CBC · California Building Code

Materials and specifications

This hub points you to the CBC chapters and sections that set material specs, required tests, product identification and referenced standards.

Last reviewed: July 5, 2026

Overview

This area of the California Building Code governs the required quality, testing, labeling and referenced standards for building materials and products used in construction — from concrete and gypsum to roof coverings and insulation. It tells designers, manufacturers, contractors and inspectors which test methods and product identifications are required to show compliance, and it ties those requirements to nationally recognized standards to ensure consistent performance and safety. See the code’s rules on referenced standards in Chapter 35 and the general specifications for tests and materials at §1903 §—Specifications for Tests and Materials .

The CBC organizes material requirements both by material type (for example, Chapter 25 on gypsum panel products and plaster) and by application (for example, roof-covering materials in §1506–1507), and it prescribes when special inspection or testing is required (see special inspections and tests provisions in Chapter 17/1705). For gypsum products and installation quality-control provisions, consult Chapter 25 ; for roof material specifications and product ID requirements, see §1506 and §1507 ; and for special inspection/testing duties tied to material quality, see Chapter 17/1705 .

In this section

Code references

Grounded in the retrieved California Building Code — click a citation to read the verbatim passage:

  • CBC § 25-1 High relevance — show source text

    2025 CALIFORNIA BUILDING CODE 25-1

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    25-2 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    25 GYPSUM PANEL PRODUCTS AND PLASTER

    User notes:

    About this chapter: Chapter 25 contains the provisions and referenced standards that regulate the design, construction and quality of gypsum panel products and plaster and, in addition, addresses reinforced gypsum concrete. These materials are some of the most commonly used interior and exterior finish materials in the building industry. This chapter primarily addresses qualitycontrol-related issues with regard to material specifications and installation requirements. Most products are manufactured in accordance with industry standards. The building official or inspector needs to verify that the appropriate product is used and properly installed for the intended use and location. Proper design and installation of these materials are necessary to provide weather resistance and required fire protection for both structural and nonstructural building components.

    ICC code development note: Code change proposals to sections preceded by the designation [BF] will be considered by a code development committee meeting during the 2024 (Group A) Code Development Cycle. All other code change proposals to this chapter will be considered by the IBC—Structural Code Development Committee during the 2025 (Group B) Code Development Cycle.

    SECTION 2501—GENERAL

    2501.1 Scope. Provisions of this chapter shall govern the materials, design, construction and quality of gypsum panel products, lath, gypsum plaster, cement plaster and reinforced gypsum concrete.

    2501.1.1 Application. [DSA-SS, DSA-SS/CC & OSHPD] The scope of application of Chapter 25 is as follows: 1. Applications listed in Sections 1.10.1, 1.10.2, 1.10.4 and 1.10.5 regulated by the Department of Health Care Access and Infor- mation/Office of Statewide Hospital Planning and Development (OSHPD). These applications include hospitals, hospital buildings removed from general acute care service, skilled nursing facility buildings, intermediate care facility buildings, correctional treatment centers and acute psychiatric hospital buildings. 2. Structures regulated by the Division of the State Architect—Structural Safety, which include those applications listed in Section 1.9.2.1 (DSA-SS) and 1.9.2.2 (DSA-SS/CC). These applications include public elementary and secondary schools, community colleges and state-owned or state-leased essential services buildings

    2501.1.2 Amendments in this chapter. [DSA-SS, DSA-SS/CC, OSHPD] DSA-SS, DSA-SS/CC, OSHPD adopt this chapter as amended. 1. OSHPD amendments appear in this chapter preceded with the appropriate acronym, as follows:

    [OSHPD 1] - For applications listed in Section 1.10.1.

    [OSHPD 1R] - For applications listed in Section 1.10.1.

    [OSHPD 2] - For applications listed in Section 1.10.2.

    [OSHPD 4] - For applications listed in Section 1.10.4.

  • CBC § 1505.7 High relevance — show source text

    [BF] 1505.7 Special purpose roofs. Special purpose wood shingle or wood shake roofing shall conform to the grading and application requirements of Section 1507.8 or 1507.9. In addition, an underlayment of [5] / 8 -inch (15.9 mm) Type X water-resistant gypsum backing board or gypsum sheathing shall be placed under minimum nominal [1] / 2 -inch-thick (12.7 mm) wood structural panel solid sheathing or 1-inch (25 mm) nominal spaced sheathing.

    [BF] 1505.8 Building-integrated photovoltaic (BIPV) systems. BIPV products installed as the roof covering shall be tested, listed and labeled for fire classification in accordance with Section 1505.1.

    [BF] 1505.9 Rooftop mounted photovoltaic (PV) panel systems. Rooftop mounted photovoltaic (PV) panel systems shall be tested, listed and identified with a fire classification in accordance with UL 2703. Listed systems shall be installed in accordance with the manufacturer’s installation instructions and their listing. The fire classification shall comply with Table 1505.1 based on the type of construction of the building.

    [BF] 1505.10 Landscaped and vegetative roofs. Landscaped and vegetative roofs shall comply with Sections 1505.1 and 1507.15. Vegetative roofs shall be installed in accordance with ANSI/SPRI VF-1.

    SECTION 1506—MATERIALS

    1506.1 Scope. The requirements set forth in this section shall apply to the application of roof-covering materials specified herein. Roof coverings shall be applied in accordance with this chapter and the roof covering listing as required by Section 1505. Installation of roof coverings shall comply with the applicable provisions of Section 1507.

    1506.2 Material specifications and physical characteristics. Roof-covering materials shall conform to the applicable standards listed in this chapter.

    15-6 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    ROOF ASSEMBLIES AND ROOFTOP STRUCTURES

    1506.3 Product identification. Roof-covering materials shall be delivered in packages bearing the manufacturer’s identifying marks and approved testing agency labels required in accordance with Section 1505. Bulk shipments of materials shall be accompanied with the same information issued in the form of a certificate or on a bill of lading by the manufacturer.

    SECTION 1507—REQUIREMENTS FOR ROOF COVERINGS

    1507.1 Scope. Roof coverings shall be applied in accordance with the applicable provisions of this section and the manufacturer’s installation instructions.

  • CBC § 1.2 High relevance — show source text

    1.2_||||||||X|X|X|X|X||X|X|||||||||| |2501.1.3||||||||X|X|X|X|X||X|X|||||||||| |2503.2||||||||X|X|X|X|X||X|X|||||||||| |2503.2, Exception||||||||||||X||||||||||||| |2504.2||||||||X|X|X|X|X||X|X|||||||||| |2504.2.1, Exception||||||||||||X||||||||||||| |2505.3||||||||X|X|X|X|X||X|X|||||||||| |2505.3, Exception||||||||||||X||||||||||||| |2507.3||||||||X|X|X|X|X||X|X|||||||||| |2507.3, Exception||||||||||||X||||||||||||| |2508.6.6||||||||X|X|X|X|X||X|X|||||||||| |2508.6.6, Exception||||||||||||X||||||||||||| |2510.6.3|||||||||||||||||||||X|||| |2514.1,Exception||||||||X||X|X|X||X|X||||||||||

    The state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.

    2025 CALIFORNIA BUILDING CODE 25-1

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    25-2 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    25 GYPSUM PANEL PRODUCTS AND PLASTER

    User notes:

    About this chapter: Chapter 25 contains the provisions and referenced standards that regulate the design, construction and quality of gypsum panel products and plaster and, in addition, addresses reinforced gypsum concrete. These materials are some of the most commonly used interior and exterior finish materials in the building industry. This chapter primarily addresses qualitycontrol-related issues with regard to material specifications and installation requirements. Most products are manufactured in accordance with industry standards. The building official or inspector needs to verify that the appropriate product is used and properly installed for the intended use and location. Proper design and installation of these materials are necessary to provide weather resistance and required fire protection for both structural and nonstructural building components.

    ICC code development note: Code change proposals to sections preceded by the designation [BF] will be considered by a code development committee meeting during the 2024 (Group A) Code Development Cycle. All other code change proposals to this chapter will be considered by the IBC—Structural Code Development Committee during the 2025 (Group B) Code Development Cycle.

    SECTION 2501—GENERAL

    2501.1 Scope. Provisions of this chapter shall govern the materials, design, construction and quality of gypsum panel products, lath, gypsum plaster, cement plaster and reinforced gypsum concrete.

    _**2501.1.1 Application.

  • CBC § 1507.7.5 High relevance — show source text

    1507.7.5

    C472—20: Standard Test Methods for Physical Testing of Gypsum, Gypsum Plasters and Gypsum Concrete

    Table 2506.2

    C473—2019: Standard Test Methods for Physical Testing of Gypsum Panel Products

    Table 2506.2

    C474—15(2020): Standard Test Methods for Joint Treatment Materials for Gypsum Board Construction

    Table 2506.2

    35-12 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    REFERENCED STANDARDS

    C475/C475M—2017: Specification for Joint Compound and Joint Tape for Finishing Gypsum Board

    Table 2506.2

    C514—04(2020): Standard Specification for Nails for the Application of Gypsum Board Table 721.1(2), Table 721.1(3), Table 2506.2

    C516—19: Specifications for Vermiculite Loose Fill Thermal Insulation

    722.3.1.4, 722.4.1.1.3

    C547—19: Specification for Mineral Fiber Pipe Insulation Table 721.1(2), Table 721.1(3)

    C549—18: Specification for Perlite Loose Fill Insulation

    722.3.1.4, 722.4.1.1.3

    C552—22: Standard Specification for Cellular Glass Thermal Insulation

    Table 1508.2

    C557—2003(2017): Specification for Adhesives for Fastening Gypsum Wallboard to Wood Framing Table 2506.2, 2508.4

    C578—19: Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation Table 1404.5.2.1, Table 1404.5.2.2, 1404.5.3.1, Table 1404.5.3.2, Table 1508.2, 2603.10

    C587—2004(2018): Specification for Gypsum Veneer Plaster

    Table 2507.2

    C595/C595M—21: Specification for Blended Hydraulic Cements 1909.2.2, 1910A.1, Table 2507.2

    C618—23e1: Standard Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in Concrete

    1909.2.2, 1910A.1

    C631—2020: Standard Specification for Bonding Compounds for Interior Gypsum Plastering

    Table 2507.2

    C635/C635M—2017: Specification for the Manufacture, Performance and Testing of Metal Suspension Systems for Acoustical Tile and Lay-In Panel Ceilings

    2506.2.1

    C635/C635M— 22 : Standard Specification for the Manufacture, Performance and Testing of Metal Suspension Systems for Acoustical Tile and Lay-In Panel Ceilings

    2506.2.1, 1617A.1.21

    C636/C636M—19: Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels

    808.1.1.1, 1617.11.16, 1617A.1.21

    C652—21: Specification for Hollow Brick (Hollow Masonry Units Made from Clay or Shale)

  • CBC § 12-7 High relevance — show source text

    FIGURE 1 TEST FIGURE SCHEMATIC

    FIGURE 2 GAS BURNER IGNITION SOURCE

    12-7A-1.7 Test assembly.

    1. Dimensions. The test specimen's dimensions shall be 4 feet wide by 8 feet high (1220 mm by 2440 mm). The test specimen shall be representative of the end-use wall assembly except as specified in Items 3 and 4. The test specimen shall be mounted in the steel frame holding fixture assembly as shown in Figure 1.
    2. Joint details. The test specimen shall incorporate joint detail(s) representative of actual installation.
    3. Wall assemblies without internal cavity spaces. For wall assemblies without internal cavity spaces, the entire wall assembly shall constitute the test specimen to be tested. The wall assembly shall be constructed in accordance with manufacturer’s

    38 2025 CALIFORNIA REFERENCED STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MATERIALS AND CONSTRUCTION METHODS FOR EXTERIOR WILDFIRE EXPOSURE

    specifications and/or building code requirements, where applicable. Other components of the wall assembly, such as building felt and sheathing, are employed to conform to the manufacturer’s specifications and/or building codes. 4. Wall assemblies with internal cavity spaces. For wall assemblies with internal cavity spaces, the materials on what would be considered the interior (unexposed) side of the wall assembly shall be omitted from the test specimen. Materials such as insulation normally installed within the cavity space shall be omitted from the test specimen. The wall assembly used as the test specimen shall include the structural support elements and any sheathing, weather barrier and cladding attached to the exterior surface of the structural support elements. 5. Layered materials. For wall assemblies composed of layered materials, such as sheathing, siding (cladding) and underlayment, the installation of such layered materials shall be in accordance with the manufacturer’s instructions, or in the absence of such instructions, applicable building code requirements. In the absence of manufacturer’s specifications, the wall assembly shall include the following minimum components: nominal 2 x 4 studs spaced 16 inches (410 mm) on center, and the desired exterior siding material. If sheathing is used, tests shall be run on typical [7] / 16 -inch (11 mm) oriented strandboard (OSB) of Exposure 1 rating. Where specified by the manufacturer, sheathing material and installation shall be in accordance with the manufacturer’s instructions. The sheathing shall have one vertical seam on a selected stud with a 0.125 inch (3 mm) gap. 6. Edge protection. Protect the vertical and horizontal edges of the test specimen with 12-mm-thick ceramic wool blanket (or equivalent) to eliminate the gap between the holder and the test specimen and prevent unwanted edge effects caused by heat transfer to the edges of the test specimen through the sample holder. 7. Replicates. Three matched test specimen assemblies shall be tested. 8. Pre-test conditioning of test specimens. The completed test specimens are to be stored indoors at temperatures not lower than 60°F (16°C) nor higher than 90°F (32°C) for the period of time necessary to cure or condition the assembly components. Test specimens are to be stored so that each will be surrounded by freely circulating air.

  • CBC § 11B-809.10.6.4 High relevance — show source text

    11B-809.10.6.4 Reinforcement for grab bars. Reinforcement for grabs bars shall comply with the following: Continuous rein- forcement shall be installed in the walls of showers 30 inches (762 mm) maximum to 38 inches (965 mm) minimum above the finish floor. The grab bar reinforcement shall be 8 inches (203 mm) minimum in height. Glass-walled shower stalls shall provide rein- forcement for installation of floor-mounted or ceiling-mounted grab bars.

    FIGURE 11B-809.10.6.4—REINFORCEMENT FOR GRAB BARS

    11B-809.10.6.5 Thresholds. Where provided thresholds shall be 2 inches (51 mm) maximum in height and have a beveled or sloped angle not exceeding 1 unit vertical in 2 units horizontal (26.6 degrees from the horizontal). Thresholds [1] / 2 inch (12.7 mm) or less in height shall have a beveled or sloped angle not exceeding 1 unit vertical in 1 unit horizontal (45 degrees from the horizontal).

    11B-809.10.6.6 Controls. Controls and operating mechanisms shall comply with Section 11B-309.4.

    11B-809.10.6.7 Shower enclosures. Doors and panels of shower enclosures shall comply with Section 11B-809.10.5.4.

    11B-809.10.7 Water closets. Water closets required by Section 11B-809.10 shall comply with this section.

    11B-809.10.7.1 Floor space. The floor space at water closets shall be 48 inches (1219 mm) wide minimum measured perpendicu- lar to the side wall. A floor space 48 inches (1219 mm) wide minimum by 36 inches (914 mm) deep minimum shall be provided in front of the water closet.

    Exception: The 48-inch (1219 mm) minimum clear width may be reduced to 36 inches (914 mm) minimum for lavatories, cabi- nets, wing walls or privacy walls located immediately adjacent to a water closet which extend 24 inches (610 mm) maximum in depth.

    11B-126 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    ACCESSIBILITY TO PUBLIC BUILDINGS, PUBLIC ACCOMMODATIONS, COMMERCIAL BUILDINGS AND PUBLIC HOUSING

    FIGURE 11B-809.10.7.1—FLOOR SPACE

    11B-809.10.7.2 Location. Water closets shall be located within bathrooms in a manner that permits a grab bar to be installed on at least one side of the fixture. The centerline of the water closet shall be 17 inches (432 mm) minimum to 18 inches (457 mm) maxi- mum from a wall or partition that is 54 inches (1372 mm) minimum in length. In locations where water closets are adjacent to other walls, vanities, lavatories or bathtubs, the centerline of the fixture shall be 18 inches (457 mm) minimum from the obstacle.

    11B-809.10.7.3 Reinforcement for grab bars. Reinforcement for grabs bars shall comply with the following:

  • CBC § 1703.4.1 High relevance — show source text

    1703.4.1 Polyethylene (PE). Polyethylene pipe or tubing shall be manufactured in accordance with the standards listed in Table 1703.2. Pipe or tubing shall have a minimum wall thickness equal to SDR-11 and shall have a minimum pressure rating of not less than 160 psi (1103 kPa) at 73°F (23°C).

    Polyethylene pipe and tubing shall be manufactured from a PE compound that has a pipe material designation code of PE 3608, PE 3708, PE 3710, PE 4608, PE 4708, or PE 4710 as defined in the applicable standards referenced in Table 1703.2, with a cell classification in accordance with ASTM D3350 appropriate for the material designation code, and a color and ultraviolet stabilizer code of C or E. Code E compounds shall be stabilized against deterioration from unprotected exposure to ultraviolet rays for not less than 3 years in accordance with the test criteria specified in ASTM D2513.

    1703.4.1.1 Joining Methods for Polyethylene Pipe or Tubing. Joints between high density polyethylene (HDPE) plastic pipe or tubing and fittings shall be installed in accordance with the manufac

    TABLE 1701.11.1

    WATER QUALITY [1]

    WATER QUALITY TABLE 1703.3

    GROUND SOURCE LOOP PIPE FITTINGS

    PARAMETER ACCEPTABLE RANGE

    Ammonium
    < 2 ppm

    Chlorides2
    < 125 ppm


    (Free CO2)3
    < 50 ppm


    pH
    7.0 – 8.5

    Sulphates
    < 125 ppm

    TDS
    10 – 1000 ppm

    Total Hardness
    < 150 ppm

    Notes: 1 Where chemical additives are used, the acceptable ranges provided shall be in accordance with the equipment manufacturer’s specifications, or this table, whichever is more stringent. 2 The provided acceptable range for chlorides is dependent upon the system heat exchanger and piping materials. See the manufacturer’s specifications for equipment and materials used. 3 The limit provided pertains to makeup water.

    «

    «

    «

    «

    «

    »»

    »

    »

    backflow prevention device. The connection of a discharge line to the sanitary or storm sewer system, or private sewage disposal system, shall be in accordance with the plumbing code or in accordance with the Authority Having Jurisdiction.

    TABLE 1701.11.1

    WATER QUALITY [1]

    Notes: 1 Where chemical additives are used, the acceptable ranges provided shall be in accordance with the equipment manufacturer’s specifications, or this table, whichever is more stringent. 2 The provided acceptable range for chlorides is dependent upon the system heat exchanger and piping materials. See the manufacturer’s specifications for equipment and materials used. 3 The limit provided pertains to makeup water.

    1703.0 Design of Systems.

    1703.1 Ground-Heat Exchanger Design. The groundheat exchanger design shall be provided by a licensed professional or a designer with the appropriate certifications or credentials as defined by the Authority Having Jurisdiction.

  • CBC § 19-5 High relevance — show source text

    1903 Specifications for Tests and Materials . . . . . . . . . . . 19-5

    1904 Durability Requirements . . . . . . . . . . . . . . . . . . . . . . . 19-6

    1905 Seismic Requirements . . . . . . . . . . . . . . . . . . . . . . . . . 19-6

    1906 Footings for Light-Frame Construction . . . . . . . . . . 19-8

    1907 Slabs-on-Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-8

    1908 Shotcrete. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-8

    1909 Additional Requirements for Community Colleges

    [DSA-SS/CC]. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19-8

    1910 Additional Requirements for Skilled Nursing Facilities, Intermediate Care Facilities, Acute Psychiatric and Non-GAC Buildings

    [OSHPD 1R, 2 & 5]. . . . . . . . . . . . . . . . . . . . . . . . . . . . .19-12

    1911 Existing Concrete Structures [OSHPD 1R, 2 & 5]. . . . . . .19-13

    CHAPTER 19A CONCRETE . . . . . . . . . . . . . . . . . . . . . . . . . . 19A-1

    1901A General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19A-3

    1902A Coordination of Terminology . . . . . . . . . . . . . . . . . . . .19A-4

    1903A Specifications for Tests and Materials . . . . . . . . . . . .19A-4

    1904A Durability Requirements . . . . . . . . . . . . . . . . . . . . . . . .19A-4

    1905A Seismic Requirements . . . . . . . . . . . . . . . . . . . . . . . . . .19A-4

    1906A Reserved . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19A-5

    1907A Slabs-on-Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19A-5

    1908A Shotcrete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19A-6

    1909A Modifications to ACI 318. . . . . . . . . . . . . . . . . . . . . . . . .19A-6

  • CBC § 1901.7.1 High relevance — show source text

    1901.7.1 Cast-in-place concrete tolerances. Structural tolerances for cast-in-place concrete structural elements shall be in accordance with ACI 117.

    Exceptions:

    1. Group R-3 detached one- or two-family dwellings are not required to comply with this section.
    2. Shotcrete is not required to comply with this section.

    1901.7.2 Precast concrete tolerances. Structural tolerances for precast concrete structural elements shall be in accordance with ACI ITG-7.

    Exception: Group R-3 detached one- or two-family dwellings are not required to comply with this section.

    SECTION 1902—COORDINATION OF TERMINOLOGY

    1902.1 General. Coordination of terminology used in ACI 318 and ASCE 7 shall be in accordance with Section 1902.1.1.

    1902.1.1 Design displacement. Design displacement shall be the Design Earthquake Displacement, δ DE, defined in ASCE 7 Section 12.8.6.3. For diaphragms that can be idealized as rigid in accordance with ASCE 7 Section 12.3.1.2, δ di, displacement due to diaphragm deformation corresponding to the design earthquake, is permitted to be taken as zero.

    SECTION 1903—SPECIFICATIONS FOR TESTS AND MATERIALS

    1903.1 General. Materials used to produce concrete, concrete itself and testing thereof shall comply with the applicable standards listed in ACI 318.

    Exception: The following standards as referenced in Chapter 35 shall be permitted to be used.

    1. ASTM C150

    2. ASTM C595

    3. ASTM C1157

    1903.2 Glass fiber-reinforced concrete. Glass fiber-reinforced concrete (GFRC) and the materials used in such concrete shall be in accordance with the PCI 128.

    1903.3 Flat wall insulating concrete form (ICF) systems. Insulating concrete form material used for forming flat concrete walls shall conform to ASTM E2634. [OSHPD 1R, 2 & 5] Not Permitted by OSHPD.

    1903.4 Steel fiber reinforcement - [OSHPD 1R, 2 & 5] Not permitted by OSHPD.

    2025 CALIFORNIA BUILDING CODE 19-5

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CONCRETE

    1903.5 Welding of reinforcing bars - [OSHPD 1R, 2 & 5] Modify ACI 318 Section 26.6.4.1(b) by adding the following:

  • CBC § 4005.2.1.1 Medium relevance — show source text

    4005.2.1.1 Elevated walkways. Where provided, elevated walkways between barrels shall be constructed in accordance with one of the following:

    1. Noncombustible materials that are 50 percent open.
    2. Noncombustible materials that are open less than 50 percent, provided that the walkway has a maximum width of 1 foot (305 mm) and a minimum gap of 3 inches (76 mm) is provided between the walkway and the barrel storage.
    3. Combustible materials that are provided with a row of automatic sprinklers directly beneath each walkway.

    4005.2.2 Flue spaces for on-end wooden barrels. Rack storage arrangements with on-end wooden barrels shall be provided with transverse and longitudinal flue spaces with a minimum width of 6 inches (152 mm).

    4005.2.3 Fire protection for rack storage. Rack storage arrangements of alcohol-water mixtures up to 75 percent alcohol in wooden barrels with sizes not exceeding 130 gallons (492 L) shall be protected in accordance with Sections 4005.2.3.1 through 4005.2.3.6.

    4005.2.3.1 Hose stream allowance. The automatic sprinkler system design shall include a 500-gallon-per-minute (1900 L/min) hose stream allowance.

    4005.2.3.2 Water supply duration. The automatic sprinkler system water supply duration, including hose stream demand, shall be a minimum of 1 hour.

    4005.2.3.3 Dry-pipe automatic sprinkler system. Where dry-pipe automatic sprinkler systems are installed, the automatic sprinkler system shall be designed to deliver water to the most remote four sprinklers within 40 seconds.

    2025 CALIFORNIA FIRE CODE 40-5

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    STORAGE OF DISTILLED SPIRITS AND WINES

    4005.2.3.4 Ceiling automatic sprinkler systems. The automatic sprinkler systems installed at the ceiling shall be designed with a minimum density of 0.2 gallon per minute (0.8 L/min) per square foot with an operating area of 2,000 square feet (186 m [2] ).

    4005.2.3.5 Automatic sprinkler system balancing. The automatic sprinkler system installed at the ceiling and the in-rack sprinkler system shall be balanced at the point of connection.

    4005.2.3.6 Automatic sprinkler system design. The design of the automatic sprinkler system at the ceiling and the in-rack sprinkler system shall be in accordance with Table 4005.2.3.6.

    |TABLE 4005.2.3.6—RACK STORAGE OF DISTILLED SPIRITS IN WOODEN

  • CBC § 1701.1 Medium relevance — show source text

    Chapter 16 Nonpotable Rainwater Catchment Systems.

    Chapter 16 regulates nonpotable rainwater catchment systems that include irrigation; toilet and urinal flushing with proper treatment; provisions where permits are required; maintenance of alternate water sources; and minimum water quality. This chapter provides guidance on how to optimize rainwater use while ensuring there is a decrease of risk to consumers from poor design, installation, and maintenance. Rainwater harvesting is the process of capturing, channeling, and storing water runoff for later use. Most systems are constructed of three principal components: the catchment area, the collection device, and the conveyance system.

    Chapter 17 Referenced Standards.

    Chapter 17 provides two comprehensive tables with referenced standards. The standards listed in Table 1701.1 are applied as indicated in the applicable reference section(s). A list of additional approved standards, publications, practices, and guides that are not referenced in specific sections appear in Table 1701.2.

    Referenced standards set forth specific details of accepted practices, materials specifications, or test methods in many specialized applications. Standards provide an efficient method of conveying complex information and specifications on the performance requirements for materials, products, systems, application, and installation. The manner and purpose for a standard’s use and, in turn, code compliance, must be definitive in all references to the standard. If the standard is intended to be a requirement for judging code compliance, the code must state its intent for use. The standard should adequately address a defined need and at the same time specify the minimum performance requirements, technical characteristics and methods of testing, and required test results.

    The referenced standards tables are organized in a manner that makes it easy to find specific standards in alphabetical order, and by acronym of the publishing agency of the standard. The tables list the title of the standard, the edition, and any addenda. Contact information for each publishing agency is provided at the end of the chapter.

    Appendix A Recommended Rules for Sizing the Water Supply System.

    Appendix A provides a method of sizing the water supply and distribution system that provides precise calculations to establish the proper pressures and flow to the system’s fixtures. The goal of sizing the system is to deliver an acceptable volume of water to the most hydraulically remote fixture during minimum pressure and maximum flow conditions; provide satisfactory water pressure to the most hydraulically remote fixture during minimum pressure and maximum flow conditions; and to prevent excessive water velocity during maximum flow conditions.

    Appendix B Explanatory Notes on Combination Waste and Vent Systems.

    Appendix B contains general guidelines for the design and installation of combination waste and vent systems. These systems are designed for waste piping and are purposely oversized to serve as both a waste and vent pipe to avoid excessive pneumatic effects at fixture drains.

    Appendix C Alternate Plumbing Systems.

    The intent of this appendix is to provide clarification of procedures for the design and approval of engineered plumbing systems, alternate materials, and equipment that are not specifically covered in other parts of the code. Alternative methods are allowed to be used where approved by the authority having jurisdiction. Approval of alternatives is based on a demonstration showing that the method or material used is at least equivalent in strength, deflection, and capacity to that provided by the prescriptive methods and materials.

    Appendix D Sizing Storm Water Drainage Systems.

    Appendix D provides general guidelines for the sizing of stormwater drainage systems. There are two pieces of information that must always be a given. They are the roof size and the rate of rainfall f

  • CBC § 12-7 Medium relevance — show source text

    CHAPTER 12-7-1 FIRE-RESISTIVE STANDARDS. . . . . . . . . . 13

    CHAPTER 12-7-2 FIRE-RESISTIVE STANDARDS

    RESERVED . . . . . . . . . . . . . . . . . . . . . . . . . 23

    CHAPTER 12-7-3 FIRE-RESISTIVE STANDARDS. . . . . . . . . . 25

    CHAPTER 12-7-4 FIRE-RESISTIVE STANDARDS. . . . . . . . . . 31

    CHAPTER 12-7-5 FIRE-RESISTIVE STANDARDS. . . . . . . . . . 35

    CHAPTER 12-7A MATERIALS AND CONSTRUCTION

    METHODS FOR EXTERIOR WILDFIRE

    EXPOSURE . . . . . . . . . . . . . . . . . . . . . . . . . 37

    CHAPTER 12-8-1 FIRE-RESISTIVE STANDARDS FOR

    FIRE PROTECTION . . . . . . . . . . . . . . . . . . 51

    APPENDIX 12-8-1A CALCULATION OF THE TOTAL RATE

    OF HEAT AND CARBON MONOXIDE OR

    CARBON DIOXIDE PRODUCTION . . . . . . . 63

    APPENDIX 12-8-1B GUIDE TO MOUNTING TECHNIQUES FOR

    WALL AND CEILING INTERIOR FINISH

    MATERIAL. . . . . . . . . . . . . . . . . . . . . . . . . . 67

    CHAPTER 12-10-1 EXITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

    CHAPTER 12-10-2 EXITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

    CHAPTER 12-10-3 EXITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

    CHAPTERS 12-11A AND 12-11B

    BUILDING AND FACILITY ACCESS

    SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . 85

    CHAPTER 12-12 RESERVED . . . . . . . . . . . . . . . . . . . . . . . . . 87

    CHAPTER 12-13 STANDARDS FOR INSULATING

    MATERIAL. . . . . . . . . . . . . . . . . . . . . . . . . . 89

    CHAPTER 12-16-1 ENGINEERING REGULATIONS—QUALITY

    AND DESIGN OF THE MATERIALS OF

    CONSTRUCTION . . . . . . . . . . . . . . . . . . . 101

    CHAPTER 12-16-2 ENGINEERING REGULATIONS—QUALITY

    AND DESIGN OF THE MATERIALS OF

    CONSTRUCTION . . . . . . . . . . . . . . . . . . . 103

Frequently asked questions

What section lists the standards the CBC uses for material specifications?

Referenced standards are collected in Chapter 35 (Referenced Standards), which lists the editions and where each standard is applied in the code .

Where are concrete material and test requirements found?

Concrete materials and test requirements are addressed in Chapter 19 (and Chapter 19A for certain concrete topics) with general specifications at §1903—Specifications for Tests and Materials and related ACI references incorporated by the code .

How does the CBC require products be identified on delivery?

Some chapters require product identification and listing/labeling — for example roof-covering materials must be delivered with manufacturer marks and approved testing‑agency labels as required in §1506–1507 .

More in California Building Code

Ask about the CBC

Get cited, plain-English answers on the California Building Code for your project — any code section, any scenario.

Start Free Trial

Related in the CBC