Seismic design and reinforcement
Use §1613 to determine seismic category and ASCE 7 procedures, then follow the CBC’s foundation, concrete and masonry reinforcement and anchorage rules (for example §1810, §1807, §1905, §2113) when seismic demands control design.
Last reviewed: July 5, 2026
Overview
This area of the California Building Code (CBC) covers required seismic loads, seismic design categories, and the detailing and anchorage needed to make structural and nonstructural elements resist earthquake motion. The CBC establishes earthquake-load scope and procedure in §1613 and explicitly ties seismic design to the referenced ASCE 7 procedures for seismic forces and site-class effects .
The code also sets prescriptive and analysis-based reinforcement requirements where seismic forces govern: for example, seismic reinforcement rules for deep foundations and cast‑in‑place elements appear in §1810.3.9.4, foundation‑wall and retaining‑wall seismic limits are in §1807.1.6.2.1, and restrictions on structural plain concrete in higher seismic categories are in §1905.6.2 . Special provisions for masonry elements such as chimneys and anchorage are found in §2113.3 .
The practical effect: determine the Seismic Design Category per §1613, apply ASCE 7 where called out, and follow the CBC’s specific reinforcement, anchorage and detailing sections (chapters on soils and foundations, concrete, masonry, and structural design) when seismic loads control the design .
In this section
Code references
Grounded in the retrieved California Building Code — click a citation to read the verbatim passage:
CBC § 1810.3.9.4.1 High relevance — show source text
1810.3.9.4.1 Seismic reinforcement in Seismic Design Category C. For structures assigned to Seismic Design Category C, cast-in-place deep foundation elements shall be reinforced as specified in this section. Reinforcement shall be provided where required by analysis.
Not fewer than four longitudinal bars, with a minimum longitudinal reinforcement ratio of 0.0025, shall be provided throughout the minimum reinforced length of the element as defined in this section starting at the top of the element. The minimum reinforced length of the element shall be taken as the greatest of the following:
One-third of the element length.
A distance of 10 feet (3048 mm).
Three times the least element dimension.
The distance from the top of the element to the point where the design cracking moment determined in accordance with Section 1810.3.9.1 exceeds the required moment strength determined using the load combinations of ASCE 7, Section 2.3.
2025 CALIFORNIA BUILDING CODE 18-27
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
SOILS AND FOUNDATIONS
Transverse reinforcement shall consist of closed ties or spirals with a minimum [3] / 8 inch (9.5 mm) diameter. Spacing of transverse reinforcement shall not exceed the smaller of 6 inches (152 mm) or 8-longitudinal-bar diameters, within a distance of three times the least element dimension from the bottom of the pile cap. Spacing of transverse reinforcement shall not exceed 16 longitudinal bar diameters throughout the remainder of the reinforced length.
Exceptions:
- The requirements of this section shall not apply to concrete cast in structural steel pipes or tubes.
- A spiral-welded metal casing of a thickness not less than the manufacturer’s standard No. 14 gage (0.068 inch) is permitted to provide concrete confinement in lieu of the closed ties or spirals. Where used as such, the metal casing shall be protected against possible deleterious action due to soil constituents, changing water levels or other factors indicated by boring records of site conditions.
1810.3.9.4.2 Seismic reinforcement in Seismic Design Categories D through F. For structures assigned to Seismic Design Category D, E or F, cast-in-place deep foundation elements shall be reinforced as specified in this section. Reinforcement shall be provided where required by analysis.
Not fewer than four longitudinal bars, with a minimum longitudinal reinforcement ratio of 0.005, shall be provided throughout the minimum reinforced length of the element as defined in this section starting at the top of the element. The minimum reinforced length of the element shall be taken as the greatest of the following:
One-half of the element length.
A distance of 10 feet (3048 mm).
Three times the least element dimension.
The distance from the top of the element to the point where the design cracking moment determined in accordance with Section 1810.3.9.1 exceeds the required moment strength determined using the load combinations of ASCE 7, Section 2.3.
CBC § 2.1. High relevance — show source text
Isolated deep foundation elements supporting posts and bracing from decks and patios appurtenant to Group R-3 and U occupancies not exceeding two stories of light-frame construction shall be permitted to be reinforced as required by rational analysis but with not less than one No. 4 bar, without ties or spirals, where the lateral load, E, to the top of the element does not exceed 200 pounds (890 N) and the soil provides adequate lateral support in accordance with Section 1810 A .2.1.
Deep foundation elements supporting the concrete foundation wall of Group R-3 and U occupancies not exceeding two stories of light-frame construction shall be permitted to be reinforced as required by rational analysis but with not less than two No. 4 bars, without ties or spirals, where the design cracking moment determined in accordance with Section 1810 A .3.9.1 exceeds the required moment strength determined using the load combinations with overstrength factor in Section 2.3.6 or 2.4.5 of ASCE 7 and the soil provides adequate lateral support in accordance with Section 1810 A .2.1.
Closed ties or spirals where required by Section 1810 A .3.9.4.2 shall be permitted to be limited to the top 3 feet (914 mm) of deep foundation elements 10 feet (3048 mm) or less in depth supporting Group R-3 and U occupancies of Seismic Design Category D, not exceeding two stories of light-frame construction.
1810 A .3.9.4.1 Seismic reinforcement in Seismic Design Category C. Not permitted by DSA-SS, DSA-SS/CC or OSHPD.
1810 A .3.9.4.2 Seismic reinforcement in Seismic Design Categories D through F. For structures assigned to Seismic Design Category D, E or F, cast-in-place deep foundation elements shall be reinforced as specified in this section. Reinforcement shall be provided where required by analysis.
Not fewer than four longitudinal bars, with a minimum longitudinal reinforcement ratio of 0.005, shall be provided throughout the minimum reinforced length of the element as defined in this section starting at the top of the element. The minimum reinforced length of the element shall be taken as the greatest of the following:
One-half of the element length.
A distance of 10 feet (3048 mm).
Three times the least element dimension.
2025 CALIFORNIA BUILDING CODE 18A-21
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
SOILS AND FOUNDATIONS
- The distance from the top of the element to the point where the design cracking moment determined in accordance with Section 1810 A .3.9.1 exceeds the required moment strength determined using the load combinations of ASCE 7, Section 2.3.
Transverse reinforcement shall consist of closed ties or spirals not smaller than No. 3 bars for elements with a least dimension up to 20 inches (508 mm), and No. 4 bars for larger elements. Throughout the remainder of the reinforced length outside the regions with transverse confinement reinforcement, as specified in Section 1810 A .3.9.4.2.1 or 1810 A .3.9.4.2.2, the spacing of transverse reinforcement shall not exceed the least of the following:
- 12 longitudinal bar diameters.
CBC § 2113.2 High relevance — show source text
2113.2 Footings and foundations. Footings for masonry chimneys shall be constructed of concrete or solid masonry not less than 12 inches (305 mm) thick and shall extend not less than 6 inches (152 mm) beyond the face of the foundation or support wall on all sides. Footings shall be founded on natural undisturbed earth or engineered fill below frost depth. In areas not subjected to freezing, footings shall be not less than 12 inches (305 mm) below finished grade.
2113.3 Seismic reinforcement. In structures assigned to Seismic Design Category A or B, seismic reinforcement is not required. In structures assigned to Seismic Design Category C or D, masonry chimneys shall be reinforced and anchored in accordance with Sections 2113.3.1, 2113.3.2 and 2113.4. In structures assigned to Seismic Design Category E or F, masonry chimneys shall be reinforced in accordance with the requirements of Sections 2101 through 2108 and anchored in accordance with Section 2113.4.
2113.3.1 Vertical reinforcement. For chimneys up to 40 inches (1016 mm) wide, four No. 4 continuous vertical bars anchored in the foundation shall be placed in the concrete between wythes of solid masonry or within the cells of hollow unit masonry and grouted in accordance with Section 2103.3. Grout shall be prevented from bonding with the flue liner so that the flue liner is free to move with thermal expansion. For chimneys greater than 40 inches (1016 mm) wide, two additional No. 4 vertical bars shall be provided for each additional 40 inches (1016 mm) in width or fraction thereof. 2113.3.2 Horizontal reinforcement. Vertical reinforcement shall be placed enclosed within [1] / 4 -inch (6.4 mm) ties, or other reinforcing of equivalent net cross-sectional area, spaced not to exceed 18 inches (457 mm) on center in concrete, or placed in the bed joints of unit masonry, at not less than every 18 inches (457 mm) of vertical height. Two such ties shall be provided at each bend in the vertical bars.
2113.4 Seismic anchorage. Masonry chimneys and foundations shall be anchored at each floor, ceiling or roof line more than 6 feet (1829 mm) above grade with two [3] / 16 -inch by 1-inch (4.8 mm by 25 mm) straps embedded not less than 12 inches (305 mm) into the chimney. Straps shall be hooked around the outer bars and extend 6 inches (152 mm) beyond the bend. Each strap shall be fastened to not less than four floor joists with two [1] / 2 -inch (12.7 mm) bolts.
Exception: Seismic anchorage is not required for the following:
- In structures assigned to Seismic Design Category A or B.
- Where the masonry fireplace is constructed completely within the exterior walls.
CBC § 1810.2.1. High relevance — show source text
Exceptions:
Isolated deep foundation elements supporting posts of Group R-3 and U occupancies not exceeding two stories of light-frame construction shall be permitted to be reinforced as required by rational analysis but with not less than one No. 4 bar, without ties or spirals, where detailed so the element is not subject to lateral loads and the soil provides adequate lateral support in accordance with Section 1810.2.1.
Isolated deep foundation elements supporting posts and bracing from decks and patios appurtenant to Group R-3 and U occupancies not exceeding two stories of light-frame construction shall be permitted to be reinforced as required by rational analysis but with not less than one No. 4 bar, without ties or spirals, where the lateral load, E, to the top of the element does not exceed 200 pounds (890 N) and the soil provides adequate lateral support in accordance with Section 1810.2.1.
Deep foundation elements supporting the concrete foundation wall of Group R-3 and U occupancies not exceeding two stories of light-frame construction shall be permitted to be reinforced as required by rational analysis but with not less than two No. 4 bars, without ties or spirals, where the design cracking moment determined in accordance with Section 1810.3.9.1 exceeds the required moment strength determined using the load combinations with overstrength factor in Section 2.3.6 or 2.4.5 of ASCE 7 and the soil provides adequate lateral support in accordance with Section 1810.2.1.
Closed ties or spirals where required by Section 1810.3.9.4.2 shall be permitted to be limited to the top 3 feet (914 mm) of deep foundation elements 10 feet (3048 mm) or less in depth supporting Group R-3 and U occupancies of Seismic Design Category D, not exceeding two stories of light-frame construction.
1810.3.9.4.1 Seismic reinforcement in Seismic Design Category C. For structures assigned to Seismic Design Category C, cast-in-place deep foundation elements shall be reinforced as specified in this section. Reinforcement shall be provided where required by analysis.
Not fewer than four longitudinal bars, with a minimum longitudinal reinforcement ratio of 0.0025, shall be provided throughout the minimum reinforced length of the element as defined in this section starting at the top of the element. The minimum reinforced length of the element shall be taken as the greatest of the following:
One-third of the element length.
A distance of 10 feet (3048 mm).
Three times the least element dimension.
The distance from the top of the element to the point where the design cracking moment determined in accordance with Section 1810.3.9.1 exceeds the required moment strength determined using the load combinations of ASCE 7, Section 2.3.
2025 CALIFORNIA BUILDING CODE 18-27
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
SOILS AND FOUNDATIONS
Transverse reinforcement shall consist of closed ties or spirals with a minimum [3] / 8 inch (9.5 mm) diameter. Spacing of transverse reinforcement shall not exceed the smaller of 6 inches (152 mm) or 8-longitudinal-bar diameters, within a distance of three times the least element dimension from the bottom of the pile cap. Spacing of transverse reinforcement shall not exceed 16 longitudinal bar diameters throughout the remainder of the reinforced length.
CBC § 1807.1.6.2. High relevance — show source text
Provisions for this table are based on design and construction requirements specified in Section 1807.1.6.2.
c. PC = Plain Concrete.
d. Where unbalanced backfill height exceeds 8 feet and design lateral soil loads from Table 1610.1 are used, the requirements for 30 and 45 psf per foot of depth are not applica-
ble (see Section 1610).
e. For height of unbalanced backfill, see Section 1807.1.2.|1807.1.6.2.1 Seismic requirements. Based on the seismic design category assigned to the structure in accordance with Section 1613, concrete foundation walls designed using Table 1807.1.6.2 shall be subject to the following limitations:
- Seismic Design Categories A and B. Not less than one No. 5 bar shall be provided around window, door and similar sized openings. The bar shall be anchored to develop f y in tension at the corners of openings.
- Seismic Design Categories C, D, E and F. Tables shall not be used except as allowed for plain concrete members in Section 1905.6.2.
1807.1.6.3 Masonry foundation walls. Masonry foundation walls shall comply with the following:
- The thickness shall comply with the requirements of Table 1807.1.6.3(1) for plain masonry walls or Table 1807.1.6.3(2), 1807.1.6.3(3) or 1807.1.6.3(4) for masonry walls with reinforcement.
- Vertical reinforcement shall have a minimum yield strength of 60,000 psi (414 MPa).
- The specified location of the reinforcement shall equal or exceed the effective depth distance, d, noted in Tables 1807.1.6.3(2), 1807.1.6.3(3) and 1807.1.6.3(4) and shall be measured from the face of the exterior (soil) side of the wall to the center of the vertical reinforcement. The reinforcement shall be placed within the tolerances specified in TMS 602 for the specified location.
- Grout shall comply with Section 2103.3.
- Concrete masonry units shall comply with ASTM C90.
- Clay masonry units shall comply with ASTM C652 for hollow brick, except compliance with ASTM C62 or ASTM C216 shall be permitted where solid masonry units are installed in accordance with Table 1807.1.6.3(1) for plain masonry.
- Masonry units shall be laid in running bond and installed with Type M or S mortar in accordance with Section 2103.2.1.
- The unfactored axial load per linear foot of wall shall not exceed 1.2 tf′ m where t is the specified wall thickness in inches and f′ m is the specified compressive strength of masonry in pounds per square inch.
2025 CALIFORNIA BUILDING CODE 18-11
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
SOILS AND FOUNDATIONS
- Not less than 4 inches (102 mm) of solid masonry shall be provided at girder supports at the top of hollow masonry unit foundation walls.
CBC § 1810.3.11.1 High relevance — show source text
1810.3.11.1 Seismic Design Categories C through F. For structures assigned to Seismic Design Category C, D, E or F, concrete deep foundation elements shall be connected to the pile cap in accordance with ACI 318.
For resistance to uplift forces, anchorage of steel pipes, tubes or H-piles to the pile cap shall be made by means other than concrete bond to the bare steel section. Concrete-filled steel pipes or tubes shall have reinforcement of not less than 0.01 times the cross-sectional area of the concrete fill developed into the cap and extending into the fill a length equal to two times the required cap embedment, but not less than the development length in tension of the reinforcement.
1810.3.11.2 Seismic Design Categories D through F. For structures assigned to Seismic Design Category D, E or F, deep foundation element resistance to uplift forces or rotational restraint shall be provided by anchorage into the pile cap, designed considering the combined effect of axial forces due to uplift and bending moments due to fixity to the pile cap. Anchorage shall develop not less than 25 percent of the strength of the element in tension. Anchorage into the pile cap shall comply with the following:
- In the case of uplift, the anchorage shall be capable of developing the least of the following: 1.1. The nominal tensile strength of the longitudinal reinforcement in a concrete element. 1.2. The nominal tensile strength of a steel element. 1.3. The frictional force developed between the element and the soil multiplied by 1.3. Exception: The anchorage is permitted to be designed to resist the axial tension force resulting from the seismic load effects including overstrength factor in accordance with Section 2.3.6 or 2.4.5 of ASCE 7.
- In the case of rotational restraint, the anchorage shall be designed to resist the axial and shear forces, and moments resulting from the seismic load effects including overstrength factor in accordance with Section 2.3.6 or 2.4.5 of ASCE 7 or the anchorage shall be capable of developing the full axial, bending and shear nominal strength of the element.
- The connection between the pile cap and the steel H-piles or unfilled steel pipe piles in structures assigned to Seismic Design Category D, E or F shall be designed for a tensile force of not less than 10 percent of the pile compression capacity.
2025 CALIFORNIA BUILDING CODE 18-29
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
SOILS AND FOUNDATIONS
Exceptions:
- Connection tensile capacity need not exceed the strength required to resist seismic load effects including overstrength of ASCE 7 Section 12.4.3 or 12.14.3.2.
- Connections need not be provided where the foundation or supported structure does not rely on the tensile capacity of the piles for stability under the design seismic force. [OSHPD 1R, 2 & 5] Not permitted by OSHPD.
Where the vertical lateral-force-resisting elements are columns, the pile cap flexural strengths shall exceed the column flexural strength. The connection between batter piles and pile caps shall be designed to resist the nominal strength of the pile acting as a short column. Batter piles and their connection shall be designed to resist forces and moments that result from the application of seismic load effects including overstrength factor in accordance with Section 2.3.6 or 2.4.5 of ASCE 7.
CBC § 0.20 High relevance — show source text
- Horizontal reinforcement of not less than 0.20 square inch (129 mm [2] ) in cross-sectional area shall be provided: 2.1. Continuously at structurally connected roof and floor levels and at the top of walls. 2.2. At the bottom of load-bearing walls or in the top of foundations where doweled to the wall. 2.3. At a maximum spacing of 120 inches (3048 mm).
Reinforcement at the top and bottom of openings, where used in determining the maximum spacing specified in Item 2.3, shall be continuous in the wall.
19-6 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
CONCRETE
1905.6 Structural plain concrete. Structural plain concrete elements shall comply with this section in lieu of Section 14.1.4 of ACI 318. [OSHPD 1R, 2 & 5] Plain concrete shall not be permitted.
1905.6.1 Seismic Design Categories A and B. In structures assigned to Seismic Design Category A or B, detached one- and twofamily dwellings three stories or less in height constructed with stud-bearing walls are permitted to have plain concrete footings without longitudinal reinforcement.
1905.6.2 Seismic Design Categories C, D, E and F. Structures assigned to Seismic Design Category C, D, E or F shall not have elements of structural plain concrete, except as follows:
Structural plain concrete basement, foundation or other walls below the base as defined in ASCE/SEI 7 are permitted in detached one- and two-family dwellings three stories or less in height constructed with stud-bearing walls. In dwellings assigned to Seismic Design Category D or E, the height of the wall shall not exceed 8 feet (2438 mm), the thickness shall be not less than 7 [1] / 2 inches (190 mm), and the wall shall retain not more than 4 feet (1219 mm) of unbalanced fill. Walls shall have reinforcement in accordance with Section 14.6.1 of ACI 318.
Isolated footings of plain concrete supporting pedestals or columns are permitted, provided that the projection of the footing beyond the face of the supported member does not exceed the footing thickness. Exception: In detached one- and two-family dwellings three stories or less in height, the projection of the footing beyond the face of the supported member is permitted to exceed the footing thickness.
Plain concrete footings supporting walls are permitted, provided that the footings have not fewer than two continuous longitudinal reinforcing bars. Bars shall not be smaller than No. 4 and shall have a total area of not less than 0.002 times the gross cross-sectional area of the footing. For footings that exceed 8 inches (203 mm) in thickness, not fewer than one bar shall be provided at the top and bottom of the footing. Continuity of reinforcement shall be provided at corners and intersections.
Exceptions:
- Where assigned to Seismic Design Category C, detached one- and two-family dwellings three stories or less in height constructed with stud-bearing walls are permitted to have plain concrete footings without longitudinal reinforcement.
CBC § 2.2 High relevance — show source text
Splices occurring in the upper 10 feet (3048 mm) of the embedded portion of an element shall be designed to resist at allowable stresses the moment and shear that would result from an assumed eccentricity of the axial load of 3 inches (76 mm), or the element shall be braced in accordance with Section 1810 A .2.2 to other deep foundation elements that do not have splices in the upper 10 feet (3048 mm) of embedment.
1810 A .3.6.1 Seismic Design Categories C through F. For structures assigned to Seismic Design Category C, D, E or F splices of deep foundation elements shall develop the lesser of the following:
- The nominal strength of the deep foundation element.
- The axial and shear forces and moments from the seismic load effects including overstrength factor in accordance with Section 2.3.6 or 2.4.5 of ASCE 7.
1810 A .3.7 Top of element detailing at cutoffs. Where a minimum length for reinforcement or the extent of closely spaced confinement reinforcement is specified at the top of a deep foundation element, provisions shall be made so that those specified lengths or extents are maintained after cutoff.
1810 A .3.8 Precast concrete piles. Precast concrete piles shall be designed and detailed in accordance with ACI 318.
Exception: Where the axial load from seismic forces is amplified by the applicable overstrength factor, Ω 0 , the axial load limits in Section 18.13.5.10.6 of ACI 318 may be increased by two times.
1810 A .3.9 Cast-in-place deep foundations. Cast-in-place deep foundation elements shall be designed and detailed in accordance with Sections 1810 A .3.9.1 through 1810 A .3.9.6.
18A-20 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
SOILS AND FOUNDATIONS
1810 A .3.9.1 Design cracking moment. The design cracking moment ( φ M n ) for a cast-in-place deep foundation element not enclosed by a structural steel pipe or tube shall be determined using the following equation:
Equation 18 A -5
φ M n = 3 f ′ c S m
For SI: φ M n = 0.25 f ′ c S m
where:
f ′ c = Specified compressive strength of concrete or grout, psi (MPa). S m = Elastic section modulus, neglecting reinforcement and casing, cubic inches (mm [3] ).
1810 A .3.9.2 Required reinforcement. Where subject to uplift or where the required moment strength determined using the load combinations of ASCE 7, Section 2.3 exceeds the design cracking moment determined in accordance with Section 1810 A .3.9.1, cast-in-place deep foundations not enclosed by a structural steel pipe or tube shall be reinforced. Where reinforcement is required, it shall be in compliance with Chapter 20 of ACI 318.
CBC § 18A-20 High relevance — show source text
18A-20 2025 CALIFORNIA BUILDING CODE
on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.
SOILS AND FOUNDATIONS
1810 A .3.9.1 Design cracking moment. The design cracking moment ( φ M n ) for a cast-in-place deep foundation element not enclosed by a structural steel pipe or tube shall be determined using the following equation:
Equation 18 A -5
φ M n = 3 f ′ c S m
For SI: φ M n = 0.25 f ′ c S m
where:
f ′ c = Specified compressive strength of concrete or grout, psi (MPa). S m = Elastic section modulus, neglecting reinforcement and casing, cubic inches (mm [3] ).
1810 A .3.9.2 Required reinforcement. Where subject to uplift or where the required moment strength determined using the load combinations of ASCE 7, Section 2.3 exceeds the design cracking moment determined in accordance with Section 1810 A .3.9.1, cast-in-place deep foundations not enclosed by a structural steel pipe or tube shall be reinforced. Where reinforcement is required, it shall be in compliance with Chapter 20 of ACI 318.
1810 A .3.9.3 Placement of reinforcement. Reinforcement where required shall be assembled and tied together and shall be placed in the deep foundation element as a unit before the reinforced portion of the element is filled with concrete.
Exceptions:
Steel dowels embedded 5 feet (1524 mm) or less shall be permitted to be placed after concreting, while the concrete is still in a semifluid state.
For deep foundation elements installed with a hollow-stem auger, tied reinforcement shall be placed after elements are concreted, while the concrete is still in a semifluid state. Longitudinal reinforcement without lateral ties shall be placed either through the hollow stem of the auger prior to concreting or after concreting, while the concrete is still in a semifluid state.
For Group R-3 and U occupancies not exceeding two stories of light-frame construction, reinforcement is permitted to be placed after concreting, while the concrete is still in a semifluid state, and the concrete cover requirement is permitted to be reduced to 2 inches (51 mm), provided that the construction method can be demonstrated to the satisfaction of the building official.
1810 A .3.9.4 Seismic reinforcement. Where a structure is assigned to Seismic Design Category D, E or F, reinforcement shall be provided in accordance with Section 1810 A .3.9.4.2.
Exceptions:
- Isolated deep foundation elements supporting posts of Group R-3 and U occupancies not exceeding two stories of light-frame construction shall be permitted to be reinforced as required by rational analysis but with not less than one No. 4 bar, without ties or spirals, where detailed so the element is not subject to lateral loads and the soil provides adequate lateral support in accordance with Section 1810 A .2.1.
CBC § 1807.1.2. High relevance — show source text
For height of unbalanced backfill, see Section 1807.1.2.
e. Where unbalanced backfill height exceeds 8 feet and design lateral soil loads from Table 1610.1 are used, the requirements for 30 and 45 psf per foot of depth are not applica-
ble. See Section 1610.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0.157 kPa/m.
a. For design lateral soil loads, see Section 1610.
b. Provisions for this table are based on design and construction requirements specified in Section 1807.1.6.3.
c. For alternative reinforcement, see Section 1807.1.6.3.1.
d. For height of unbalanced backfill, see Section 1807.1.2.
e. Where unbalanced backfill height exceeds 8 feet and design lateral soil loads from Table 1610.1 are used, the requirements for 30 and 45 psf per foot of depth are not applica-
ble. See Section 1610.|1807.1.6.3.1 Alternative foundation wall reinforcement. In lieu of the reinforcement provisions for masonry foundation walls in Table 1807.1.6.3(2), 1807.1.6.3(3) or 1807.1.6.3(4), alternative reinforcing bar sizes and spacings having an equivalent cross-sectional area of reinforcement per linear foot (mm) of wall shall be permitted to be used, provided that the spacing of reinforcement does not exceed 72 inches (1829 mm) and reinforcing bar sizes do not exceed No. 11.
1807.1.6.3.2 Seismic requirements. Based on the seismic design category assigned to the structure in accordance with Section 1613, masonry foundation walls designed using Tables 1807.2.5.
- Seismic Design Categories A and B. No additional seismic requirements.
- Seismic Design Category C. A design using Tables 1807.1.6.3(1) through 1807.1.6.3(4) is subject to the seismic requirements of Section 7.4.3 of TMS 402.
- Seismic Design Category D. A design using Tables 1807.1.6.3(2) through 1807.1.6.3(4) is subject to the seismic requirements of Section 7.4.4 of TMS 402.
- Seismic Design Categories E and F. A design using Tables 1807.1.6.3(2) through 1807.1.6.3(4) is subject to the seismic requirements of Section 7.4.5 of TMS 402.
1807.2 Retaining walls. Retaining walls shall be designed in accordance with Sections 1807.2.1 through 1807.2.4.
1807.2.1 General. Retaining walls shall be designed to ensure stability against overturning, sliding, excessive foundation pressure and water uplift.
CBC § 2.2. High relevance — show source text
2.2. Construction documents shall include a statement that the building is designed in accordance with ASCE 24, including that the pile or column foundation and building or structure to be attached thereto is designed to be anchored to resist flotation, collapse and lateral movement due to the effects of wind and flood loads acting simultaneously on all building components, and other load requirements of Chapter 16. 2.3. For breakaway walls designed to have a resistance of more than 20 psf (0.96 kN/m [2] ) determined using allowable stress design or a resistance to an ultimate load of more than 33 pounds per square foot (1.58 kN/m [2] ), construction documents shall include a statement that the breakaway wall is designed in accordance with ASCE 24. 2.4 For breakaway walls where provisions to allow for the automatic entry and exit of floodwaters do not meet the minimum requirements in Section 2.7.2.1 of ASCE 24, construction documents shall include a statement that the design will provide for equalization of hydrostatic flood forces in accordance with Section 2.7.2.2 of ASCE 24.
SECTION 1613 A —EARTHQUAKE LOADS
1613 A .1 Scope. Every structure, and portion thereof, including nonstructural components that are permanently attached to structures and their supports and attachments, shall be designed and constructed to resist the effects of earthquake motions in accordance with Chapters 11, 12, 13, 15, 17 and 18 of ASCE 7, as applicable. The seismic design category for a structure is permitted to be determined in accordance with Section 1613 A or ASCE 7.
1613 A .2 Determination of seismic design category. Structures shall be assigned to a Seismic Design Category D or higher based on one of the following methods unless the authority having jurisdiction or geotechnical data determines that Site Class DE, E or F soils are present at the site:
Based on the structure risk category using Figure 1613.2(1).
Determined in accordance with ASCE 7.
Where Site Class DE, E or F soils are present, the seismic design category shall be determined in accordance with ASCE 7.
1613 A .3 Simplified design procedure. Not permitted by DSA-SS and OSHPD.
1613 A .4 Ballasted photovoltaic panel systems. Ballasted, roof-mounted photovoltaic panel systems need not be rigidly attached to the roof or supporting structure.
[DSA-SS] Ballasted, roof-mounted photovoltaic panel systems shall comply with ASCE 7, Section 13.6.12. [OSHPD 1 & 4] Ballasted photovoltaic panel systems shall be considered as an alternative system.
1613 A .5 Elevators, escalators and other conveying systems. Elevators, escalators and other conveying systems and their components shall satisfy the seismic requirements of ASCE 7 and ASME A17.1/CSA B44 as applicable.
1613 A .6 Automatic sprinkler systems. Where required, automatic sprinkler systems, including anchorage and bracing, shall comply with ASCE 7 and Section 903.3.1.1.
SECTION 1614 A —ATMOSPHERIC ICE LOADS
CBC § 4.1 High relevance — show source text
Mortar shall be Type M or S and masonry shall be laid in running bond.
b. Alternative reinforcing bar sizes and spacings having an equivalent cross-sectional area of reinforcement per lineal foot of wall shall be permitted provided the spacing of the
reinforcement does not exceed 72 inches in Seismic Design Categories A, B and C, and 48 inches in Seismic Design Categories D0, D1 and D2.
c. Vertical reinforcement shall be Grade 60 minimum. The distance,d, from the face of the soil side of the wall to the center of vertical reinforcement shall be not less than 5
inches.
d. Soil classes are in accordance with the Unified Soil Classification System and design lateral soil loads are for moist conditions without hydrostatic pressure. Refer to Table
R401.4.1(2).
e. Unbalanced backfill height is the difference in height between the exterior finish ground level and the lower of the top of the concrete footing that supports the foundation
wall or the interior finish ground level. Where an interior concrete slab-on-grade is provided and is in contact with the interior surface of the foundation wall, measurement of
the unbalanced backfill height from the exterior finish ground level to the top of the interior concrete slab is permitted.
f. The use of this table shall be prohibited for soil classifications not shown.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0.157 kPa/mm.
a. Mortar shall be Type M or S and masonry shall be laid in running bond.
b. Alternative reinforcing bar sizes and spacings having an equivalent cross-sectional area of reinforcement per lineal foot of wall shall be permitted provided the spacing of the
reinforcement does not exceed 72 inches in Seismic Design Categories A, B and C, and 48 inches in Seismic Design Categories D0, D1 and D2.
c. Vertical reinforcement shall be Grade 60 minimum. The distance,d, from the face of the soil side of the wall to the center of vertical reinforcement shall be not less than 5
inches.
d. Soil classes are in accordance with the Unified Soil Classification System and design lateral soil loads are for moist conditions without hydrostatic pressure. Refer to Table
R401.4.1(2).
e. Unbalanced backfill height is the difference in height between the exterior finish ground level and the lower of the top of the concrete footing that supports the foundation
wall or the interior finish ground level. Where an interior concrete slab-on-grade is provided and is in contact with the interior surface of the foundation wall, measurement of
the unbalanced backfill height from the exterior finish ground level to the top of the interior concrete slab is permitted.
f. The use of this table shall be prohibited for soil classifications not shown.|For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0.157 kPa/mm.
a. Mortar shall be Type M or S and masonry shall be laid in running bond.
b. Alternative reinforcing bar sizes and spacings having an equivalent cross-sectional area of reinforcement per lineal foot of wall shall be permitted provided the spacing of the
reinforcement does not exceed 72 inches in Seismic Design Categories A, B and C, and 48 inches in Seismic Design Categories D0, D1 and D2.
c. Vertical reinforcement shall be Grade 60 minimum.
Frequently asked questions
What CBC section defines earthquake loads and how to determine the seismic design category?
The CBC defines earthquake-load scope and the Seismic Design Category in §1613 and requires use of ASCE 7 for seismic procedures and site‑class considerations .
When does the CBC require additional seismic reinforcement for deep foundations or foundation walls?
Where a structure’s Seismic Design Category and load effects indicate seismic demand, the CBC requires seismic reinforcement for cast‑in‑place deep foundations in §1810.3.9.4 and places seismic limits and reinforcement requirements on foundation walls in §1807.1.6.2.1 .
Are plain concrete elements allowed in high seismic zones?
The CBC restricts structural plain concrete in Seismic Design Categories C, D, E and F; see §1905.6.2 for permitted exceptions and required reinforcement where plain concrete is limited .
More in California Building Code
- Administration & Permits
- Energy Efficiency
- Existing Buildings
- Occupancy Classification & Use
- Hazardous Materials & Occupancies
- Types of Construction
- Fire-Resistance & Fire Safety
- Interior Finishes
- Means of Egress
- Accessibility
- Exterior Walls
- Roofing & Roof Assemblies
- Structural Design
- Special Inspections & Tests
- Foundations & Soils
- Concrete
- Masonry
- Steel
- Wood
- Elevators & Conveying Systems
Ask about the CBC
Get cited, plain-English answers on the California Building Code for your project — any code section, any scenario.
Start Free Trial