CBC · California Building Code

Roof-covering types, installation rules, and fire classification

Chapter 15 of the CBC (and the Wildland‑Urban Interface Code) sets roof‑covering types, required installation practices, and Class A/B/C fire classifications with testing/listing and special rules for PV and WUI areas.

Last reviewed: July 5, 2026

Overview

This area of the California Building Code (CBC) is Chapter 15—Roof Assemblies and Rooftop Structures and the companion Wildland‑Urban Interface provisions. It covers roof‑covering classifications (Class A, B and C), material standards, product identification, installation requirements (underlayments, fasteners, manufacturer instructions) and special rules for photovoltaic and vegetative roofs; see Chapter 15 and its sections §1505–§1507 for the core requirements .

Fire classification and test standards are central: §1505 sets the minimum roof assembly classification by construction type (Table 1505.1) and requires listings and testing to ASTM E108 or UL 790 for Class A/B/C systems; Class definitions appear in §1505.2–§1505.4 . Photovoltaic roof coverings and BIPV products must be tested and labeled for fire classification (UL 2703 for PV; BIPV requirements referenced in Chapter 15 and the Residential Code) .

Installation and product controls are in §§1506–1507: roof‑covering materials must bear manufacturer/test labels, be applied per the listing and the manufacturer’s instructions, and use specified underlayment/fastening patterns for each covering type; detailed installation rules (for underlayment, cap sheets, mechanical fasteners, etc.) are provided in §1507 and related tables . Where the property is in a Fire Hazard Severity Zone or WUI, more stringent Class A and ignition‑resistant construction provisions apply under the Wildland‑Urban Interface Code (see Section 504 and §1505.1.1) .

In this section

Code references

Grounded in the retrieved California Building Code — click a citation to read the verbatim passage:

  • CBC § 1505.7. High relevance — show source text

    Buildings that are not more than two stories above grade plane and having not more than 6,000 square feet of projected roof area and where there is a minimum 10-foot fire-
    separation distance from the leading edge of the roof to a lot line on all sides of the building, except for street fronts or public ways, shall be permitted to have roofs of No. 1
    cedar or redwood shakes and No. 1 shingles constructed in accordance with Section 1505.7.|For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2.
    a. Unless otherwise required in accordance with the_California Wildland-Urban Interface Code_ or due to the location of the building within a fire district in accordance with
    Appendix D.
    b. Nonclassified roof coverings shall be permitted on buildings of Group U occupancies, where there is a minimum fire-separation distance of 6 feet measured from the leading
    edge of the roof.
    c. Buildings that are not more than two stories above grade plane and having not more than 6,000 square feet of projected roof area and where there is a minimum 10-foot fire-
    separation distance from the leading edge of the roof to a lot line on all sides of the building, except for street fronts or public ways, shall be permitted to have roofs of No. 1
    cedar or redwood shakes and No. 1 shingles constructed in accordance with Section 1505.7.|

    2025 CALIFORNIA BUILDING CODE 15-5

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    ROOF ASSEMBLIES AND ROOFTOP STRUCTURES

    1505.1.1 Roofing requirements within Fire Hazard Severity Zones or in the Wildland-Urban Interface (WUI). Roofing require- ments for structures located within Fire Hazard Severity Zones or in the Wildland-Urban Interface (WUI) shall also comply with Section 705A.

    1505.1.2 Roof coverings within all other areas other than Fire Hazard Severity Zones or a Wildland-Urban Interface (WUI). The entire roof covering of every existing structure where more than 50 percent of the total roof area is replaced within any one-year period, the entire roof covering of every new structure, and any roof covering applied in the alteration, repair or replacement of the roof of every existing structure, shall be a fire-retardant roof covering that is at least Class C fire classification.

    [BF] 1505.2 Class A roof assemblies. Class A roof assemblies are those that are effective against severe fire test exposure. Class A roof assemblies and roof coverings shall be listed and identified as Class A by an approved testing agency. Class A roof assemblies shall be permitted for use in buildings or structures of all types of construction.

    Exceptions:

    1. Class A roof assemblies include those with coverings of brick, masonry or an exposed concrete roof deck.
    2. Class A roof assemblies also include ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile or slate installed on noncombustible decks or ferrous, copper or metal sheets installed without a roof deck on noncombustible framing.
    3. Class A roof assemblies include minimum 16 ounce per square foot (0.0416 kg/m [2] ) copper sheets installed over combustible decks.
  • CBC § 4.882 High relevance — show source text

    Chapter 9 also provides requirements for roof drainage, flashing, above-deck thermal insulation, rooftop-mounted photovoltaic systems and recovering or replacing an existing roof covering.

    SECTION R901—GENERAL

    R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies.

    SECTION R902—FIRE CLASSIFICATION

    R902.1 Roof assemblies. Roof decks shall be covered with materials as set forth in Section R904 or with roof coverings as set forth in Section R905. A minimum Class A, B or C roofing shall be installed in areas designated by this section or where the edge of the roof deck is less than 3 feet (914 mm) from a lot line. Where Class A, B or C roof assemblies are required, they shall be tested in accordance with ASTM E108 or UL 790. Where required, the roof assembly shall be listed and identified as to class by an approved testing agency.

    Exceptions:

    1. Class A roof assemblies include those with coverings of brick, masonry and exposed concrete roof deck.

    2. Class A roof assemblies include ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile, or slate installed on noncombustible roof decks or ferrous, copper or metal sheets installed without a roof deck on noncombustible framing.

    3. Class A roof assemblies include minimum 16 ounces per square foot (4.882 kg/m [2] ) copper sheets installed over combustible roof decks.

    4. Class A roof assemblies include slate installed over underlayment over ASTM D226, Type II underlayment over combustible decks.

    R902.1.1 Roofing requirements within Fire Hazard Severity Zones or in Wildland-Urban Interface (WUI) area. Roofing require- ments for structures located within Fire Hazard Severity Zones or in a Wildland-Urban Interface (WUI) area shall also comply with Part 7, California Wildland-Urban Interface Code.

    R902.1.2 Roof coverings in all other areas other than Fire Hazard Severity Zones or a Wildland-Urban Interface (WUI) area. The entire roof covering of every existing structure where more than 50 percent of the total roof area is replaced within any one-year period, the entire roof covering of every new structure, and any roof covering applied in the alteration, repair or replacement of the roof of every existing structure, shall be a fire-retardant roof covering that is at least Class C fire classification.

    R902.2 Fire-retardant-treated shingles and shakes. Fire-retardant-treated wood shakes and shingles are wood shakes and shin- gles complying with UBC Standard 15-3 or 15-4 which are impregnated by the full-cell vacuum-pressure process with fire-retardant chemicals, and which have been qualified by UBC Standard 15-2 or ASTM E108 or UL 790 for use on Class A, B or C roofs. Fire-retardant- treated wood shakes and shingles shall comply with ICC-ES EG107 and with the weathering requirements contained in Health and Safety Code Section 13132.7 (j). Each bundle shall bear labels from an ICBO accredited quality control agency identifying their roof-covering classification and indicating their compliance with ICC-ES EG107 and with the weathering requirements contained in Health and Safety Code Section 13132.7 (j).

  • CBC § 1505.3 High relevance — show source text
    1. Class A roof assemblies include slate installed over ASTM D226, Type II or ASTM D4869, Type IV underlayment over combustible decks.

    [BF] 1505.3 Class B roof assemblies. Class B roof assemblies are those that are effective against moderate fire-test exposure. Class B roof assemblies and roof coverings shall be listed and identified as Class B by an approved testing agency.

    [BF] 1505.4 Class C roof assemblies. Class C roof assemblies are those that are effective against light fire-test exposure. Class C roof assemblies and roof coverings shall be listed and identified as Class C by an approved testing agency.

    [BF] 1505.5 Nonclassified roofing. Nonclassified roofing is approved material that is not listed as a Class A, B or C roof covering assembly or roof covering.

    [BF] 1505.6 Fire-retardant-treated wood shingles and shakes. Fire-retardant-treated wood shakes and shingles are wood shakes and shingles complying with UBC Standard 15-3 or 15-4 which are impregnated by the full-cell vacuum-pressure process with fire-retar- dant chemicals, and which have been qualified by UBC Standard 15-2 or ASTM E108 or UL 790 for use on Class A, B or C roofs.

    Fire-retardant-treated wood shakes and shingles shall comply with ICC-ES EG107 and with the weathering requirements contained in Health and Safety Code Section 13132.7(j). Each bundle shall bear labels from an ICC accredited quality control agency identifying their roof-covering classification and indicating their compliance with ICC-ES EG107 and with the weathering requirements contained in Health and Safety Code Section 13132.7(j).

    Health and Safety Code Section 13132.7(j). No wood roof covering materials shall be sold or applied in this state unless both of the following conditions are met: (1) The materials have been approved and listed by the State Fire Marshal as complying with the requirements of this section. (2) The materials have passed at least five years of the 10-year natural weathering test. The 10-year natural weathering test required by this subdivision shall be conducted in accordance with standard 15-2 of the 1994 edition of the Uniform Building Code at a testing facility recognized by the State Fire Marshal.

    [BF] 1505.7 Special purpose roofs. Special purpose wood shingle or wood shake roofing shall conform to the grading and application requirements of Section 1507.8 or 1507.9. In addition, an underlayment of [5] / 8 -inch (15.9 mm) Type X water-resistant gypsum backing board or gypsum sheathing shall be placed under minimum nominal [1] / 2 -inch-thick (12.7 mm) wood structural panel solid sheathing or 1-inch (25 mm) nominal spaced sheathing.

    [BF] 1505.8 Building-integrated photovoltaic (BIPV) systems. BIPV products installed as the roof covering shall be tested, listed and labeled for fire classification in accordance with Section 1505.1.

    [BF] 1505.9 Rooftop mounted photovoltaic (PV) panel systems. Rooftop mounted photovoltaic (PV) panel systems shall be tested, listed and identified with a fire classification in accordance with UL 2703. Listed systems shall be installed in accordance with the manufacturer’s installation instructions and their listing. The fire classification shall comply with Table 1505.1 based on the type of construction of the building.

  • CBC § 1505.1.1 High relevance — show source text

    ROOF ASSEMBLIES AND ROOFTOP STRUCTURES

    1505.1.1 Roofing requirements within Fire Hazard Severity Zones or in the Wildland-Urban Interface (WUI). Roofing require- ments for structures located within Fire Hazard Severity Zones or in the Wildland-Urban Interface (WUI) shall also comply with Section 705A.

    1505.1.2 Roof coverings within all other areas other than Fire Hazard Severity Zones or a Wildland-Urban Interface (WUI). The entire roof covering of every existing structure where more than 50 percent of the total roof area is replaced within any one-year period, the entire roof covering of every new structure, and any roof covering applied in the alteration, repair or replacement of the roof of every existing structure, shall be a fire-retardant roof covering that is at least Class C fire classification.

    [BF] 1505.2 Class A roof assemblies. Class A roof assemblies are those that are effective against severe fire test exposure. Class A roof assemblies and roof coverings shall be listed and identified as Class A by an approved testing agency. Class A roof assemblies shall be permitted for use in buildings or structures of all types of construction.

    Exceptions:

    1. Class A roof assemblies include those with coverings of brick, masonry or an exposed concrete roof deck.

    2. Class A roof assemblies also include ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile or slate installed on noncombustible decks or ferrous, copper or metal sheets installed without a roof deck on noncombustible framing.

    3. Class A roof assemblies include minimum 16 ounce per square foot (0.0416 kg/m [2] ) copper sheets installed over combustible decks.

    4. Class A roof assemblies include slate installed over ASTM D226, Type II or ASTM D4869, Type IV underlayment over combustible decks.

    [BF] 1505.3 Class B roof assemblies. Class B roof assemblies are those that are effective against moderate fire-test exposure. Class B roof assemblies and roof coverings shall be listed and identified as Class B by an approved testing agency.

    [BF] 1505.4 Class C roof assemblies. Class C roof assemblies are those that are effective against light fire-test exposure. Class C roof assemblies and roof coverings shall be listed and identified as Class C by an approved testing agency.

    [BF] 1505.5 Nonclassified roofing. Nonclassified roofing is approved material that is not listed as a Class A, B or C roof covering assembly or roof covering.

    [BF] 1505.6 Fire-retardant-treated wood shingles and shakes. Fire-retardant-treated wood shakes and shingles are wood shakes and shingles complying with UBC Standard 15-3 or 15-4 which are impregnated by the full-cell vacuum-pressure process with fire-retar- dant chemicals, and which have been qualified by UBC Standard 15-2 or ASTM E108 or UL 790 for use on Class A, B or C roofs.

    Fire-retardant-treated wood shakes and shingles shall comply with ICC-ES EG107 and with the weathering requirements contained in Health and Safety Code Section 13132.7(j). Each bundle shall bear labels from an ICC accredited quality control agency identifying their roof-covering classification and indicating their compliance with ICC-ES EG107 and with the weathering requirements contained in Health and Safety Code Section 13132.7(j).

  • CBC § 1.2 High relevance — show source text

    R902.1.2 Roof coverings in all other areas other than Fire Hazard Severity Zones or a Wildland-Urban Interface (WUI) area. The entire roof covering of every existing structure where more than 50 percent of the total roof area is replaced within any one-year period, the entire roof covering of every new structure, and any roof covering applied in the alteration, repair or replacement of the roof of every existing structure, shall be a fire-retardant roof covering that is at least Class C fire classification.

    R902.2 Fire-retardant-treated shingles and shakes. Fire-retardant-treated wood shakes and shingles are wood shakes and shin- gles complying with UBC Standard 15-3 or 15-4 which are impregnated by the full-cell vacuum-pressure process with fire-retardant chemicals, and which have been qualified by UBC Standard 15-2 or ASTM E108 or UL 790 for use on Class A, B or C roofs. Fire-retardant- treated wood shakes and shingles shall comply with ICC-ES EG107 and with the weathering requirements contained in Health and Safety Code Section 13132.7 (j). Each bundle shall bear labels from an ICBO accredited quality control agency identifying their roof-covering classification and indicating their compliance with ICC-ES EG107 and with the weathering requirements contained in Health and Safety Code Section 13132.7 (j).

    Health and Safety Code Section 13132.7 (j) No wood roof covering materials shall be sold or applied in this state unless both of the following conditions are met: (1) The materials have been approved and listed by the State Fire Marshal as complying with the requirements of this section. (2) The materials have passed at least five years of the 10-year natural weathering test. The 10-year natural weathering test required by this subdivision shall be conducted in accordance with Standard 15-2 of the 1994 edition of the Uniform Building Code at a testing facility recognized by the State Fire Marshal.

    R902.3 Building-integrated photovoltaic (BIPV) systems. Building-integrated photovoltaic (BIPV) systems installed as the roof covering shall be tested, listed and labeled for fire classification in accordance with UL 7103 [SFM] Section R902.1 through R902.1.2. Class A, B or C BIPV products shall be installed where the edge of the roof is less than 3 feet (914 mm) from a lot line.

    R902.4 Rooftop-mounted photovoltaic (PV) panel systems. Rooftop-mounted photovoltaic (PV) panel systems installed on or above the roof covering shall be tested, listed and identified with a fire classification in accordance with UL 2703. Listed systems shall be installed in accordance with the manufacturer’s installation instructions and their listing. Class A, B or C photovoltaic panel systems

    2025 CALIFORNIA RESIDENTIAL CODE 9-3

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    ROOF ASSEMBLIES

    and modules shall be installed in jurisdictions designated by law as requiring their use or where the edge of the roof is less than 3 feet (914 mm) from a lot line.

    SECTION R903—WEATHER PROTECTION

  • CBC § 4.1 High relevance — show source text

    1|||X||||||||||||||||||||| |R902.1 - R902.4|||X||||||||||||||||||||| |R903.4.1||||X|||||||||||||||||||| |R904.1 - R904.4|||X||||||||||||||||||||| |R905.15||||X|||||||||||||||||||| |R905.16||||X|||||||||||||||||||| |R907.1||||X|||||||||||||||||||| |R907.2 – R907.5|||X||||||||||||||||||||| |R909|||X|||||||||||||||||||||

    The state agency does not adopt sections identified with the following symbol: †

    2025 CALIFORNIA RESIDENTIAL CODE 9-1

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    9-2 2025 CALIFORNIA RESIDENTIAL CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    9 ROOF ASSEMBLIES

    User notes:

    About this chapter: Chapter 9 addresses the design and construction of roof assemblies. A roof assembly includes the roof deck, substrate or thermal barrier, insulation, vapor retarder and roof covering. This chapter provides the requirement for wind resistance of roof coverings. The types of roof covering materials and installation addressed by Chapter 9 are: asphalt shingles, clay and concrete tile, metal roof shingles, mineral-surfaced roll roofing, slate and slate-type shingles, wood shakes and shingles, built-up roofs, metal roof panels, modified bitumen roofing, thermoset and thermoplastic single-ply roofing, sprayed polyurethane foam roofing, liquid applied coatings and building-integrated photovoltaic (BIPV) roof coverings. Chapter 9 also provides requirements for roof drainage, flashing, above-deck thermal insulation, rooftop-mounted photovoltaic systems and recovering or replacing an existing roof covering.

    SECTION R901—GENERAL

    R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies.

    SECTION R902—FIRE CLASSIFICATION

    R902.1 Roof assemblies. Roof decks shall be covered with materials as set forth in Section R904 or with roof coverings as set forth in Section R905. A minimum Class A, B or C roofing shall be installed in areas designated by this section or where the edge of the roof deck is less than 3 feet (914 mm) from a lot line. Where Class A, B or C roof assemblies are required, they shall be tested in accordance with ASTM E108 or UL 790. Where required, the roof assembly shall be listed and identified as to class by an approved testing agency.

    Exceptions:

    1. Class A roof assemblies include those with coverings of brick, masonry and exposed concrete roof deck.

    2. Class A roof assemblies include ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile, or slate installed on noncombustible roof decks or ferrous, copper or metal sheets installed without a roof deck on noncombustible framing.

    3. Class A roof assemblies include minimum 16 ounces per square foot (4.882 kg/m [2] ) copper sheets installed over combustible roof decks.

    4. Class A roof assemblies include slate installed over underlayment over ASTM D226, Type II underlayment over combustible decks.

  • CBC § 504.1 High relevance — show source text

    SECTION 504—IGNITION-RESISTANT CONSTRUCTION

    504.1 General. Ignition-resistant construction shall be in accordance with Sections 504.2 through 504.11.6 .

    5-4 2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    SPECIAL BUILDING CONSTRUCTION REGULATIONS

    504.2 Roof assembly. Roofs shall have a roof assembly that complies with a Class A fire classification when tested in accordance with ASTM E108 or UL 790.

    Exceptions: The following assemblies are exempt from testing and shall be considered as equivalent to the Class A fire classification:

    1. Roof assemblies with coverings of brick, masonry or an exposed concrete roof deck.
    2. Roof assemblies with ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile or slate installed on noncombustible decks or ferrous, copper or metal sheets installed without a roof deck on noncombustible framing.
    3. Roof assemblies with minimum 16 oz/sq ft (0.0416 kg/m [2] ) copper sheets installed over combustible roof decks. 4. Roof assemblies of slate roof covering installed over ASTM D226, Type II underlayment over combustible decks.

    504.2.1 Roof covering voids. Where there is a void under the roof covering it shall comply with Section 504.2.1.1 or 504.2.1.2.

    504.2.1.1 Airspace under roof covering. Where the roof covering is installed over a combustible deck and the roofing profile creates an airspace under the roof covering, the installation shall comply with the following: 1. A 72 lb. (32.7 kg) cap sheet complying with ASTM D3909 Standard Specification for “Asphalt Rolled Roofing (Glass Felt) Surfaced with Mineral Granules,” shall be installed over the roof deck.

    Exception: Cap sheet is not required where not less than 1 inch of mineral wool board or other noncombustible material is located between the roofing material and wood framing or deck. 2. Bird stops shall be used at the eaves where the profile fits, to prevent the entry of debris at the eave. 3. Hip and ridge caps shall be mudded in to prevent intrusion of fire or embers.

    504.2.1.2 Roof underlayment. A listed and labeled roof underlayment that has been tested as part of the roof assembly in accor- dance with ASTM E108 or UL 790 for Class A fire classification shall be installed in accordance with the underlayment manufacturer’s installation instructions and listing. Bird stops shall be used at the eaves when the profile fits, to prevent the entry of debris at the eave. Hip and ridge caps shall be mudded in to prevent intrusion of fire or embers.

    Exception: Where the roof sheathing is fire-retardant-treated wood labeled for exterior use and complies with Section 2303.2 of the California Building Code, the underlayment shall not be required to comply with a Class A fire classification.

  • CBC § 1505.7 High relevance — show source text

    [BF] 1505.7 Special purpose roofs. Special purpose wood shingle or wood shake roofing shall conform to the grading and application requirements of Section 1507.8 or 1507.9. In addition, an underlayment of [5] / 8 -inch (15.9 mm) Type X water-resistant gypsum backing board or gypsum sheathing shall be placed under minimum nominal [1] / 2 -inch-thick (12.7 mm) wood structural panel solid sheathing or 1-inch (25 mm) nominal spaced sheathing.

    [BF] 1505.8 Building-integrated photovoltaic (BIPV) systems. BIPV products installed as the roof covering shall be tested, listed and labeled for fire classification in accordance with Section 1505.1.

    [BF] 1505.9 Rooftop mounted photovoltaic (PV) panel systems. Rooftop mounted photovoltaic (PV) panel systems shall be tested, listed and identified with a fire classification in accordance with UL 2703. Listed systems shall be installed in accordance with the manufacturer’s installation instructions and their listing. The fire classification shall comply with Table 1505.1 based on the type of construction of the building.

    [BF] 1505.10 Landscaped and vegetative roofs. Landscaped and vegetative roofs shall comply with Sections 1505.1 and 1507.15. Vegetative roofs shall be installed in accordance with ANSI/SPRI VF-1.

    SECTION 1506—MATERIALS

    1506.1 Scope. The requirements set forth in this section shall apply to the application of roof-covering materials specified herein. Roof coverings shall be applied in accordance with this chapter and the roof covering listing as required by Section 1505. Installation of roof coverings shall comply with the applicable provisions of Section 1507.

    1506.2 Material specifications and physical characteristics. Roof-covering materials shall conform to the applicable standards listed in this chapter.

    15-6 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    ROOF ASSEMBLIES AND ROOFTOP STRUCTURES

    1506.3 Product identification. Roof-covering materials shall be delivered in packages bearing the manufacturer’s identifying marks and approved testing agency labels required in accordance with Section 1505. Bulk shipments of materials shall be accompanied with the same information issued in the form of a certificate or on a bill of lading by the manufacturer.

    SECTION 1507—REQUIREMENTS FOR ROOF COVERINGS

    1507.1 Scope. Roof coverings shall be applied in accordance with the applicable provisions of this section and the manufacturer’s installation instructions.

  • CBC § 1.0 High relevance — show source text

    Interpolation shall be permitted for wind speed, mean roof height and parapet height. Extrapolation is not permitted.
    c. Basic wind speed,V, and wind exposure shall be determined in accordance with Section 1609.
    d. Where the minimum required parapet height is indicated to be 2 inches (51 mm), a gravel stop shall be permitted and shall extend not less than 2 inches (51 mm) from the roof
    surface and not less than the height of the aggregate.
    e. The tabulated values apply only to conditions where the topographic factor (Kzt) determined in accordance with Chapter 26 of ASCE 7 is 1.0 or where_Kzt_ is incorporated in the
    basic wind speed in Section 1609.
    f. For Exposure D, add 8 inches (203 mm) to the parapet height required for Exposure C and the parapet height shall not be less than 12 inches (305 mm).|

    SECTION 1505—FIRE CLASSIFICATION

    [BF] 1505.1 General. Fire classification of roof assemblies shall be in accordance with Section 1505. The minimum fire classification of roof assemblies installed on buildings shall comply with Table 1505.1 based on type of construction of the building. Class A, B and C roof assemblies and roof coverings required to be listed by this section shall be tested in accordance with ASTM E108 or UL 790. In addition, fire-retardant-treated woodroof coverings shall be tested in accordance with ASTM D2898; fire-retardant-treated shingles and shakes shall comply with Section 1505.6.

    Exception: Skylights and sloped glazing that comply with Chapter 24 or Section 2610.

    [BF] TABLE 1505.1—MINIMUM ROOF ASSEMBLY CLASSIFICATION FOR TYPES OF CONSTRUCTIONa, b Col2 Col3 Col4 Col5 Col6 Col7 Col8 Col9
    IA IB IIA IIB IIIA IIIB IV VA VB
    B B B Cc B Cc B B Cc
    For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2.
    a. Unless otherwise required in accordance with the_California Wildland-Urban Interface Code_ or due to the location of the building within a fire district in accordance with
    Appendix D.
    b. Nonclassified roof coverings shall be permitted on buildings of Group U occupancies, where there is a minimum fire-separation distance of 6 feet measured from the leading
    edge of the roof.
    c. Buildings that are not more than two stories above grade plane and having not more than 6,000 square feet of projected roof area and where there is a minimum 10-foot fire-
    separation distance from the leading edge of the roof to a lot line on all sides of the building, except for street fronts or public ways, shall be permitted to have roofs of No. 1
    cedar or redwood shakes and No. 1 shingles constructed in accordance with Section 1505.7.
    For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929 m2.
    a. Unless otherwise required in accordance with the_California Wildland-Urban Interface Code_ or due to the location of the building within a fire district in accordance with
    Appendix D.
    b.
  • CBC § 504.2.1.1 High relevance — show source text

    504.2.1.1 Airspace under roof covering. Where the roof covering is installed over a combustible deck and the roofing profile creates an airspace under the roof covering, the installation shall comply with the following: 1. A 72 lb. (32.7 kg) cap sheet complying with ASTM D3909 Standard Specification for “Asphalt Rolled Roofing (Glass Felt) Surfaced with Mineral Granules,” shall be installed over the roof deck.

    Exception: Cap sheet is not required where not less than 1 inch of mineral wool board or other noncombustible material is located between the roofing material and wood framing or deck. 2. Bird stops shall be used at the eaves where the profile fits, to prevent the entry of debris at the eave. 3. Hip and ridge caps shall be mudded in to prevent intrusion of fire or embers.

    504.2.1.2 Roof underlayment. A listed and labeled roof underlayment that has been tested as part of the roof assembly in accor- dance with ASTM E108 or UL 790 for Class A fire classification shall be installed in accordance with the underlayment manufacturer’s installation instructions and listing. Bird stops shall be used at the eaves when the profile fits, to prevent the entry of debris at the eave. Hip and ridge caps shall be mudded in to prevent intrusion of fire or embers.

    Exception: Where the roof sheathing is fire-retardant-treated wood labeled for exterior use and complies with Section 2303.2 of the California Building Code, the underlayment shall not be required to comply with a Class A fire classification.

    504.2.2 Roof valleys. Where provided, valley flashings shall be not less than 0.019 inch (0.48 mm) (No. 26 galvanized sheet gage) corrosion-resistant metal installed over a minimum 36-inch-wide (914 mm) underlayment consisting of one layer of 72-pound (32.4 kg) mineral-surfaced, nonperforated cap sheet complying with ASTM D3909 running the full length of the valley.

    504.3 Protection of enclosed eaves. The exposed underside of enclosed roof eaves and soffits shall be protected on the exposed underside by one or more of the following:

    1. Noncombustible materials.

    2. Ignition-resistant building materials. 3. Materials approved for not less than 1-hour fire-resistance-rated construction on the exterior side, as tested in accordance with ASTM E119 or UL 263.

    4. 2-inch (51 mm) nominal dimension lumber . 5. 1-inch (25 mm) nominal fire-retardant-treated lumber or [3] / 4 -inch (19.1 mm) nominal fire-retardant-treated plywood, identified for exterior use and complying with Section 2303.2 of the California Building Code . 6. Boxed-in roof eave soffit assemblies with an underside that meets the performance criteria in Section 504.7.2 when tested in accordance with the test procedures set forth in ASTM E2957. 7. Boxed-in roof eave soffit assemblies with an underside that meets the performance criteria in accordance with the test proce- dures set forth in SFM Standard 12-7A-3.

  • CBC § 1.0 High relevance — show source text

    Extrapolation is not permitted.
    c. Basic wind speed,V, and wind exposure shall be determined in accordance with Section 1609.
    d. Where the minimum required parapet height is indicated to be 2 inches (51 mm), a gravel stop shall be permitted and shall extend not less than 2 inches (51 mm) from the roof
    surface and not less than the height of the aggregate.
    e. The tabulated values apply only to conditions where the topographic factor (Kzt) determined in accordance with Chapter 26 of ASCE 7 is 1.0 or where_Kzt_ is incorporated in the
    basic wind speed in Section 1609.
    f. For Exposure D, add 8 inches (203 mm) to the parapet height required for Exposure C and the parapet height shall not be less than 12 inches (305 mm).|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mile per hour = 0.447 m/s.
    a. Parapet height is measured vertically from the top surface of the coping down to the surface of the roof covering in the field of the roof adjacent to the parapet and outbound
    of any cant strip.
    b. Interpolation shall be permitted for wind speed, mean roof height and parapet height. Extrapolation is not permitted.
    c. Basic wind speed,V, and wind exposure shall be determined in accordance with Section 1609.
    d. Where the minimum required parapet height is indicated to be 2 inches (51 mm), a gravel stop shall be permitted and shall extend not less than 2 inches (51 mm) from the roof
    surface and not less than the height of the aggregate.
    e. The tabulated values apply only to conditions where the topographic factor (Kzt) determined in accordance with Chapter 26 of ASCE 7 is 1.0 or where_Kzt_ is incorporated in the
    basic wind speed in Section 1609.
    f. For Exposure D, add 8 inches (203 mm) to the parapet height required for Exposure C and the parapet height shall not be less than 12 inches (305 mm).|

    SECTION 1505—FIRE CLASSIFICATION

    [BF] 1505.1 General. Fire classification of roof assemblies shall be in accordance with Section 1505. The minimum fire classification of roof assemblies installed on buildings shall comply with Table 1505.1 based on type of construction of the building. Class A, B and C roof assemblies and roof coverings required to be listed by this section shall be tested in accordance with ASTM E108 or UL 790. In addition, fire-retardant-treated woodroof coverings shall be tested in accordance with ASTM D2898; fire-retardant-treated shingles and shakes shall comply with Section 1505.6.

    Exception: Skylights and sloped glazing that comply with Chapter 24 or Section 2610.

  • CBC § 503.2.5 High relevance — show source text

    503.2.5 Surface treatment protection. Use of paints, coatings, stains or other surface treatments are not an approved method of protection as required in this chapter.

    503.3 Standards of quality. Building material, systems, assemblies and methods of construction shall be tested in accordance with the standards specified in Chapter 5.

    503.3.1 Qualification by testing. Material and material assemblies tested in accordance with the requirements of Section 503 shall be accepted for use when the results and conditions of those tests are met. Product evaluation testing of material and material assemblies shall be approved or listed by the State Fire Marshal or identified in a current report issued by an approved agency.

    503.3.2 Approved agency. Product evaluation testing shall be performed by an approved agency in accordance with Section 1703 of the California Building Code. The scope of accreditation for the approved agency shall include building product compliance with this code.

    503.3.3 Labeling. Material and material assemblies tested in accordance with the referenced standards shall bear an identification label showing the fire test results. That identification label shall be issued by a testing and/or inspecting agency approved by the State Fire Marshal.

    1. Identification mark of the approved testing and/or inspecting agency.

    2. Contact and identification information of the manufacturer.

    3. Model number or identification of the product or material. 4. Pretest weathering specified in this chapter. 5. Compliance standard as described under Chapter 7.

    503.3.4 Fire-retardant-treated wood shingles and shakes. Fire-retardant-treated wood shingles and shakes shall be approved and listed by the State Fire Marshal in accordance with Section 208(c), Title 19 California Code of Regulations.

    SECTION 504—IGNITION-RESISTANT CONSTRUCTION

    504.1 General. Ignition-resistant construction shall be in accordance with Sections 504.2 through 504.11.6 .

    5-4 2025 CALIFORNIA WILDLAND-URBAN INTERFACE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    SPECIAL BUILDING CONSTRUCTION REGULATIONS

    504.2 Roof assembly. Roofs shall have a roof assembly that complies with a Class A fire classification when tested in accordance with ASTM E108 or UL 790.

    Exceptions: The following assemblies are exempt from testing and shall be considered as equivalent to the Class A fire classification:

    1. Roof assemblies with coverings of brick, masonry or an exposed concrete roof deck.
    2. Roof assemblies with ferrous or copper shingles or sheets, metal sheets and shingles, clay or concrete roof tile or slate installed on noncombustible decks or ferrous, copper or metal sheets installed without a roof deck on noncombustible framing.
    3. Roof assemblies with minimum 16 oz/sq ft (0.0416 kg/m [2] ) copper sheets installed over combustible roof decks. 4. Roof assemblies of slate roof covering installed over ASTM D226, Type II underlayment over combustible decks.

    504.2.1 Roof covering voids. Where there is a void under the roof covering it shall comply with Section 504.2.1.1 or 504.2.1.2.

Frequently asked questions

Who determines whether a roof must be Class A, B or C?

Minimum classification is set by the building’s type of construction and Table 1505.1; additionally, new roofs and major replacements outside WUI areas must be at least Class C per §1505.1.2, and WUI/Fire Hazard Severity Zones can require Class A under the Wildland‑Urban Interface Code .

Do rooftop PV and BIPV systems need a fire classification?

Yes. Rooftop PV modules and systems must be tested/listed and identified with a fire classification in accordance with UL 2703 (and BIPV products per the listing requirements in Chapter 15); they must be installed per their listing and manufacturer instructions .

What about wood shakes or shingles?

Wood shakes and shingles used on roofs must meet the CBC’s fire‑retardant requirements, be tested/listed (ASTM/UL standards and ICC‑ES/State Fire Marshal approvals), and—where required—meet the CBC and WUI preweathering/listing conditions before sale or application .