building official or by the registered design professional responsible for each portion of the work.
The type and extent of each special inspection.
The type and extent of each test.
Additional requirements for special inspections or tests for seismic or wind resistance as specified in Sections 1705.12, 1705.13 and 1705.14.
For each type of special inspection, identification as to whether it will be continuous special inspection, periodic special inspection or performed in accordance with the notation used in the referenced standard where the inspections are defined.
Deferred submittal items that require a supplemental statement of special inspections.
2025 CALIFORNIA BUILDING CODE 17-5
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
SPECIAL INSPECTIONS AND TESTS
CMC § 703.1 High relevance — show source text
Certification by a national or regional green building program or standard publisher. 2. Certification by a statewide energy consulting or verification organization, building performance contractors and home energy auditors. 3. Successful completion of a third party apprentice training program in the appropriate trade. 4. Other programs acceptable to the enforcing agency.
Note: Special inspectors shall be independent entities with no financial interest in the materials or the project they are inspecting for compliance with this code.
[BSC-CG] When required by the enforcing agency, the owner or the responsible entity acting as the owner’s agent shall employ one or more special inspectors to provide inspection or other duties necessary to substantiate compliance with this code. Special inspectors shall demonstrate competence to the satisfaction of the enforcing agency for the particular type of inspection or task to be performed. In addition, the special inspector shall have a certification from a recognized state, national or international association, as determined by the local agency. The area of certification shall be closely related to the primary job function, as determined by the local agency.
Note: Special inspectors shall be independent entities with no financial interest in the materials or the project they are inspecting for compliance with this code.
SECTION 703—VERIFICATIONS
703.1 Documentation. Documentation used to show compliance with this code shall include but is not limited to, construction documents, plans, specifications, builder or installer certification, inspection reports or other methods acceptable to the enforcing agency which demonstrate substantial conformance. When specific documentation or special inspection is necessary to verify compliance, that method of compliance will be specified in the appropriate section or identified in the application checklist.
2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 7-3
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
7-4 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CALIFORNIA GREEN BUILDING STANDARDS CODE – MATRIX ADOPTION TABLE
CHAPTER 8 – COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL
(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
Adopting agency BSC BSC-
CGSFM HCD Col6 Col7 DSA Col9 OSHPD Col11 Col12 Col13 Col14 Col15 BSCC DPH AGR DWR CEC CA SL SLC Adopting agency BSC BSC-
CGSFM 1 2 1/AC AC SS 1 1R 2 3 4 5 5 5 5 5 5 5 5 5 Adopt entire CA chapter X Adopt entire chapter as
amended (amended
sections listed below)Adopt only those sections
that are listedCMC § 312.1. Medium relevance — show source text
Exceptions:
- Special inspections and tests are not required for construction of a minor nature or as warranted by conditions in the jurisdiction as approved by the building official.
- Unless otherwise required by the building official, special inspections and tests are not required for Group U occupancies that are accessory to a residential occupancy including, but not limited to, those listed in Section 312.1.
- Special inspections and tests are not required for portions of structures designed and constructed in accordance with the cold-formed steel light-frame construction provisions of Section 2206.1.2 or the conventional light-frame construction provisions of Section 2308. [OSHPD 1R, 2 & 5] Not permitted by OSHPD.
17-4 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
SPECIAL INSPECTIONS AND TESTS
- The contractor is permitted to employ the approved agencies where the contractor is also the owner. [OSHPD 1R, 2 & 5] Not permitted by OSHPD. 5. [HCD 1] The provisions of Health and Safety Code Division 13, Part 6 and the California Code of Regulations, Title 25, Division 1, Chapter 3, commencing with Section 3000, shall apply to the construction and inspection of factory-built housing as defined in Health and Safety Code Section 19971.
1704.2.1 Special inspector qualifications. Prior to the start of the construction, the approved agencies shall provide written documentation to the building official demonstrating the competence and relevant experience or training of the special inspectors who will perform the special inspections and tests during construction. Experience or training shall be considered to be relevant where the documented experience or training is related in complexity to the same type of special inspection or testing activities for projects of similar complexity and material qualities. These qualifications are in addition to qualifications specified in other sections of this code.
The registered design professional in responsible charge and engineers of record involved in the design of the project are permitted to act as an approved agency and their personnel are permitted to act as special inspectors for the work designed by them, provided they qualify as special inspectors.
1704.2.2 Access for special inspection. The construction or work for which special inspection or testing is required shall remain accessible and exposed for special inspection or testing purposes until completion of the required special inspections or tests.
1704.2.3 Statement of special inspections. The applicant shall submit a statement of special inspections in accordance with Section 107.1 as a condition for permit issuance. This statement shall be in accordance with Section 1704.3.
Exception: A statement of special inspections is not required for portions of structures designed and constructed in accordance with the cold-formed steel light-frame construction provisions of Section 2206.1.2 or the conventional light-frame construction provisions of Section 2308. [OSHPD 1R, 2 & 5] Not permitted by OSHPD.
1704.2.4 Report requirement. Approved agencies shall keep records of special inspections and tests. The approved agency shall submit reports of special inspections and tests to the building official and to the registered design professional in responsible charge at frequencies required by the approved construction documents or building official. All reports shall describe the nature and extent of inspections and tests, the location where the inspections and tests were performed, and indicate that work inspected or tested was or was not completed in conformance to approved construction documents.
CMC § 1704.2.2 Medium relevance — show source text
The registered design professional in responsible charge and engineers of record involved in the design of the project are permitted to act as an approved agency and their personnel are permitted to act as special inspectors for the work designed by them, provided they qualify as special inspectors.
1704.2.2 Access for special inspection. The construction or work for which special inspection or testing is required shall remain accessible and exposed for special inspection or testing purposes until completion of the required special inspections or tests.
1704.2.3 Statement of special inspections. The applicant shall submit a statement of special inspections in accordance with Section 107.1 as a condition for permit issuance. This statement shall be in accordance with Section 1704.3.
Exception: A statement of special inspections is not required for portions of structures designed and constructed in accordance with the cold-formed steel light-frame construction provisions of Section 2206.1.2 or the conventional light-frame construction provisions of Section 2308. [OSHPD 1R, 2 & 5] Not permitted by OSHPD.
1704.2.4 Report requirement. Approved agencies shall keep records of special inspections and tests. The approved agency shall submit reports of special inspections and tests to the building official and to the registered design professional in responsible charge at frequencies required by the approved construction documents or building official. All reports shall describe the nature and extent of inspections and tests, the location where the inspections and tests were performed, and indicate that work inspected or tested was or was not completed in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If they are not corrected, the discrepancies shall be brought to the attention of the building official and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and tests, and correction of any discrepancies noted in the inspections or tests, shall be submitted at a point in time agreed upon prior to the start of work by the owner or the owner’s authorized agent to the building official. [OSHPD 1R, 2 & 5] Report requirement shall be per 1704A.2.4.
1704.2.5 Special inspection of fabricated items. Where fabrication of structural, load-bearing or lateral load-resisting members or assemblies is being conducted on the premises of a fabricator’s shop, special inspections of the fabricated items shall be performed during fabrication, except where the fabricator has been approved to perform work without special inspections in accordance with Section 1704.2.5.1.
1704.2.5.1 Fabricator approval. [OSHPD 1R, 2 & 5] Not permitted by OSHPD. Special inspections during fabrication are not required where the work is done on the premises of a fabricator approved to perform such work without special inspection. Approval shall be based on review of the fabricator’s written fabrication procedures and quality control manuals that provide a basis for control of materials and workmanship, with periodic auditing of fabrication and quality control practices by an approved agency or the building official. At completion of fabrication, the approved fabricator shall submit a certificate of compliance to the owner or the owner’s authorized agent for submittal to the building official as specified in Section 1704.5 stating that the work was performed in accordance with the approved construction documents.
CMC § 103.0 Medium relevance — show source text
103.0 Duties and Powers of the Authority Having Jurisdiction.
103.1 General. The Authority Having Jurisdiction shall be the Authority duly appointed to enforce this code. For such purposes, the Authority Having Jurisdiction shall have the powers of a law enforcement officer. The Authority Having Jurisdiction shall have the power to render interpretations of this code and to adopt and enforce rules and regulations supplemental to this code as deemed necessary in order to clarify the application of the provisions of this code. Such interpretations, rules, and regulations shall comply with the intent and purpose of this code.
In accordance with the prescribed procedures and with the approval of the appointing authority, the Authority Having Jurisdiction shall be permitted to appoint a such number of technical officers, inspectors, and other employees as shall be authorized from time to time. The Authority Having Jurisdiction shall be permitted to deputize such inspectors or employees as necessary to carry out the functions of the code enforcement agency.
The Authority Having Jurisdiction shall be permitted to request the assistance and cooperation of other officials of this jurisdiction so far as required in the discharge of the duties in accordance with this code or other pertinent law or ordinance.
103.2 Liability. The Authority Having Jurisdiction charged with the enforcement of this code, acting in good faith and without malice in the discharge of the Authority Having Jurisdiction’s duties, shall not thereby be rendered personally liable for damage that accrues to persons or property as a result of an act or by reason of an act or omission in the discharge of duties. A suit brought against the Authority Having Jurisdiction or employee because of such act or omission performed in the enforcement of provisions of this code shall be defended by legal counsel provided by this jurisdiction until final termination of such proceedings.
103.3 Applications and Permits. The Authority Having Jurisdiction shall be permitted to require the submission of plans, specifications, drawings, and such other information in accordance with the Authority Having Jurisdiction, prior to the commencement of, and at a time during the progress of, work regulated by this code.
The issuance of a permit upon construction documents shall not prevent the Authority Having Jurisdiction from thereafter requiring the correction of errors in said construction documents or from preventing construction operations being carried on thereunder where in violation of this code or of other pertinent ordinance or from revoking a certificate of approval where issued in error.
103.3.1 Licensing. Provision for licensing shall be determined by the Authority Having Jurisdiction. 103.4 Right of Entry. Where it is necessary to make an inspection to enforce the provisions of this code, or where the Authority Having Jurisdiction has reasonable cause to believe that there exists in a building or upon premises a condition or violation of this code that makes the building or premises unsafe, insanitary, dangerous, or hazardous, the Authority
Having Jurisdiction shall be permitted to enter the building or premises at reasonable times to inspect or to perform the duties imposed by the Authority Having Jurisdiction by this code, provided that where such building or premises is occupied, the Authority Having Jurisdiction shall present credentials to the occupant and request entry. Where such building or premises is unoccupied, the Authority Having Jurisdiction shall first make a reasonable effort to locate the owner or other person having charge or control of the building or premises and request entry. Where entry is refused, the Authority Having Jurisdiction has recourse to every remedy provided by law to secure entry.
CMC § 2.1 Medium relevance — show source text
1704 A .2.1 Special inspector qualifications. Prior to the start of the construction, the approved agencies shall provide written documentation to the building official demonstrating the competence and relevant experience or training of the special inspectors who will perform the special inspections and tests during construction. Experience or training shall be considered to be relevant where the documented experience or training is related in complexity to the same type of special inspection or testing activities for projects of similar complexity and material qualities. These qualifications are in addition to qualifications specified in other sections of this code.
The registered design professional in responsible charge and engineers of record involved in the design of the project are permitted to act as an approved agency and their personnel are permitted to act as special inspectors for the work designed by them, provided they qualify as special inspectors.
1704 A .2.2 Access for special inspection. The construction or work for which special inspection or testing is required shall remain accessible and exposed for special inspection or testing purposes until completion of the required special inspections or tests.
1704 A .2.3 Statement of special inspections. The applicant shall submit a statement of special inspections prepared by the regis- tered design professional in general responsible charge in accordance with Section 107.1 as a condition for construction documents review . This statement shall be in accordance with Section 1704 A .3.
[DSA-SS, DSA-SS/CC] Reference to Section 107.1 shall be to the California Administrative Code instead.
1704 A .2.4 Report requirement. The inspector(s) of record and approved agencies shall keep records of special inspections and tests. The inspector of record and approved agency shall submit reports of special inspections and tests to the building official and to the registered design professional in responsible charge at frequencies required by the approved construction documents or building official as required by the California Administrative Code . All reports shall describe the nature and extent of inspections and tests, the location where the inspections and tests were performed, and indicate that work inspected or tested was or was not completed in conformance to approved construction documents . Discrepancies shall be brought to the immediate attention of the contractor for correction. If they are not corrected, the discrepancies shall be brought to the attention of the building official and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and tests, and correction of any discrepancies noted in the inspections or tests, shall be submitted at a point in time agreed upon prior to the start of work by the owner or the owner’s authorized agent to the building official.
1704 A .2.5 Special inspection of fabricated items. Where fabrication of structural, load-bearing or lateral load-resisting members or assemblies is being conducted on the premises of a fabricator’s shop, special inspections of the fabricated items shall be performed during fabrication.
1704 A .2.5.1 Fabricator approval. Not permitted by DSA-SS, DSA-SS/CC or OSHPD.
1704 A .3 Statement of special inspections. Where special inspections or tests are required by Section 1705 A, the registered design professional in responsible charge shall prepare a statement of special inspections in accordance with Section 1704 A .3.1 for submittal by the applicant in accordance with Section 1704 A .2.3.
CMC § 1013.2 Medium relevance — show source text
Where the owner or his authorized representative requests inspection of a boiler prior to its installation, the Authority Having Jurisdiction shall make such inspection. 1013.2 Operating Permit. It shall be unlawful to operate a boiler or pressure vessel without first obtaining a valid operating permit to do so from the Authority Having Jurisdiction. Such permit shall be displayed in a conspicuous place adjacent to the boiler or vessel. The operating permit shall not be issued until the equipment has been inspected and approved by the Authority Having Jurisdiction.
Exception: The operation of steam-heating boilers, low-pressure hot-water-heating boilers, hot water supply boilers, and pressure vessels in residential occupancies of less than six dwelling units and utility occupancies. 1013.3 Maintenance Inspection. The Authority Having Jurisdiction shall inspect boilers and pressure vessels operated under a permit in accordance with ASHRAE/ACCA 180 at such intervals as deemed necessary, but not less frequently than in accordance with Section 1013.4 through Section 1013.7.
1013.4 Power and Miniature Boilers. Power boilers and miniature boilers shall be inspected externally annually. Where construction and operating conditions permit, they shall be subject to inspection internally annually. 1013.5 Steam-Heating and Water-Heating Boilers. Steam-heating boilers and hot-water-heating boilers shall be inspected externally annually. Where construction and operating conditions permit, they shall also be subject to inspection internally annually. 1013.6 Automatic Steam-Heating Boilers. Automatic steam-heating boilers shall be inspected externally biennially. Where construction and operating conditions permit, they shall be subject to inspection internally biennially. 1013.7 Unfired Pressure Vessels. Unfired pressure vessels shall be inspected externally biennially. Where subject to corrosion and construction permits, they shall be subject to inspection internally biennially.
Inspection of boilers and pressure vessels covered by insurance shall be permitted to be made by employees of the insuring company holding commissions from the National Board of Boiler and Pressure Vessel Inspectors, subject to approval of the Authority Having Jurisdiction. Approved insuring company inspectors shall make reports on prescribed forms on inspections authorized by the Authority Having Jurisdiction. The reports shall be filed in the Authority Having Jurisdiction office. Company inspectors shall notify the Authority Having Jurisdiction of suspension of insurance because of dangerous conditions, new insurance in effect, and discontinuance of insurance
coverage.
1014.0 Operation and Maintenance of Boilers and Pressure Vessels.
1014.1 General. Boilers and pressure vessels shall be operated and maintained in accordance with requirements for pro
tection of the public established by the Authority Having Jurisdiction in accordance with nationally recognized standards.
The Authority Having Jurisdiction shall notify the owner or authorized representative of defects or deficiencies and properly corrected. Where such corrections are not made, or where the operation of the boiler or pressure vessel is deemed unsafe by the Authority Having Jurisdiction, they shall have the authority to revoke the permit to operate the boiler or pressure vessel. Where the operation of a boiler or pressure vessel is deemed by the Authority Having Jurisdiction to constitute an immediate danger, the pressure on such boiler or pressure vessel shall be permitted to be relieved at the owner’s cost and the boiler or pressure vessel shall not thereafter be operated without the approval of the Authority Having Jurisdiction.
2025 CALIFORNIA MECHANICAL CODE 221
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
CMC § 1705.3.5 Medium relevance — show source text
The approved agency shall make a verified_ report identifying the members by mark and shall include such pertinent data as lot numbers of tendons used, tendon jack- ing forces, age and strength of concrete at time of tendon release and such other information that may be required. 3. The special inspector of prestressed members post-tensioned at the site shall check the condition of the prestressing tendons, anchorage assemblies and concrete in the area of the anchorage, the tensioning equipment and the tensioning procedure and prepare daily written reports. The approved agency shall make a verified report of the prestressing opera- tion identifying the members or tendons by mark and including such pertinent data as the initial cable slack, net elongation of tendons, jacking force developed and such other information as may be required. 4. The verified reports of construction shall show that of the special inspector’s own personal knowledge, the work covered by the report has been performed and materials used and installed in every material respect in compliance with the duly approved construction documents for plant fabrication inspection. The verified report shall be accompanied by test reports required for materials used. For site post-tensioning special inspections, the verified report shall be accompanied by copies of calibration charts, certified by an approved testing laboratory, showing the relationship between gage readings and force applied by the jacks used in the prestressing procedure
1705.3.5 Concrete pre-placement inspection. [OSHPD 1R, 2 & 5] Concrete shall not be placed until the forms and reinforcement have been inspected, all preparations for the placement have been completed, and the preparations have been checked by the Inspector of Record.
1705.3.6 Placing record. [OSHPD 1R, 2 & 5] A record shall be kept on the site of the time and date of placing the concrete in each portion of the structure. Such record shall be kept until the completion of the structure and shall be open to the inspection of the enforcement agency.
1705.3.7 Composite construction cores. [OSHPD 1R, 2 & 5] Composite construction cores shall be taken and tested in accordance with Section 1910A.4.
17-10 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
SPECIAL INSPECTIONS AND TESTS
1705.3.8 Special Inspections and tests for post-installed anchors in concrete. [OSHPD 1R, 2 & 5] Special inspections and tests for post-installed anchors in concrete shall be in accordance with Table 1705.3 and Section 1901.3.
1705.3.9 Shotcrete. [OSHPD 1R, 2 & 5] All shotcrete work shall be continuously inspected during placing by an approved agency. The shotcrete special inspector shall check the materials, placing equipment, details of construction and construction procedure. The approved agency shall furnish a verified report that of his or her own personal knowledge the work covered by the report has been performed and materials have been used and installed in every material respect in compliance with the duly approved construction documents.
CMC § 102.6 Medium relevance — show source text
102.6 Changes in Building Occupancy. Mechanical systems that are a part of a building or structure undergoing a change in use or occupancy, as defined in the building code, shall be in accordance with the requirements of this code that are applicable to the new use or occupancy. 102.7 Moved Structures. Parts of the mechanical system of a building and part thereof that is moved from one foundation to another, or from one location to another, shall be in accordance with the provisions of this code for new installations and completely tested as prescribed elsewhere in this section for new work, except that walls or floors need not be removed during such test where equivalent means of inspection acceptable to the Authority Having Jurisdiction are provided. 102.8 Appendices. The provisions in the appendices are intended to supplement the requirements of this code and shall not be considered part of this code unless formally adopted as such.
2025 CALIFORNIA MECHANICAL CODE 21
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
DIVISION II SCOPE AND ADMINISTRATION
103.0 Duties and Powers of the Authority Having Jurisdiction.
103.1 General. The Authority Having Jurisdiction shall be the Authority duly appointed to enforce this code. For such purposes, the Authority Having Jurisdiction shall have the powers of a law enforcement officer. The Authority Having Jurisdiction shall have the power to render interpretations of this code and to adopt and enforce rules and regulations supplemental to this code as deemed necessary in order to clarify the application of the provisions of this code. Such interpretations, rules, and regulations shall comply with the intent and purpose of this code.
In accordance with the prescribed procedures and with the approval of the appointing authority, the Authority Having Jurisdiction shall be permitted to appoint such number of technical officers, inspectors, and other employees as shall be authorized from time to time. The Authority Having Jurisdiction shall be permitted to deputize such inspectors or employees as necessary to carry out the functions of the code enforcement agency.
The Authority Having Jurisdiction shall be permitted to request the assistance and cooperation of other officials of this jurisdiction so far as required in the discharge of the duties required by this code or other pertinent law or ordi nance.
103.2 Liability. The Authority Having Jurisdiction charged with the enforcement of this code, acting in good faith and without malice in the discharge of the Authority Having Jurisdiction’s duties, shall not thereby be rendered personally liable for damage that accrues to persons or property as a result of an act or by reason of an act or omission in the discharge of such duties. A suit brought against the Authority Having Jurisdiction or employee because of such act or omission performed in the enforcement of provisions of this code shall be defended by legal counsel provided by this jurisdiction until final termination of such proceedings.
103.3 Applications and Permits. The Authority Having Jurisdiction shall be permitted to require the submission of plans, specifications, drawings, and such other information in accordance with the Authority Having Jurisdiction, prior to the commencement of, and at a time during the progress of, work regulated by this code.
The issuance of a permit upon construction documents shall not prevent the Authority Having Jurisdiction from thereafter requiring the correction of errors in said construction documents or from preventing construction operations being carried on thereunder where in violation of this code or of other pertinent ordinance or from revoking a certificate of approval where issued in error.
CMC § 102.5 Medium relevance — show source text
** Openings into a drainage or vent system, excepting those openings to which plumbing fixtures are properly connected or which constitute vent terminals, shall be permanently plugged or capped in an approved manner, using the appropriate materials in accordance with this code.
102.5 Health and Safety. Where compliance with the provisions of this code fails to eliminate or alleviate a nuisance, or other dangerous or insanitary condition that involves health or safety hazards, the owner or the owner’s agent shall install such additional plumbing and drainage facilities or shall make such repairs or alterations as ordered by the Authority Having Jurisdiction. 102.6 Changes in Building Occupancy. Plumbing systems that are a part of a building or structure undergoing a change in use or occupancy, as defined in the building code, shall be in accordance with the requirements of this code that are applicable to the new use or occupancy. 102.7 Moved Structures. Parts of the plumbing system of a building or part thereof that is moved from one foundation to another, or from one location to another, shall be in accordance with the provisions of this code for new installations and completely tested as prescribed elsewhere in this section for new work, except that walls or floors need not be removed during such test where other equivalent means of inspection acceptable to the Authority Having Jurisdiction are provided. 102.8 Appendices. The provisions in the appendices are intended to supplement the requirements of this code and shall not be considered part of this code unless formally adopted as such.
2025 CALIFORNIA PLUMBING CODE 21
), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.
DIVISION II SCOPE AND ADMINISTRATION
103.0 Duties and Powers of the Authority Having Jurisdiction.
103.1 General. The Authority Having Jurisdiction shall be the Authority duly appointed to enforce this code. For such purposes, the Authority Having Jurisdiction shall have the powers of a law enforcement officer. The Authority Having Jurisdiction shall have the power to render interpretations of this code and to adopt and enforce rules and regulations supplemental to this code as deemed necessary in order to clarify the application of the provisions of this code. Such interpretations, rules, and regulations shall comply with the intent and purpose of this code.
In accordance with the prescribed procedures and with the approval of the appointing authority, the Authority Having Jurisdiction shall be permitted to appoint a such number of technical officers, inspectors, and other employees as shall be authorized from time to time. The Authority Having Jurisdiction shall be permitted to deputize such inspectors or employees as necessary to carry out the functions of the code enforcement agency.
The Authority Having Jurisdiction shall be permitted to request the assistance and cooperation of other officials of this jurisdiction so far as required in the discharge of the duties in accordance with this code or other pertinent law or ordinance.
103.2 Liability. The Authority Having Jurisdiction charged with the enforcement of this code, acting in good faith and without malice in the discharge of the Authority Having Jurisdiction’s duties, shall not thereby be rendered personally liable for damage that accrues to persons or property as a result of an act or by reason of an act or omission in the discharge of duties. A suit brought against the Authority Having Jurisdiction or employee because of such act or omission performed in the enforcement of provisions of this code shall be defended by legal counsel provided by this jurisdiction until final termination of such proceedings.
More in California Mechanical Code
Ask about the CMC
Get cited, plain-English answers on the California Mechanical Code for your project — any code section, any scenario.
Start Free Trial