CMC · California Mechanical Code

What plumbing connection and backflow protections apply to mechanical equipment?

If mechanical equipment connects to potable water and can create backsiphonage or backpressure (pumps, boilers, chemical injection, water‑cooled equipment), the California Plumbing Code requires an approved backflow prevention method (air gap, vacuum breaker, double‑check, or reduced‑pressure assembly depending on the hazard). The uploaded California Mechanical Code files did not contain the exact text of **§ 312.0** or **§ 312.1**, so device selection and testing rules are cited from the CPC (**§ 602.0**, **§ 603.0** and subparts, Table 603.2) ; the Mechanical Code file shows Chapter 312 heading (fuel gas piping) but the specific sections requested were not available in the provided CMC files .

Last reviewed: July 6, 2026

What the code requires

Mechanical Code sections § 312.0 and § 312.1 requested by the user were not found in the uploaded California Mechanical Code (CMC) files (the Mechanical Code copy in the files shows the Chapter 312 heading for fuel gas piping but the specific text of § 312.0 / § 312.1 was not available) . Because the CMC text for those exact sections is not present in the provided files, I cannot quote or summarize those specific CMC paragraphs.

Where potable-water connections to mechanical equipment are concerned, the applicable requirements for backflow prevention are contained in the California Plumbing Code (CPC) — specifically the cross‑connection / backflow provisions in § 603.0 and its subparts and the unlawful‑connection rules in § 602.0. For example, the CPC requires cross‑connection control for any water‑operated equipment that can contaminate or cause backflow into the potable supply, and it lists device choices and application rules (air gap, AVB, PVB, DC, RP, etc.) in Chapter 6, Table 603.2 and sections § 603.3 / § 603.5 .

The single most important point: any mechanical equipment that can cause backsiphonage or backpressure to the potable system must be protected with an approved backflow prevention method — follow the CPC cross‑connection rules (Chapter 6) for the device selection and installation requirements (e.g., § 603.0, Table 603.2) .


Requirements in detail

Scope & applicability (what kinds of mechanical equipment)

  • Any equipment connected to the potable water supply that can contaminate or return water (used water, cooling water, chemical‑treated fluids, boiler water, etc.) is within cross‑connection control per § 602.0 and § 603.0 of the CPC .
  • The CPC explicitly calls out: water‑cooled equipment (compressors, degreasers, etc.), steam/hot water boilers, chemical injectors, and many equipment‑mounted inlets as requiring backflow protection (see § 603.5.8, § 603.5.10, § 603.5.6.3) .

Types of protection required — decision table

The code choice depends on the degree of hazard (pollution vs contamination) and on whether backpressure or backsiphonage is possible. Use Table 603.2 to select the device. Key practical rules are summarized below.

Equipment / situation Degree of hazard Typical required protection Code Reference
Water‑cooled compressors, chillers, degreasers Potential contamination or backpressure (depends on fluid) Backflow preventer suitable to degree of hazard (double check or reduced‑pressure where chemical/backpressure present) § 603.5.8, Table 603.2
Potable supply to steam/hot‑water boilers Often contamination if treatment chemicals present Double check assembly, RP (reduced‑pressure) or backflow preventer with intermediate vent + PRV; RP required when chemicals introduced
Irrigation / sprinklers with pumps or chemical injection Backpressure possible; chemicals Reduced‑pressure principle (RP) (mandatory with pumps/chemical injectors)
Tanks, vats, sumps, pool fill lines Backsiphonage risk Approved air gap or listed vacuum breaker or appropriate backflow assembly per Table 603.2
Hose‑end outlets on mechanical equipment Backsiphonage risk Non‑removable hose bibb backflow preventer, hose vacuum breaker, or AVB ≥ 6 in above usage point (critical level)

(For exact device selection, consult Table 603.2 in the CPC and the specific sub‑sections § 603.3§ 603.5 for device definitions and permitted uses) .

Installation & maintenance highlights

  • Devices must be approved by the Authority Having Jurisdiction and be tested to accepted standards; installations must follow the device listing instructions (§ 603.2, § 603.4) .
  • Backflow assemblies must be tested at installation and at least annually thereafter, or more often if the AHJ requires, by a certified tester (per CPC) .
  • Air‑gaps must meet the minimum distances in Table 603.3.1 (air‑gap sizing) and device‑mounted vacuum breakers must be installed at their listed critical level .

How to decide between DC (double check) and RP (reduced pressure)

  • Use RP (reduced‑pressure principle assembly) for high‑hazard contamination (toxic chemicals, health hazards) or systems capable of creating backpressure (pumps, chemical injectors) — the CPC requires RP in those cases (see § 603.5.6.1, § 603.5.6.3) .
  • Double check (DC) assemblies may be acceptable for lower‑hazard situations where there is no chemical injection and the hazard is pollution rather than contamination; check Table 603.2 for each application .

Exceptions & special cases

  • If the mechanical equipment discharges only to an open atmospheric receiver and cannot generate backpressure or draw return water, an air gap may be acceptable in lieu of a mechanical assembly; follow air gap sizing rules in Table 603.3.1 .
  • Where the plumbing code allows specific alternatives (equipment‑mounted, listed vacuum breakers, or special ASSE/IAPMO listed devices) use the device in accordance with its listing and manufacturer’s instructions (§ 603.5.13) .
  • For fire‑protection systems, special rules apply (hydraulic considerations, antifreeze/chemicals require RP) — see the CPC fire‑system cross‑connection subsections (§ 603.5.14 et seq.) .

If you need a CMC‑only quote for § 312.0 / § 312.1, I cannot provide it because those specific paragraphs were not present in the uploaded CMC files; the CMC file only shows the chapter heading for 312 (Fuel Gas Piping) in the available copy .


Common mistakes

  • Assuming mechanical code covers potable‑water backflow for equipment — in California the CPC (Plumbing Code) contains the cross‑connection/backflow rules that apply to water connections on mechanical equipment (see § 603.0) .
  • Installing the wrong device for the degree of hazard (e.g., installing a DC when chemicals or pumps require an RP) — check Table 603.2 and § 603.5 subitems before finalizing device selection .
  • Forgetting annual testing and certification requirements — assemblies must be tested at installation and at least annually by a certified tester (§ 603.2, testing requirements) .
  • Mounting a vacuum breaker at the wrong height — many vacuum breaker listings require a minimum critical level (for example, 1 in for some deck‑mounts, 6 in for others) — follow § 603.3.1 / § 603.5.13 and device listing .

Worked example

Scenario: A rooftop packaged chiller uses potable water for cooling condenser tubes. The chiller has a booster pump on the condenser water side and glycol may be introduced seasonally for freeze protection.

  1. Hazard analysis: Because a pump and chemical (glycol) are present, the system can create backpressure and introduces a chemical contamination hazard.
  2. Code requirement: The CPC requires protection where pumps or chemical injectors are present — RP (reduced‑pressure principle backflow prevention assembly) is required in this scenario per § 603.5.6.1 and § 603.5.6.3 (systems with pumps / chemical injectors) and Table 603.2 .
  3. Installation steps (high level):
    • Specify a listed RP assembly sized for the chiller inlet flow and the system pressures.
    • Install the RP on the potable supply to the chiller upstream of any shutoff valves in accordance with the manufacturer and CPC installation requirements (§ 603.4) .
    • Provide space for testing (isolation valves, test cocks) and arrange for the assembly to be tested at installation and annually by a certified tester (§ 603.2) .

Numeric illustration: if the chiller makes a nominal inlet demand of 50 gpm, select an RP rated above that flow and ensure pressure drop through the RP is accounted for in the chiller’s inlet pressure calculations (the CPC notes hydraulic effects must be considered where backflow devices are installed in fire or pressurized systems; similar prudence applies to mechanical service connections) .


Related provisions (CMC / CPC)

  • California Plumbing Code — § 602.0 (Unlawful connections / cross‑contamination) .
  • California Plumbing Code — § 603.0 (Cross‑connection control; device approval / Table 603.2) .
  • California Plumbing Code — § 603.3 through § 603.5 (Definitions of devices and application rules; equipment‑specific subsections such as § 603.5.8 for water‑cooled equipment and § 603.5.10 for boilers) .
  • California Mechanical Code — Chapter heading § 312 (Fuel gas piping) — available in the Mechanical Code file but the specific § 312.0 / § 312.1 text was not present in the uploaded Mechanical Code files; see chapter heading in the provided CMC file .
  • California Mechanical Code — refrigeration / machinery room provisions (example relevant CMC sections: § 1106.11 series for refrigerating machinery rooms) — mechanical code text present in uploaded files (useful when mechanical equipment contains refrigerants or special room conditions) .

Code references

Grounded in the retrieved California Mechanical Code — click a citation to read the verbatim passage:

  • CMC § 302.2 High relevance — show source text

    E 302.2 Water Service Outlet. Each manufactured home lot shall be provided with a water service outlet delivering potable water. The water service outlet riser shall be not less than [3] ⁄ 4 of an inch (20 mm) nominal pipe size and capable of delivering 12 water supply fixture units.

    E 302.2.1 Connection. A manufactured home shall be connected to the park water service outlet by a flexible connector, such as copper or copper alloy or other approved material not less than [3] ⁄ 4 of an inch nominal (20 mm) interior diameter.

    E 302.2.2 Water Supply Fixture Units. Park water distribution systems shall be designed to deliver a minimum of 12 water supply fixture units to each lot and installed with materials in accordance with Chapter 6, Appendix A, or both of this code.

    E 302.2.3 Pressure. Each manufactured home park water distribution system shall be so designed and maintained as to provide a pressure of not less than 20 poundsforce per square inch (psi) (138 kPa) at each manufactured home lot at maximum operating conditions.

    E 302.2.4 Location. Each lot water service outlet shall be located in the third rear section and within 4 feet (1219 mm) of the proposed location of the manufactured home.

    E 302.3 Shutoff Valve. A separate water shutoff valve shall be installed in each water service outlet at each manufactured home lot. Where a listed backflow protective device is installed, the service shutoff shall be located on the supply side of such device.

    E 302.4 Backflow Preventer. Where a condition exists in the plumbing of a manufactured home that creates a crossconnection, a listed backflow preventer shall be installed in the water service line to the manufactured home at or near the

    water service outlet. Where a hose bibb or outlet is installed on the supply outlet riser in addition to the service connector, a listed backflow preventer shall be installed on each additional outlet.

    E 302.5 Pressure-Relief Valve. Where it is required to install a backflow preventer at the manufactured home lot service outlet, a listed pressure-relief valve shall be installed in the water service line on the discharge side of the backflow preventer. Pressure-relief valves shall be set to release at a pressure at a maximum of 150 psi (1034 kPa). Pressurerelief valves shall discharge toward the ground. Backflow preventers and pressure-relief valves shall be not less than 12 inches (305 mm) above the ground.

    408 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    APPENDIX E

    E 302.6 Mechanical Protection. Park water service out lets, backflow preventers, and pressure-relief valves shall be protected from damage by vehicles or other causes. Such protection shall be permitted to consist of posts, fencing, or other permanent barriers.

    E 302.7 Water-Conditioning Equipment. A permit shall be obtained from the Authority Having Jurisdiction before installing water-conditioning equipment on a manufactured home lot. Approval of the park operator is required on applications for a permit to install such equipment. Where the water-conditioning equipment is of the regenerating type, and the park drainage system discharges into a public sewer, approval of the sanitary district or agency having jurisdiction over the public sewer is required.

  • CMC § 603.5.6.1 High relevance — show source text

    (1) Atmospheric vacuum breaker (AVB)

    (2) Pressure vacuum breaker backflow prevention assembly (PVB)

    (3) Spill-resistant pressure vacuum breaker (SVB)

    (4) Reduced-pressure principle backflow prevention assembly (RP)

    (5) A valve complying with IAPMO PS 72 603.5.6.1 Systems with Pumps. Where sprinkler and irrigation systems have pumps, connections for pumping equipment, or auxiliary air tanks, or are otherwise capable of creating backpressure, the potable water supply shall be protected by the following type of device where the backflow device is located upstream from the source of backpressure:

    (1) Reduced-pressure principle backflow prevention assembly (RP) 603.5.6.2 Systems with Backflow Devices. Where systems have a backflow device installed downstream from a potable water supply pump or a potable water supply pump connection, the device shall be one of the following:

    (1) Atmospheric vacuum breaker (AVB)

    (2) Pressure vacuum breaker backflow prevention assembly (PVB)

    (3) Spill-resistant pressure vacuum breaker (SVB)

    (4) Reduced-pressure principle backflow prevention assembly (RP) 603.5.6.3 Systems with Chemical Injectors. Where systems include a chemical injector or provisions for chemical injection, the potable water supply shall be protected by a reduced-pressure principle backflow prevention assembly (RP).

    2025 CALIFORNIA PLUMBING CODE 141

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    WATER SUPPLY AND DISTRIBUTION

    TABLE 603.2 BACKFLOW PREVENTION DEVICES, ASSEMBLIES, AND METHODS Col2 Col3 Col4 Col5 Col6 Col7
    DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD DEGREE OF HAZARD
    DEVICE, ASSEMBLY,
    OR METHOD1
    APPLICABLE
    STANDARDS
    POLLUTION
    (LOW HAZARD)
    POLLUTION
    (LOW HAZARD)
    CONTAMINATION
    (HIGH HAZARD)
    CONTAMINATION
    (HIGH HAZARD)
    INSTALLATION2,3
    DEVICE, ASSEMBLY,
    OR METHOD1
    APPLICABLE
    STANDARDS
    BACK-
    SIPHONAGE
    BACK-
    PRESSURE
    BACK-
    SIPHONAGE
    BACK-
    PRESSURE
    BACK-
    PRESSURE
    Air gap ASME
    A112.1.2
    X –– X –– See Table 603.3.1 in this chapter.
    Air gap fittings for use
    with plumbing fixtures,
    appliances, and appurte-
    nances
    ASME
    A112.1.3
    X –– X –– Air gap fitting is a device with an internal air
    gap, and typical installation includes
    plumbing fixtures, appliances,
  • CMC § 603.2 High relevance — show source text

    3, Table 603.2| |ASSE 1003-2020e2|Water Pressure Reducing Valves for Potable Water Distribution
    Systems|Valves|608.2| |ASSE 1004-2017|Commercial Dishwashing Machines|Backflow Protection|414.2| |ASSE 1008-2020|Plumbing Aspects of Residential Food Waste Disposer Units|Appliances|419.1| |ASSE 1010-2004|Water Hammer Arresters|Appliances|609.11| |ASSE 1011-2017|Hose Connection Vacuum Breakers|Backflow Protection|Table 603.2|

    2025 CALIFORNIA PLUMBING CODE 337

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    REFERENCED STANDARDS

    TABLE 1701.1 (continued) REFERENCED STANDARDS

    STANDARD NUMBER STANDARD TITLE APPLICATION REFERENCED
    SECTION
    ASSE 1012-2009 Backflow Preventers with an Intermediate Atmospheric Vent Backflow Protection Table 603.2
    ASSE 1013-2021 Reduced Pressure Principle Backflow Prevention Assemblies Backflow Protection Table 603.2
    ASSE 1014-2020 Backflow Prevention Devices for Hand-Held Showers Backflow Protection 417.3
    ASSE 1015-2021 Double Check Backflow Prevention Backflow Protection Table 603.2
    ASSE 1016-2017/ASME
    A112.1016-2017/CSA
    B125.16-2017
    Automatic Compensating Valves for Individual Showers and
    Tub/Shower Combinations
    Valves 408.4, 408.4.2(1)
    ASSE 1018-2001 (R2021) Trap Seal Primer Valves - Potable Water Supplied Valves 1007.2
    ASSE 1019-2011 (R2016) Wall Hydrant with Backflow Protection and Freeze Resistance Backflow Protection Table 603.2
    ASSE 1020-2020 Pressure Vacuum Breaker Assemblies Backflow Protection Table 603.2
    ASSE 1022-2021 Backflow Preventer for Beverage Dispensing Equipment Backflow Protection Table 603.2,
    603.5.12
    ASSE 1023-2020 Electrically Heated or Cooled Water Dispensers Appliances 417.6
    ASSE 1024-2017 (R2021) Dual Check Backflow Preventers Backflow Protection Table 603.2, 603.5.12
    ASSE 1032-2004 (R2021) Dual Check Valve Type Backflow Preventers for Carbonated
    Beverage Dispensers, Post Mix Type
    Backflow Protection 603.5.12
    ASSE 1035-2020 Laboratory Faucet Backflow Preventers Backflow Protection Table 603.2,
    603.3.11
    ASSE 1037-2020/ASME
    A112.1037-2020/CSA
    B125.37-2020
    Pressurized Flushing Devices for Plumbing Fixtures Backflow Protection 413.2
    ASSE 1044-2015 (R2020) Trap Seal Primer - Drainage Types and Electric Design Types DWV Components 1007.
  • CMC § 602.4 High relevance — show source text

    602.4 Approval by Authority. No water piping supplied by a private water supply system shall be connected to any other source of supply without the approval of the Authority Having Jurisdiction, Health Department, or other department having jurisdiction.

    603.0 Cross-Connection Control.

    603.1 General. Cross-connection control shall be provided in accordance with the provisions of this chapter.

    No person shall install a water-operated equipment or mechanism, or use a water-treating chemical or substance, where it is found that such equipment, mechanism, chemical, or substance causes pollution or contamination of the domestic water supply. Such equipment or mechanism shall be permitted where equipped with an approved backflow prevention device or assembly.

    603.2 Approval of Devices or Assemblies. Before a device or an assembly is installed for the prevention of backflow, it shall have first been approved by the Authority Having Jurisdiction. Devices or assemblies shall be tested in accordance with recognized standards or other standards acceptable to the Authority Having Jurisdiction. Backflow prevention devices and assemblies shall comply with Table 603.2, except for specific applications and provisions as stated in Section 603.5.1 through Section 603.5.22.

    2025 CALIFORNIA PLUMBING CODE 139

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    WATER SUPPLY AND DISTRIBUTION

    Devices or assemblies installed in a potable water supply system for protection against backflow shall be maintained in good working condition by the person or persons having control of such devices or assemblies. Such devices or assemblies shall be tested at the time of installation, repair, or relocation and not less than on an annual schedule thereafter, or more often where required by the Authority Having Jurisdiction. Where found to be defective or inoperative, the device or assembly shall be repaired or replaced. No device or assembly shall be removed from use or relocated or other device or assembly substituted, without the approval of the Authority Having Jurisdiction.

    Testing or maintenance shall be performed by a certified backflow assembly tester or repairer certified in accordance with ASSE/IAPMO/ANSI Series 5000 or any other additional certification approved by the Authority Having Jurisdiction.

    603.3 Backflow Prevention Devices, Assemblies, and Methods. Backflow prevention devices, assemblies, and methods shall comply with Section 603.3.1 through Section 603.3.12.

    603.3.1 Air Gap. The minimum air gap to afford backflow protection shall be in accordance with Table 603.3.1. 603.3.2 Atmospheric Vacuum Breaker (AVB). An atmospheric vacuum breaker consists of a body, a checking member, and an atmospheric port.

    603.3.3 Hose Connection Backflow Preventer. A hose connection backflow preventer consists of two independent check valves with an independent atmospheric vent between and a means of field testing and draining.

    603.3.4 Double Check Valve Backflow Prevention Assembly (DC). A double check valve backflow prevention assembly consists of two independently acting internally loaded check valves, four properly located test cocks, and two isolation valves.

    603.3.5 Pressure Vacuum Breaker Backflow Pre- vention Assembly (PVB). A pressure vacuum breaker backflow prevention assembly consists of a loaded air inlet valve, an internally loaded check valve, two properly located test cocks, and two isolation valves.

  • CMC § 603.5.2 High relevance — show source text

    603.5.2 Ballcock. Water closet and urinal tanks shall be equipped with a ballcock. The ballcock shall be installed with the critical level not less than 1 inch (25.4 mm) above the full opening of the overflow pipe. In cases where the ballcock has no hush tube, the bottom of the water supply inlet shall be installed 1 inch (25.4 mm) above the full opening of the overflow pipe.

    603.5.3 Backflow Prevention. Water closet flushometer tanks shall be protected against backflow by an approved backflow prevention assembly, device, or method.

    603.5.4 Heat Exchangers. Heat exchangers used for heat transfer, heat recovery, or solar heating shall protect the potable water system from being contaminated by the

    heat-transfer medium. Single-wall heat exchangers used in indirect-fired water heaters shall meet the requirements of Section 505.4.1. Double-wall heat exchangers shall separate the potable water from the heat-transfer medium by providing a space between the two walls that are vented to the atmosphere. 603.5.5 Water Supply Inlets. Water supply inlets to tanks, vats, sumps, swimming pools, and other receptors shall be protected by one of the following means:

    (1) An approved air gap.

    (2) A listed vacuum breaker installed on the discharge side of the last valve with the critical level not less than 6 inches (152 mm) or in accordance with its listing.

    (3) A backflow preventer suitable for the degree of hazard, installed in accordance with the requirements for that type of device or assembly as set forth in this chapter. 603.5.6 Protection from Lawn Sprinklers and Irri- gation Systems. Potable water supplies to systems having no pumps or connections for pumping equipment, and no chemical injection or provisions for chemical injection, shall be protected from backflow by one of the following devices:

    (1) Atmospheric vacuum breaker (AVB)

    (2) Pressure vacuum breaker backflow prevention assembly (PVB)

    (3) Spill-resistant pressure vacuum breaker (SVB)

    (4) Reduced-pressure principle backflow prevention assembly (RP)

    (5) A valve complying with IAPMO PS 72 603.5.6.1 Systems with Pumps. Where sprinkler and irrigation systems have pumps, connections for pumping equipment, or auxiliary air tanks, or are otherwise capable of creating backpressure, the potable water supply shall be protected by the following type of device where the backflow device is located upstream from the source of backpressure:

    (1) Reduced-pressure principle backflow prevention assembly (RP) 603.5.6.2 Systems with Backflow Devices. Where systems have a backflow device installed downstream from a potable water supply pump or a potable water supply pump connection, the device shall be one of the following:

    (1) Atmospheric vacuum breaker (AVB)

    (2) Pressure vacuum breaker backflow prevention assembly (PVB)

    (3) Spill-resistant pressure vacuum breaker (SVB)

    (4) Reduced-pressure principle backflow prevention assembly (RP) 603.5.6.3 Systems with Chemical Injectors. Where systems include a chemical injector or provisions for chemical injection, the potable water supply shall be protected by a reduced-pressure principle backflow prevention assembly (RP).

    2025 CALIFORNIA PLUMBING CODE 141

  • CMC § 602.0 High relevance — show source text

    602.0 Unlawful Connections.

    602.1 Prohibited Installation. No installation of potable water supply piping, or part thereof, shall be made in such a manner that it will be possible for used, unclean, polluted, or contaminated water, mixtures, or substances to enter a portion of such piping from a tank, receptor, equipment, or plumbing fixture by reason of backsiphonage, suction, or other cause, either during normal use and operation thereof, or where such tank, receptor, equipment, or plumbing fixture is flooded or subject to pressure exceeding the operating pressure in the hot or cold water piping. 602.2 Cross-Contamination. No person shall make a connection or allow one to exist between pipes or conduits carrying domestic water supplied by a public or private building supply system, and pipes, conduits, or fixtures containing or carrying water from any other source or containing or carrying water that has been used for any purpose whatsoever, or piping carrying chemicals, liquids, gases, or substances whatsoever, unless there is provided a backflow prevention device approved for the potential hazard and maintained in accordance with this code. Each point of use shall be separately protected where potential cross-contamination of individual units exists.

    602.3 Backflow Prevention. No plumbing fixture, device, or construction shall be installed or maintained, or shall be connected to a domestic water supply, where such installation or connection provides a possibility of polluting such water supply or cross-connection between a distributing system of water for drinking and domestic purposes and water that becomes contaminated by such plumbing fixture, device, or construction unless there is provided a backflow prevention device approved for the potential hazard.

    602.4 Approval by Authority. No water piping supplied by a private water supply system shall be connected to any other source of supply without the approval of the Authority Having Jurisdiction, Health Department, or other department having jurisdiction.

    603.0 Cross-Connection Control.

    603.1 General. Cross-connection control shall be provided in accordance with the provisions of this chapter.

    No person shall install a water-operated equipment or mechanism, or use a water-treating chemical or substance, where it is found that such equipment, mechanism, chemical, or substance causes pollution or contamination of the domestic water supply. Such equipment or mechanism shall be permitted where equipped with an approved backflow prevention device or assembly.

    603.2 Approval of Devices or Assemblies. Before a device or an assembly is installed for the prevention of backflow, it shall have first been approved by the Authority Having Jurisdiction. Devices or assemblies shall be tested in accordance with recognized standards or other standards acceptable to the Authority Having Jurisdiction. Backflow prevention devices and assemblies shall comply with Table 603.2, except for specific applications and provisions as stated in Section 603.5.1 through Section 603.5.22.

    2025 CALIFORNIA PLUMBING CODE 139

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    WATER SUPPLY AND DISTRIBUTION

  • CMC § 603.5.9 High relevance — show source text

    603.5.9 Aspirators. Water inlets to water-supplied aspirators shall be equipped with a vacuum breaker installed in accordance with its listing requirements and this chapter. The discharge shall drain through an air gap. Where the tailpiece of a fixture to receive the discharge of an aspirator is used, the air gap shall be located above the flood-level rim of the fixture.

    603.5.10 Steam or Hot Water Boilers. Potable water connections to steam or hot water boilers shall be protected from backflow by a double check valve backflow prevention assembly, backflow preventer with intermediate atmospheric vent and pressure reducing valve, or reduced pressure principle backflow prevention assembly in accordance with Table 603.2. Where chemicals are introduced into the system a reduced pressure principle backflow prevention assembly shall be provided in accordance with Table 603.2.

    603.5.11 Nonpotable Water Piping. In cases where it is impractical to correct individual cross-connections on the domestic waterline, the line supplying such outlets

    shall be considered a nonpotable water line. No drinking or domestic water outlets shall be connected to the nonpotable waterline. Where possible, portions of the nonpotable waterline shall be exposed, and exposed portions shall be properly identified in a manner satisfactory to the Authority Having Jurisdiction. Each outlet on the nonpotable waterline that is permitted to be used for drinking or domestic purposes shall be posted: “CAUTION: NONPOTABLE WATER, DO NOT DRINK.”

    [HCD 1 & HCD 2] An international symbol of a glass in a circle with a slash through it shall be provided sim- ilar to that shown in Figure 601.

    603.5.12 Beverage Dispensers. Potable water supply to carbonated beverage dispensers shall be protected by an air gap or a vented backflow preventer that complies with ASSE 1022. For carbonated beverage dispensers, piping material installed downstream of the backflow preventer shall not be affected by carbon dioxide gas. Non-carbonated beverage dispensers, such as ice makers and coffee machines, shall be protected by an air gap or dual check backflow preventer that comply with ASSE 1032 or ASSE 1024.

    603.5.13 Deck-Mounted and Equipment- Mounted Vacuum Breakers. Deck-mounted or equipment-mounted vacuum breakers shall be installed in accordance with their listing and the manufacturer’s installation instructions, with the critical level not less than 1 inch (25.4 mm) above the flood-level rim.

    603.5.14 Protection from Fire Systems.

    Note: Fire Protection Systems has not been adopted by the State Fire Marshal. This section cannot be adopted or enforced pursuant to California Health and Safety Code 13114.7(a), which is being cited for reference. California Health and Safety Code 13114.7.

    (a) For the purposes of this section the following are definitions of class I and class II systems:

    144 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    WATER SUPPLY AND DISTRIBUTION

  • CMC § 302.5 High relevance — show source text

    water service outlet. Where a hose bibb or outlet is installed on the supply outlet riser in addition to the service connector, a listed backflow preventer shall be installed on each additional outlet.

    E 302.5 Pressure-Relief Valve. Where it is required to install a backflow preventer at the manufactured home lot service outlet, a listed pressure-relief valve shall be installed in the water service line on the discharge side of the backflow preventer. Pressure-relief valves shall be set to release at a pressure at a maximum of 150 psi (1034 kPa). Pressurerelief valves shall discharge toward the ground. Backflow preventers and pressure-relief valves shall be not less than 12 inches (305 mm) above the ground.

    408 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    APPENDIX E

    E 302.6 Mechanical Protection. Park water service out lets, backflow preventers, and pressure-relief valves shall be protected from damage by vehicles or other causes. Such protection shall be permitted to consist of posts, fencing, or other permanent barriers.

    E 302.7 Water-Conditioning Equipment. A permit shall be obtained from the Authority Having Jurisdiction before installing water-conditioning equipment on a manufactured home lot. Approval of the park operator is required on applications for a permit to install such equipment. Where the water-conditioning equipment is of the regenerating type, and the park drainage system discharges into a public sewer, approval of the sanitary district or agency having jurisdiction over the public sewer is required.

    E 302.7.1 Approval. Regenerating water-conditioning equipment shall be listed and labeled by an approved listing agency.

    E 302.7.2 Installation. Regenerating units shall discharge the effluent of regeneration into a trap not less than 1 [1] ⁄ 2 inches (40 mm) in diameter connected to the manufactured home park drainage system. An approved air gap shall be installed on the discharge line a minimum of 12 inches (305 mm) above the ground.

    E 302.8 Testing. Installations shall be tested and inspected in accordance with Chapter 3 of this code.

    E 401.0 Fuel Supply.

    E 401.1 Fuel Gas Piping Systems. All fuel gas piping systems serving manufactured homes, accessory buildings, or structures and communities shall be designed and constructed in accordance with any applicable provisions of NFPA 54 and NFPA 58. NFPA 31 shall apply to oil fuel-burning systems and shall conform to the criteria of the Authority Having Jurisdiction. [NFPA 501A:4.1.1.1 – 4.1.1.2]

    E 401.2 Gas Supply Connections. Gas supply connections at sites, where provided from an underground gas supply piping system, shall be located and arranged to permit attachment to a manufactured home occupying the site.

    For the installation of liquefied petroleum gas (LP-Gas) storage systems, the provisions of NFPA 58 shall be followed. [NFPA 501A:4.1.2.1 – 4.1.2.2]

    E 401.3 Location of Gas Supply Connection. The gas supply to the manufactured home shall be located within 4 feet (1219 mm) of the manufactured home stand.

  • CMC § 25.4 High relevance — show source text

    2 Vertical walls, ribs, or similar obstructions extending from the water surface to or above the horizontal plane of the spout opening other than specified in Footnote 1 above. The effect of three or more such vertical walls or ribs has not been determined. In such cases, the air gap shall be measured from the top of the wall. 3 The effective opening shall be the minimum cross-sectional area at the seat of the control valve or the supply pipe or tubing that feeds the device or outlet. Where two or more lines supply one outlet, the effective opening shall be the sum of the cross-sectional areas of the individual supply lines or the area of the single outlet, whichever is smaller. 4 Air gaps less than 1 inch (25.4 mm) shall be approved as a permanent part of a listed assembly that has been tested under actual backflow conditions with vacuums of 0 to 25 inches of mercury (85 kPa).

    603.5.7 Outlets with Hose Attachments. Potable water outlets with hose attachments, other than water heater drains, boiler drains, and clothes washer connections, shall be protected by a nonremovable hose bibbtype backflow preventer, a nonremovable hose bibb-type vacuum breaker, or by an atmospheric vacuum breaker installed not less than 6 inches (152 mm) above the highest point of usage located on the discharge side of the last valve. In climates where freezing temperatures occur, a listed self-draining frost-proof hose bibb with an integral backflow preventer or vacuum breaker shall be used. 603.5.8 Water-Cooled Equipment. Water-cooled compressors, degreasers, or other water-cooled equipment shall be protected by a backflow preventer installed in accordance with the requirements of this chapter. Water-cooled equipment that produces backpressure shall be equipped with the appropriate protection. 603.5.9 Aspirators. Water inlets to water-supplied aspirators shall be equipped with a vacuum breaker installed in accordance with its listing requirements and this chapter. The discharge shall drain through an air gap. Where the tailpiece of a fixture to receive the discharge of an aspirator is used, the air gap shall be located above the flood-level rim of the fixture.

    603.5.10 Steam or Hot Water Boilers. Potable water connections to steam or hot water boilers shall be protected from backflow by a double check valve backflow prevention assembly, backflow preventer with intermediate atmospheric vent and pressure reducing valve, or reduced pressure principle backflow prevention assembly in accordance with Table 603.2. Where chemicals are introduced into the system a reduced pressure principle backflow prevention assembly shall be provided in accordance with Table 603.2.

    603.5.11 Nonpotable Water Piping. In cases where it is impractical to correct individual cross-connections on the domestic waterline, the line supplying such outlets

    shall be considered a nonpotable water line. No drinking or domestic water outlets shall be connected to the nonpotable waterline. Where possible, portions of the nonpotable waterline shall be exposed, and exposed portions shall be properly identified in a manner satisfactory to the Authority Having Jurisdiction. Each outlet on the nonpotable waterline that is permitted to be used for drinking or domestic purposes shall be posted: “CAUTION: NONPOTABLE WATER, DO NOT DRINK.”

    [HCD 1 & HCD 2] An international symbol of a glass in a circle with a slash through it shall be provided sim- ilar to that shown in Figure 601.

  • CMC § 601.8.1.1 High relevance — show source text

    601.8.1.1 Equipment using potable water shall be so installed as to prevent back-siphonage into the potable water system.

    601.8.1.2 Non-potable water is permitted only in those parts of o ffi cial plants where no edible product is han- dled or prepared, and then only for limited purposes, such as on ammonia condensers not connected with the potable water supply, in vapor lines serving inedi- ble product rendering tanks, in connection with equip- ment used for washing and washing inedible products preparatory to tanking, and in sewer lines for moving heavy solids in sewage. In all cases, non-potable water lines shall be clearly identi fi ed and shall not be cross connected with the potable water supply.

    Exception: Cross connection is permitted if this is necessary for fi re protection, and such connection is of a type with a break to ensure against accidental contamination, and is approved by local authorities or by the Department.

    601.8.2 All pipelines, reservoirs, tanks, cooling towers, and like equipment employed in handling reused water shall be constructed and installed so as to facilitate their cleaning and inspection.

    601.8.3 Hot water for cleaning rooms and equipment shall be delivered under pressure to outlets and shall be of such temperature as to accomplish a thorough cleanup.

    601.8.3.1 An ample supply of water at not less than 180°F (82°C) shall be available when used for san- itizing purposes.

    601.8.4 Pens, alleys, and runways shall have hose con- nections for cleanups purposes.

    602.0 Unlawful Connections.

    602.1 Prohibited Installation. No installation of potable water supply piping, or part thereof, shall be made in such a manner that it will be possible for used, unclean, polluted, or contaminated water, mixtures, or substances to enter a portion of such piping from a tank, receptor, equipment, or plumbing fixture by reason of backsiphonage, suction, or other cause, either during normal use and operation thereof, or where such tank, receptor, equipment, or plumbing fixture is flooded or subject to pressure exceeding the operating pressure in the hot or cold water piping. 602.2 Cross-Contamination. No person shall make a connection or allow one to exist between pipes or conduits carrying domestic water supplied by a public or private building supply system, and pipes, conduits, or fixtures containing or carrying water from any other source or containing or carrying water that has been used for any purpose whatsoever, or piping carrying chemicals, liquids, gases, or substances whatsoever, unless there is provided a backflow prevention device approved for the potential hazard and maintained in accordance with this code. Each point of use shall be separately protected where potential cross-contamination of individual units exists.

    602.3 Backflow Prevention. No plumbing fixture, device, or construction shall be installed or maintained, or shall be connected to a domestic water supply, where such installation or connection provides a possibility of polluting such water supply or cross-connection between a distributing system of water for drinking and domestic purposes and water that becomes contaminated by such plumbing fixture, device, or construction unless there is provided a backflow prevention device approved for the potential hazard.

  • CMC § 603.3 High relevance — show source text

    Testing or maintenance shall be performed by a certified backflow assembly tester or repairer certified in accordance with ASSE/IAPMO/ANSI Series 5000 or any other additional certification approved by the Authority Having Jurisdiction.

    603.3 Backflow Prevention Devices, Assemblies, and Methods. Backflow prevention devices, assemblies, and methods shall comply with Section 603.3.1 through Section 603.3.12.

    603.3.1 Air Gap. The minimum air gap to afford backflow protection shall be in accordance with Table 603.3.1. 603.3.2 Atmospheric Vacuum Breaker (AVB). An atmospheric vacuum breaker consists of a body, a checking member, and an atmospheric port.

    603.3.3 Hose Connection Backflow Preventer. A hose connection backflow preventer consists of two independent check valves with an independent atmospheric vent between and a means of field testing and draining.

    603.3.4 Double Check Valve Backflow Prevention Assembly (DC). A double check valve backflow prevention assembly consists of two independently acting internally loaded check valves, four properly located test cocks, and two isolation valves.

    603.3.5 Pressure Vacuum Breaker Backflow Pre- vention Assembly (PVB). A pressure vacuum breaker backflow prevention assembly consists of a loaded air inlet valve, an internally loaded check valve, two properly located test cocks, and two isolation valves. This device shall be permitted to be installed indoors where provisions for spillage are provided. 603.3.6 Spill-Resistant Pressure Vacuum Breaker (SVB). A pressure-type vacuum breaker backflow prevention assembly consists of one check valve force loaded closed and an air inlet vent valve force loaded open to atmosphere, positioned downstream of the check valve and located between and including two tightly closing shutoff valves and test cocks. 603.3.7 Reduced-Pressure Principle Backflow Prevention Assembly (RP). A reduced-pressure principle backflow prevention assembly consists of two independently acting internally loaded check valves, a differential pressure relief valve, four properly located test cocks, and two isolation valves.

    603.3.8 Double Check Detector Fire Protection Backflow Prevention Assembly. A double check valve backflow prevention assembly with a parallel

    detector assembly consisting of a water meter and a double check valve backflow prevention assembly (DC).

    603.3.9 Reduced Pressure Detector Fire Protec- tion Backflow Prevention Assembly. A reducedpressure principle backflow prevention assembly with a parallel detector assembly consisting of a water meter and a reduced-pressure principle backflow prevention assembly (RP).

    603.3.10 Dual Check Backflow Preventer. A dual check backflow preventer consists of two independently acting check valves, force loaded to a normally closed position.

    603.3.11 Laboratory Faucet Backflow Preven- ters. Laboratory faucet backflow preventers shall comply with ASSE 1035.

    603.3.12 Backflow Preventer with Intermediate Atmospheric Vent. A backflow preventer with intermediate atmospheric vent consists of two independently acting check valves, force loaded to a normally closed position, and an intermediate chamber with a means for automatically venting to atmosphere, force loaded to a normally open position. 603.4 General Requirements. Assemblies shall comply with listed standards and be acceptable to the Authority Having Jurisdiction, with jurisdiction over the selection and installation of backflow prevention assemblies.

    **603.4.1 Backflow Prevention Valve.

  • CMC § 5703.6.4 High relevance — show source text

    Exception: Vapor-recovery piping is allowed to be tested using an inert gas.

    5703.6.4 Protection from vehicles. Guard posts or other approved means shall be provided to protect piping, valves or fittings subject to vehicular damage in accordance with Section 312.

    5703.6.5 Protection from external corrosion and galvanic action. Where subject to external corrosion, piping, related fluidhandling components and supports for both underground and above-ground applications shall be fabricated from noncorrosive materials, and coated or provided with corrosion protection. Dissimilar metallic parts that promote galvanic action shall not be joined.

    5703.6.6 Valves. Piping systems shall contain a sufficient number of manual control valves and check valves to operate the system properly and to protect the plant under both normal and emergency conditions. Piping systems in connection with pumps shall contain a sufficient number of such valves to control properly the flow of liquids in normal operation and in the event of physical damage or fire exposure.

    5703.6.6.1 Backflow protections. Connections to pipelines or piping by which equipment (such as tank cars, tank vehicles or marine vessels) discharges liquids into storage tanks shall be provided with check valves or block valves for automatic protection against backflow where the piping arrangement is such that backflow from the system is possible. Where loading and unloading is done through a common pipe system, a check valve is not required. However, a block valve, located in an area where it is provided with ready access or remotely operable, shall be provided.

    5703.6.6.2 Manual drainage. Manual drainage-control valves shall be located at approved locations remote from the tanks, diked area, drainage system and impounding basin to ensure their operation in a fire condition.

    5703.6.7 Connections. Above-ground tanks with connections located below normal liquid level shall be provided with internal or external isolation valves located as close as practical to the shell of the tank. Except for liquids whose chemical characteristics are incompatible with steel, such valves, where external, and their connections to the tank shall be of steel.

    5703.6.8 Piping supports. Piping systems shall be substantially supported and protected against physical damage and excessive stresses arising from settlement, vibration, expansion, contraction or exposure to fire. The supports shall be protected against exposure to fire by one of the following:

    1. Draining liquid away from the piping system at a minimum slope of not less than 1 percent.
    2. Providing protection with a fire-resistance rating of not less than 2 hours.
    3. Other approved methods.

    5703.6.9 Flexible joints. Flexible joints shall be listed and approved and shall be installed on underground liquid, vapor and vent piping at all of the following locations:

    1. Where piping connects to underground tanks.
    2. Where piping ends at pump islands and vent risers.
    3. At points where differential movement in the piping can occur.

    5703.6.9.1 Fiberglass-reinforced plastic piping. Fiberglass-reinforced plastic (FRP) piping is not required to be provided with flexible joints in locations where both of the following conditions are present:

    1. Piping does not exceed 4 inches (102 mm) in diameter.
    2. Piping has a straight run of not less than 4 feet (1219 mm) on one side of the connection where such connections result in a change of direction.

    In lieu of the minimum 4-foot (1219 mm) straight run length, approved and listed flexible joints are allowed to be used under dispensers and suction pumps, at submerged pumps and tanks, and where vents extend above ground.

  • CMC § 603.5.14.2 High relevance — show source text

    (1) Reduced pressure principle backflow prevention assembly (RP)

    (2) Reduced pressure detector fire protection backflow prevention assembly

    Nonpotable water sources include fire department vehicles carrying water of questionable quality or water that is treated with antifreeze, corrosion inhibitors, or extinguishing agents. 603.5.14.2 Chemicals. Where antifreeze, corrosion inhibitors, or other chemicals are added to a fire protection system supplied from a potable water supply, the potable water system shall be protected by one of the following:

    (1) Reduced pressure principle backflow prevention assembly (RP)

    (2) Reduced pressure detector fire protection backflow prevention assembly 603.5.14.3 Hydraulic Design. Where a backflow device is installed in the potable water supply to a fire protection system, the hydraulic design of the system shall account for the pressure drop through the backflow device. Where such devices are retrofitted for an existing fire protection system, the hydraulics of the sprinkler system design shall be checked to verify that there will be sufficient water pressure available for satisfactory operation of the fire sprinklers. 603.5.15 Health Care or Laboratory Areas. Vacuum breakers for washer-hose bedpans shall be located not less than 5 feet (1524 mm) above the floor. Hose con

    nections in health care or laboratory areas shall be not less than 6 feet (1829 mm) above the floor. 603.5.16 Special Equipment. Portable cleaning equipment and dental vacuum pumps shall be protected from backflow by an air gap, an atmospheric vacuum breaker, a spill-resistant vacuum breaker, or a reduced pressure principle backflow preventer.

    603.5.17 Potable Water Outlets and Valves. Potable water outlets, freeze-proof yard hydrants, combination stop-and-waste valves, or other fixtures that incorporate a stop and waste feature that drains into the ground shall not be installed underground. 603.5.18 Pure Water Process Systems. The water supply to a pure water process system, such as dialysis water systems, semiconductor washing systems, and similar process piping systems, shall be protected from backpressure and backsiphonage by a reduced-pressure principle backflow preventer. 603.5.18.1 Dialysis Water Systems. The individual connections of the dialysis related equipment to the dialysis pure water system shall not require additional backflow protection. 603.5.19 Garbage Can Washers. Where garbage can washers are connected to a potable water supply system, the connection shall be protected against backflow in accordance with Table 603.2.

    603.5.20 Plumbing Fixture Fittings. Plumbing fixture fittings with integral backflow protection shall comply with ASME A112.18.1/CSA B125.1. 603.5.21 Swimming Pools, Spas, and Hot Tubs. Potable water supply to swimming pools, spas, and hot tubs shall be protected by an air gap or a reduced pressure principle backflow preventer in accordance with the following:

    (1) The unit is equipped with a submerged fill line.

    (2) The potable water supply is directly connected to the unit circulation system. 603.5.22 Chemical Dispensers. The water supply to chemical dispensers shall be protected against backflow by one of the following:

  • CMC § 1501.7 High relevance — show source text

    Residential,
    and Commercial Use|Water Quality|1501.7, 1506.8,
    1506.10.2, 1603.4| |IAPMO IGC 325-2016|Oil/Water Separators Performance|Interceptors|Table 1009.1| |IAPMO PS 53-2020|Grooved Mechanical Pipe Couplings and Grooved Fittings|Fittings|Table 604.1| |IAPMO PS 65-2019a|Airgap Units for Water Conditioning Equipment Installation|Backflow Protection|611.2| |IAPMO PS 66-2015|Dielectric Fittings|Fittings|605.15, 605.16.1,
    605.16.3| |IAPMO PS 72-2019|Valves with Atmospheric Vacuum Breakers|Valves|603.5.6(5)| |IAPMO PS 76-2021|Trap Primers for Fill Valves and Flushometer Valves|DWV Components|1007.2| |IAPMO PS 80-2019|Clarifiers|Interceptors|Table 1009.1| |IAPMO PS 90-2014|Elastomeric Test Caps, Cleanout Caps, and Combination Test
    Caps/Shielded Couplings|DWV Components|Table 707.2| |IAPMO PS 104-2019|Pressure Relief Connection for Dispensing Equipment|Valves|603.5.22(1)| |IAPMO PS 106-2015el|Tileable Shower Receptors and Shower Kits|Fixtures|408.2| |IAPMO PS 117-2021|Press Connections|Fittings|Table 604.1| |CSA B45.5-2017/IAPMO
    Z124-2017|Plastic Plumbing Fixtures (with Errata dated August 2017)|Fixtures|407.1, 408.1, 409.1,
    411.1, 412.1, 420.1| |IAPMO/ANSI Z124.5-
    2013e1 (R2018)|Plastic Toilet Seats|Appurtenance|411.3| |CSA B45.11-2017/IAPMO
    Z401-2017 (R2021)|Glass Plumbing Fixtures|Fixtures|407.1| |CSA B45.12-2013/IAPMO
    Z402-2013 (R2018)|Aluminum and Copper Plumbing Fixtures|Fixtures|407.1, 408.1, 409.1,
    420.1| |CSA B45.8-2018/IAPMO
    Z403-2018|Terrazzo, Concrete, Composite Stone, and Natural Stone
    Plumbing Fixtures|Fixtures|407.1, 420.1|

    348 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    REFERENCED STANDARDS

    TABLE 1701.1 (continued) REFERENCED STANDARDS

    STANDARD NUMBER STANDARD TITLE APPLICATION REFERENCED
    SECTION
    IAPMO/ANSI Z601-2018 Scale Reduction Devices Water Conditioning,
    Water Treatment
    611.1.2
    ANSI/CAN/IAPMO Z1001-
    2021
    Prefabricated Gravity Grease Interceptors Fixtures Table 1009.1, 1014.1,
  • CMC § 1503.1.1 High relevance — show source text

    (1) [HCD 1] The prohibition in Subsection (F) includes, but is not limited to, home photo labs or other similar hobbyist or home occupational activities.

    (2) [BSC-CG] Photo labs or similar activities.

    (G) Exemption from construction permit requirements of this code shall not be deemed to grant authorization for any

    gray water system to be installed in a manner that vio- lates other provisions of this code or any other laws or ordinances of the Enforcing Agency.

    (H) An operation and maintenance manual shall be provided to the owner. Directions shall indicate that the manual is to remain with the building throughout the life of the system and upon change of ownership or occupancy.

    (I) A gray water system shall not be connected to any potable water system without an air gap, reduced-pressure prin- ciple backflow preventer, or other physical device which prevents backflow and shall not cause ponding or runoff of gray water.

    1503.1.1 Clothes Washer System. [HCD 1] A clothes washer system in compliance with all of the fol- lowing is exempt from the construction permit specified in Section 1.8.4.1 and may be installed or altered with- out a construction permit:

    (1) If required, notification has been provided to the enforcing agency regarding the proposed location and installation of a gray water irrigation or dis- posal system.

    (2) The design shall allow the user to direct the flow to the irrigation or disposal field or the building sewer. The direction control of the gray water shall be clearly labeled and readily accessible to the user.

    (3) The installation, change, alteration, or repair of the system does not include a potable water connection or a pump and does not affect other building, plumb- ing, electrical, or mechanical components including structural features, egress, fire-life safety, sanitation, potable water supply piping, or accessibility.

    Note: The pump in a clothes washer shall not be considered part of the gray water system.

    (4) The gray water shall be contained on the site where it is generated.

    (5) Gray water shall be directed to and contained within an irrigation or disposal field.

    (6) Ponding or runoff is prohibited and shall be consid- ered a nuisance.

    (7) Gray water may be released above the ground sur- face provided at least two (2) inches (51 mm) of mulch, rock, or soil, or a solid shield covers the release point. Other methods which provide equiva- lent separation are also acceptable.

    (8) Gray water systems shall be designed to minimize contact with humans and domestic pets.

    (9) Water used to wash diapers or similarly soiled or infectious garments shall not be used and shall be diverted to the building sewer.

    (10)Gray water shall not contain hazardous chemicals derived from activities such as cleaning car parts, washing greasy or oily rags, or disposing of waste solutions from home photo labs or similar hobbyist or home occupational activities.

    312 2025 CALIFORNIA PLUMBING CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    ALTERNATE WATER SOURCES FOR NONPOTABLE APPLICATIONS

  • CMC § 1501.0 Medium relevance — show source text

    1501.0 General . . . . . . . . . . . . . . . . . . . . .309

    1501.1 Applicability . . . . . . . . . . . . . . . . . .309

    1501.2 System Design . . . . . . . . . . . . . . .309

    1501.3 Permit . . . . . . . . . . . . . . . . . . . . . .309

    1501.4 Component Identification . . . . . . .309

    1501.5 Maintenance and Inspection . . . .309

    1501.6 Operation and Maintenance Manual . . . . . . . . . . . . . . . . . . . . .309

    1501.7 Minimum Water Quality Requirements . . . . . . . . . . . . . . . .309

    Table 1501.5 Recommended Minimum Alternate Water Source Testing, Inspection, and Maintenance Frequency . . . . . . . . . . . . . . . . . . .310

    1501.8 Material Compatibility . . . . . . . . . .310

    1501.9 Signage . . . . . . . . . . . . . . . . . . . .310

    1501.10 System Controls . . . . . . . . . . . . . .310

    1502.0 Inspection and Testing . . . . . . . . .310

    1502.1 General . . . . . . . . . . . . . . . . . . . . .310

    1502.2 Supply System Inspection and Test . . . . . . . . . . . . . . . . . . . .310

    1502.3 Cross-Connection

    Inspection and Testing . . . . . . . . .310

    1502.4 Separation Requirements . . . . . . .311

    1502.5 Abandonment . . . . . . . . . . . . . . . .311

    1502.6 Sizing . . . . . . . . . . . . . . . . . . . . . .312

    1503.0 Gray Water Systems . . . . . . . . . .312

    1503.1 General . . . . . . . . . . . . . . . . . . . . .312

    1503.2 System Requirements . . . . . . . . .313

    1503.3 Connections to Potable and

    Reclaimed (Recycled) Water Systems . . . . . . . . . . . . . . . . . . . . .313

    1503.4 Location . . . . . . . . . . . . . . . . . . . .313

    1503.5 Plot Plan Submission . . . . . . . . . .313

    1503.6 Prohibited Location . . . . . . . . . . . .313

    Table 1503.4 Location of Gray Water System . . .314

    1503.7 Drawings and Specifications . . . .314

    1503.8 Procedure for Estimating Gray Water Discharge . . . . . . . . .314

    1503.9 Gray Water System Components . . . . . . . . . . . . . . . . .315

    1504.0 Subsurface Irrigation System Zones . . . . . . . . . . . . . . . .316

    1504.1 General . . . . . . . . . . . . . . . . . . . . .316

  • CMC § 1502.4 Medium relevance — show source text

    Inspection and Testing . . . . . . . . .310

    1502.4 Separation Requirements . . . . . . .311

    1502.5 Abandonment . . . . . . . . . . . . . . . .311

    1502.6 Sizing . . . . . . . . . . . . . . . . . . . . . .312

    1503.0 Gray Water Systems . . . . . . . . . .312

    1503.1 General . . . . . . . . . . . . . . . . . . . . .312

    1503.2 System Requirements . . . . . . . . .313

    1503.3 Connections to Potable and

    Reclaimed (Recycled) Water Systems . . . . . . . . . . . . . . . . . . . . .313

    1503.4 Location . . . . . . . . . . . . . . . . . . . .313

    1503.5 Plot Plan Submission . . . . . . . . . .313

    1503.6 Prohibited Location . . . . . . . . . . . .313

    Table 1503.4 Location of Gray Water System . . .314

    1503.7 Drawings and Specifications . . . .314

    1503.8 Procedure for Estimating Gray Water Discharge . . . . . . . . .314

    1503.9 Gray Water System Components . . . . . . . . . . . . . . . . .315

    1504.0 Subsurface Irrigation System Zones . . . . . . . . . . . . . . . .316

    1504.1 General . . . . . . . . . . . . . . . . . . . . .316

    1504.2 Required Area of Subsurface Irrigation Fields, Subsoil Irrigation Fields, and Mulch Basins . . . . . . . . . . . . . . . .316

    1504.3 Determination of Maximum

    Absorption Capacity . . . . . . . . . . .316

    Table 1504.2 Design of Six Typical Soils . . . . . .316

    1504.4 Groundwater Level . . . . . . . . . . . .316

    1504.5 Irrigation, Disposal Field and Mulch Basin Construction . . . . . .316

    Table 1504.5.3 Subsoil Irrigation Field Construction . . . . . . . . . . . . . . . . .318

    Table 1504.5.5 Subsurface Irrigation Design Criteria for Six Typical Soils . . . . .318

    1504.6 Reserved . . . . . . . . . . . . . . . . . . .318

    1504.7 Reserved . . . . . . . . . . . . . . . . . . .318

    1504.8 Gray Water System Color and Marking Information . . . . . . . .318

    1504.9 Other Collection and

    Distribution Systems . . . . . . . . . . .318

    1504.10 Testing . . . . . . . . . . . . . . . . . . . . .318

    1504.11 Maintenance . . . . . . . . . . . . . . . . .318

    1505.0 Recycled Water Supply Systems in Buildings . . . . . . . . . .318

  • California Mechanical Code Medium relevance — show source text

    RATING IN THOUSANDS OF BTU PER HOUR**|APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR| |HEIGHT
    H
    (feet)
    |LATERAL
    L
    (feet)
    |MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR|MAXIMUM APPLIANCE INPUT RATING IN THOUSANDS OF BTU PER HOUR| |6|0
    2
    5|39
    31
    28|70
    55
    51|116
    94
    88|170
    141
    128|232
    194
    177|312
    260
    242|500
    415
    390|750
    620
    600| |8|0
    2
    5
    10|42
    32
    29
    24|76
    61
    56
    49|126
    102
    95
    86|185
    154
    141
    131|252
    210
    194
    180|340
    284
    264
    250|542
    451
    430
    406|815
    680
    648
    625| |10|0
    2
    5
    10
    15|45
    35
    32
    27
    NA|84
    67
    61
    54
    46|138
    111
    104
    94
    84|202
    168
    153
    143
    130|279
    233
    215
    200
    186|372
    311
    289
    274
    258|606
    505
    480
    455
    432|912
    760
    724
    700
    666| |15|0
    2
    5
    10
    15
    20|49
    39
    35
    30
    NA
    NA|91
    72
    67
    58
    50
    NA|151
    122
    110
    103
    93
    82|223
    186
    170
    158
    144
    132|312
    260
    240
    223
    207
    195|420
    350
    325
    308
    291
    273|684
    570
    540
    514
    488
    466|1040
    865
    825
    795
    760
    726| |20|0
    2
    5

  • California Mechanical Code Medium relevance — show source text


    2
    5
    10
    15
    20
    30|184
    175
    215
    265
    312
    360
    461|1168
    823
    806
    777
    750
    723
    670|647
    533
    521
    501
    481
    461
    426|229
    219
    269
    327
    379
    433
    541|1542
    1069
    1049
    1017
    985
    955
    895|852
    698
    684
    662
    638
    615
    574|312
    296
    366
    440
    507
    570
    704|1971
    1346
    1324
    1287
    1251
    1216
    1147|1056
    863
    846
    821
    794
    768
    720|454
    424
    524
    620
    702
    780
    937|2996
    1999
    1971
    1927
    1884
    1841
    1759|1545
    1308
    1283
    1243
    1205
    1166
    1101| |50|0
    2
    5
    10
    15
    20
    30|176
    168
    204
    253
    299
    345
    442|1292
    971
    953
    923
    894
    866
    809|704
    613
    602
    583
    562
    543
    502|220
    209
    257
    313
    363
    415
    521|1724
    1273
    1252
    1217
    1183
    1150
    1086|948
    811
    795
    765
    736
    708
    649|295
    280
    347
    418
    481
    544
    674|2223
    1615
    1591
    1551
    1512
    1473
    1399|1189
    1007
    991
    963
    934
    906
    848|428
    401
    496
    589
    668
    741
    892|3432
    2426
    2396
    2347
    2299
    2251
    2159|1818
    1509
    1490
    1455
    1421
    1387
    1318| |100|0
    2
    5

  • CMC § 1220.4.2 Medium relevance — show source text

    8|1220.4.2 – 1220.4.6| |1221.7|1221.6| |1308.2 – 1308.4.1|1308.3 – 1308.5.1| |Table 1308.3.1|Table 1308.4.1| |1308.4.2|1308.5.2| |1308.4.2.2 – 1308.6.4|1308.5.2.1 – 1308.7.3| |Table 1308.4.6.2|Table 1308.5.6.2| |1308.6.5 – 1308.13.1|1308.7.7 – 1308.14.1| |1312.1.2 – 1312.1.3|1312.1.1 – 1312.1.2| |Chapter 17|Appendix F| |Chapter 18|Chapter 17| |D 103.2|D 103.1| |E 503.5.6.7|E 503.5.6.6| |E 503.5.7.2 – E 503.5.7.6|E 503.5.7.1 – E 503.5.7.5| |Table E 503.5.7.2|Table E 503.5.7.1| |Table E 503.5.7.6|Table E 503.5.7.5| |Table E 503.5.10.1.2(1)|Table E 503.5.10(1)| |Table E 503.5.10.1.2(2)|Table E 503.5.10(2)| |E 503.5.10.1.2|E 503.5.10| |E 503.5.10.2 – E 503.5.10.2.2|E 503.5.10.1 – E 503.5.10.1.2| |E 503.5.12.1|E 503.5.12| |E 503.5.12.2|E 503.5.12.1| |E 503.6.5.4|E 503.6.5.4.1|

    xxii 2025 CALIFORNIA MECHANICAL CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    RELATED PUBLICATIONS AND SERVICES

    The Documents Listed are Not by this Reference Adopted by The State of California.

    IAPMO provides a variety of other products which are useful for inspectors, building officials, architects, engineers,

    manufacturers, contractors, plumbers, and apprentices.

    IAPMO Headquarters Directory

    4755 East Philadelphia Street, Ontario, California 91761-2816

    Publication Order Desk Phone: 800-85-IAPMO

    Publication Toll Free Fax: 877-85-CODES

    E-mail: iapmo@iapmo.org

    Website: www.iapmo.org

    Free Code Question: 800-201-0335

    Uniform Mechanical Code – 2024 Edition:

    The Uniform Mechanical Code contains complete requirements for the installation and maintenance of heating, ventilating, cooking and refrigeration systems.

    Uniform Mechanical Code Illustrated Training Manual:

  • CMC § 2024 Medium relevance — show source text

    Important Notices and Disclaimers The 2024 edition of the Uniform Mechanical Code is developed through a consensus standards development process approved by the American National Standards Institute. This process brings together volunteers representing varied viewpoints and interests to achieve consensus on mechanical issues. While the International Association of Plumbing and Mechanical Officials (IAPMO) administers the process and establishes rules to promote fairness in the development of consensus, it does not independently test, evaluate, or verify the accuracy of any information or the soundness of any judgments contained in its codes

    and standards.

    IAPMO disclaims liability for any personal injury, property, or other damages of any nature whatsoever, whether special, indirect, consequential, or compensatory, directly or indirectly resulting from the publication, use of, or reliance on this document. IAPMO also makes no guarantee or warranty as to the accuracy or completeness of any information published

    herein.

    In issuing and making this document available, IAPMO is not undertaking to render professional or other services for or on behalf of any person or entity. Nor is IAPMO undertaking to perform any duty owed by any person or entity to someone else. Anyone using this document should rely on his or her own independent judgment or, as appropriate, seek the advice of a competent professional in determining the exercise of reasonable care in any given circumstances.

    Updating IAPMO Codes Users of IAPMO codes should be aware that IAPMO codes may be amended from time to time through the issuance of Tentative Interim Amendments or corrected by Errata. IAPMO codes consist of the current edition of the document together with any Tentative Interim Amendments and any Errata in effect.

    To access information for a specific code or to determine whether an IAPMO code has been amended through the issuance of Tentative Interim Amendments or corrected by Errata, please visit the IAPMO codes information page on the IAPMO’s website (https://www.iapmo.org/code-development). The codes information page provides a list of IAPMO codes with up-to-date specific information including any issued Tentative Interim

    Amendments and Errata.

    x 2025 CALIFORNIA MECHANICAL CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    FOREWORD

    Origin and Development The industry has long recognized the advantages of a statewide adopted mechanical code. The first edition of the Uniform Mechanical Code [®] (UMC [®] ) was adopted by IAPMO in 1967. The widespread use of this code over the past five decades by jurisdictions throughout the United States and internationally is testament to its merit.

    Publishing of the 2003 Uniform Mechanical Code was a significant milestone because it was the first time in the history of the United States a mechanical code was developed through a true consensus process. The 2024 edition represents the most current approaches in the mechanical field and is the eighth edition developed under the ANSI consensus process. Contributions to the content of this code consists of diverse interests as consumers, enforcing authorities, installers/maintainers, labor, manufacturers, research/standards/testing laboratories, special experts, and users.

  • CMC § 304.8 Medium relevance — show source text


    226
    206|342
    295
    263
    240|573
    498
    447
    409|664
    579
    520
    477|1130
    974
    870
    793|1320
    1140
    1020
    936|2340
    2030
    1820
    1660|2630
    2280
    2040
    1860|

    For SI units: 1 foot = 304.8 mm, 1 cubic foot per hour = 0.0283 m [3] /h, 1 pound-force per square inch = 6.8947 kPa, 1 inch water column = 0.249 kPa

    Notes: 1 Table entries are rounded to 3 significant digits. 2 Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, fittings, or both shall be increased by an equiv alent length of tubing to the following equation: L = 1.3 n, where L is additional length (ft) of tubing and n is the number of additional fittings, bends, or both . 3 EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the

    greater the gas capacity of the tubing.

    312 2025 CALIFORNIA MECHANICAL CODE

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

    FUEL GAS PIPING

    TABLE 1315.2(17) CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54: TABLE 6.2.1(r)]1, 2 Col2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 2, 3, 4 Col11 Col12 Col13 Col14 Col15
    GAS: GAS: GAS: ** NATURAL** ** NATURAL** ** NATURAL**
    INLET PRESSURE: INLET PRESSURE: INLET PRESSURE: ** 2.0 psi** ** 2.0 psi** ** 2.0 psi**
    PRESSURE DROP: PRESSURE DROP: PRESSURE DROP: ** 1.0 psi** ** 1.0 psi** ** 1.0 psi**
    SPECIFIC GRAVITY: SPECIFIC GRAVITY: SPECIFIC GRAVITY: ** 0.60** ** 0.60** ** 0.60**
    TUBE SIZE (EHD)5 TUBE SIZE (EHD)5 TUBE SIZE (EHD)5 **TUBE SIZE
  • California Mechanical Code Medium relevance — show source text


    5
    10
    15
    20|NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA|38
    35
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA|73
    67
    59
    NA
    NA|NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA|123
    115
    105
    95
    80|NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA|200
    183
    170
    156
    144|163
    NA
    NA
    NA
    NA|520
    NA
    NA
    NA
    NA|273
    252
    235
    217
    202| |30|2
    5
    10
    15
    20
    30|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|41
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|81
    75
    66
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|136
    127
    113
    105
    88
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|215
    196
    182
    168
    155
    NA|158
    NA
    NA
    NA
    NA
    NA|578
    NA
    NA
    NA
    NA
    NA|302
    279
    260
    240
    223
    182| |50|2
    5
    10
    15
    20
    30|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|91
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|160
    149
    136
    124
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|250
    228
    212
    195
    180
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|350
    321
    301
    278
    258
    NA| |Minimum
    internal area of
    chimney
    (square inches)|Minimum
    internal

  • CMC § 304.8 Medium relevance — show source text

    r>37
    35
    34|83
    79
    76
    73
    70|169
    161
    155
    148
    143|296
    282
    270
    260
    250|420
    400
    383
    368
    355|896
    855
    819
    787
    758|1610
    1540
    1470
    1420
    1360|2540
    2430
    2320
    2230
    2150|5300
    5050
    4840
    4650
    4480| |1600
    1700
    1800
    1900
    2000|1600
    1700
    1800
    1900
    2000|33
    32
    31
    30
    29|68
    66
    64
    62
    60|138
    134
    130
    126
    122|241
    234
    227
    220
    214|343
    331
    321
    312
    304|732
    708
    687
    667
    648|1320
    1270
    1240
    1200
    1170|2080
    2010
    1950
    1890
    1840|4330
    4190
    4060
    3940
    3830|

    For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.8947 kPa

    Notes: 1 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products. 2 Table entries are rounded to 3 significant digits.

    2025 CALIFORNIA MECHANICAL CODE 323

    ), Copyright © 2025 IAPMO, and may not be used for any other purpose or distributed to any other persons or parties.

Frequently asked questions

Do I follow the Mechanical Code or Plumbing Code for backflow on mechanical equipment?

You must follow the California Plumbing Code (CPC) cross‑connection rules for potable water connections and backflow prevention; the Mechanical Code may reference or rely on plumbing requirements but the CPC contains the specific backflow device selections and testing rules (see § 603.0 and related subsections) .

Is an air gap ever acceptable for mechanical equipment?

Yes — an approved air gap can be acceptable for many inlets (tanks, sumps, pools) where an open discharge prevents backflow. Air gaps must meet the minimum dimensions in the CPC (Table 603.3.1) or be part of a listed assembly .

When is a reduced‑pressure (RP) assembly mandatory?

When the system can create backpressure (pumps, booster pumps) or when chemicals or other high‑hazard contaminants can enter the water (chemical injectors, antifreeze), the CPC requires an RP (see § 603.5.6.1 and § 603.5.6.3) .

Who tests and maintains backflow assemblies?

Testing and maintenance must be performed by a certified backflow assembly tester/repairer; the CPC mandates testing at installation and at least annually (or more often if the AHJ requires) .

I need the exact text of CMC § 312.1 / § 312.0 — can you provide it?

I cannot provide or quote those CMC paragraphs because the uploaded CMC files did not include the specific text of § 312.0 or § 312.1; the available Mechanical Code copy shows the 312 chapter heading (fuel gas piping) but not the specific sections requested .

More in California Mechanical Code

Ask about the CMC

Get cited, plain-English answers on the California Mechanical Code for your project — any code section, any scenario.

Start Free Trial

Related in the CMC