CBC · California Building Code

What are the owner's responsibilities to maintain fire‑resistance‑rated construction?

As a building owner you must keep a list of required fire‑resistance‑rated elements, visually inspect them at least once a year, repair any damage or penetrations with systems that restore the original rating, and keep inspection and repair records; concealed spaces need not be opened for inspection unless they are accessible by a removable panel or tile.

Last reviewed: July 5, 2026

What the code requires — 2-4 sentences

The owner is responsible for keeping required fire‑resistance‑rated construction and assemblies (for example structural members, exterior walls, fire walls/barriers/partitions, horizontal assemblies and shaft enclosures) in the condition and with the fire resistance for which they were installed. The owner must keep an inventory of those elements, visually inspect them at least once a year, and promptly repair, restore or replace any element that is damaged, altered, breached or penetrated. These duties are set out in § 701.2, § 701.5 and § 701.6 of the CBC, with recordkeeping required by § 701.6.1 and Section 110.3.

Requirements in detail

Which elements must be maintained

  • Structural members, exterior walls, fire walls, fire barriers and fire partitions, horizontal assemblies (floor/ceiling and roof/ceiling assemblies) and shaft enclosures — the fire‑resistance rating of each of these must be maintained. See § 701.2.

  • Smoke barriers and smoke partitions: their fire‑resistance rating and smoke‑resistant characteristics must be maintained as required by the chapter. See §§ 701.3–701.4.

Inspection obligation and frequency

  • Owner must maintain an inventory of all required fire‑resistance‑rated construction and of the other constructions described in Sections 703–707 and §§ 602.4.1 and 602.4.2. That inventory must be visually inspected by the owner annually. Concealed elements need not be visually inspected unless the concealed space is accessible by moving or removing a panel, access door, ceiling tile or similar movable entry. See § 701.6.

Repair / restoration standard

  • Materials, systems and devices used to repair or protect breaches and openings in fire‑resistance‑rated construction and construction installed to resist the passage of smoke must be maintained in accordance with Sections 703 through 707. In short: repairs must restore the fire‑resistance and smoke‑resistance characteristics — use materials/systems that meet or exceed the requirements that applied when the assembly was constructed, remodeled or altered. See § 701.5 and related repair provisions referenced in Chapter 7.

Recordkeeping

  • Records of all required inspections, testing, repairs and maintenance must be kept in accordance with Section 110.3. See § 701.6.1.

Decision‑relevant summary table

Element / item Owner action required Frequency / value Code reference
Structural members Maintain fire‑resistance rating; repair/restore if damaged Annual visual inventory/inspection; repair when needed § 701.2
Exterior walls Maintain fire‑resistance rating Annual visual inventory/inspection; repair when needed § 701.2
Fire walls / fire barriers / fire partitions Maintain rating and continuity (no unprotected breaches) Annual visual inventory/inspection; repair when needed § 701.2
Horizontal assemblies (floor/ceiling, roof/ceiling) Maintain rating; no hanging decorations from acoustical ceilings that are part of rated horizontals Annual visual inventory/inspection; no hanging displays from acoustical ceilings § 701.2, § 701.2.1
Shaft enclosures Maintain rating; limit openings and protect penetrations Annual visual inventory/inspection; repair when needed § 701.2
Penetrations, joints, opening protectives Maintain protection; repair/replace with systems meeting Chapters 703–707 Maintain per Sections 703–707; replace with equal or better systems § 701.5; see Sections 703–707
Inventory & records Keep inventory; retain inspection/repair records per § 110.3 Annual inspection; records retained per § 110.3 § 701.6, § 701.6.1

Exceptions & special cases

  • Concealed elements: the owner is not required to visually inspect elements that are concealed unless the concealed space can be accessed by removing a panel, access door, ceiling tile or similar movable entry to the space. (So a ceiling cavity that would require demolition or permanent removal for access is exempt from the annual visual inspection requirement until made accessible.) See § 701.6.

  • Hanging displays: the code specifically prohibits hanging display materials from acoustical ceiling systems that are part of a fire‑resistance‑rated horizontal assembly; owners should prohibit tenants/occupants from doing so. See § 701.2.1.

  • Repair performance standard: where repairs are made to penetrations, joints or other protective systems, the repair materials/systems must meet the requirements of Sections 703–707 or otherwise meet or exceed the code requirements applicable when the assembly was constructed, remodeled or altered. See § 701.5 and the repair provisions referenced in Chapter 7.

Common mistakes

  • Treating inspection as a one‑time or ad‑hoc activity instead of an annual, documented duty (owner must inspect annually and keep records per § 701.6 and § 701.6.1).
  • Failing to keep an accurate inventory — the code requires the owner to maintain an inventory of all required rated construction and the items covered in Sections 703–707. § 701.6.
  • Repairing breaches with non‑tested or ad hoc materials that do not restore the rated assembly — repairs must be to systems that meet the applicable code requirements or listings. § 701.5 (and Chapters 703–707).
  • Assuming “concealed” means “never inspect” — the concealed‑space exception applies only when the space is not accessible by normal removable access (panels, tiles, doors). § 701.6.
  • Relying on tenants or vendors without supervision/documentation — the owner has the statutory responsibility to maintain inventory, inspections and records (delegation is possible but the owner remains accountable). § 701.6 and § 701.6.1.

Worked example — five‑story office building (concrete example with actions and numbers)

Scenario: You own a five‑story office building with rated floor/ceiling assemblies and two shaft enclosures. During a tenant fit‑out on the 3rd floor an electrician installs three new conduits through a fire barrier, leaving three 1.5‑inch gaps around the conduits (total unprotected penetrations ≈ 3 × 1.5″ dia.). Action plan consistent with the CBC:

  1. Inventory & inspection: Confirm the fire barrier is on the building inventory and note the location. The owner’s annual visual inspection (required by § 701.6) identifies the new penetrations. § 701.6.

  2. Immediate assessment: Because the penetrations breach a rated fire barrier, they must be protected. § 701.5 requires that materials/systems used to repair breaches be maintained in accordance with Sections 703–707 (i.e., use an appropriate listed through‑penetration firestop system that restores the original fire‑resistance rating). § 701.5.

  3. Repair: Engage a qualified installer to install a listed through‑penetration firestop system rated to at least the same fire‑resistance as the barrier. Install and label per the tested system and manufacturer instructions.

  4. Document: Record the inspection finding, the repair performed, the system/listing used, installer name and date in the owner’s records in accordance with § 701.6.1 and Section 110.3. Keep the record with the building maintenance file. § 701.6.1.

  5. Follow up: At the next annual inspection confirm that the firestop remains in place and intact; if modified again, repeat the assessment and repair. § 701.6.

This sequence satisfies the CBC’s requirement that rated assemblies be visually inspected annually by the owner and be properly repaired where breached. § 701.6; § 701.5; § 701.6.1.

Related provisions

  • § 701.1 — Scope of Chapter 7 (inspection and maintenance of fire‑resistance‑rated assemblies).
  • § 701.2 — Fire‑resistance‑rated construction that must be maintained (structural members, exterior walls, fire walls/barriers/partitions, horizontal assemblies, shaft enclosures).
  • § 701.5 — Maintaining protection; repairs and protection of breaches and openings; requires compliance with Sections 703–707.
  • § 701.6 — Owner’s responsibility to inventory, inspect annually and repair/restore/replace rated construction.
  • § 701.6.1 — Recordkeeping: inspection/testing/repair records to be maintained per Section 110.3.
  • Sections 703–707 — Detail requirements for penetrations, joints, opening protectives and other fire/smoke protection features that must be maintained/used for repairs.
  • Section 110.3 — Administrative requirement referenced by § 701.6.1 for retention of inspection/testing/repair records.

Code references

Grounded in the retrieved California Building Code — click a citation to read the verbatim passage:

  • CBC § 1.11. High relevance — show source text
    • The California Code of Regulations (CCR), Title 19, Division 1 provisions that are found in the California Fire Code are a reprint from the current CCR, Title 19, Division 1 text for the code user’s convenience only. The scope, applicability and appeals procedures of CCR, Title 19, Division I remain the same. The state agency does not adopt sections identified by the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.

    2025 CALIFORNIA FIRE CODE 7-1

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    7-2 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    7 FIRE AND SMOKE PROTECTION FEATURES

    User notes:

    About this chapter: Chapter 7 provides requirements to maintain the fire-resistance ratings of building elements and to limit fire spread. Section 701 addresses the maintenance of and owner’s responsibility for construction elements such as fire barriers and smoke barriers. The rest of the chapter deals with various aspects that also must be maintained to achieve overall fire resistance of the main fire- and smoke-resistive features. These include penetrations, joint protection, door and window openings, and duct and air transfer opening protection.

    SECTION 701—GENERAL

    701.1 Scope. The provisions of this chapter shall govern the inspection and maintenance of the materials, systems and assemblies used for structural fire resistance, fire-resistance-rated construction separation of adjacent spaces and construction installed to resist the passage of smoke to safeguard against the spread of fire and smoke within a building and the spread of fire to or from buildings. New buildings shall comply with the California Building Code.

    701.2 Fire-resistance-rated construction. The fire-resistance rating of the following fire-resistance-rated construction shall be maintained:

    1. Structural members.

    2. Exterior walls.

    3. Fire walls, fire barriers, fire partitions.

    4. Horizontal assemblies.

    5. Shaft enclosures.

    701.2.1 Hanging displays. The hanging and displaying of salable goods and other decorative materials from acoustical ceiling systems that are part of a fire-resistance-rated horizontal assembly shall be prohibited.

    701.3 Smoke barriers. The fire-resistance rating and smoke-resistant characteristics of smoke barriers shall be maintained.

    701.4 Smoke partitions. The smoke-resistant characteristics of smoke partitions shall be maintained.

    701.5 Maintaining protection. Materials, systems and devices used to repair or protect breaches and openings in fire-resistance-rated construction and construction installed to resist the passage of smoke shall be maintained in accordance with Sections 703 through 707.

    701.6 Owner’s responsibility. The owner shall maintain an inventory of all required fire-resistance-rated construction, construction installed to resist the passage of smoke and the construction included in Sections 703 through 707 and Sections 602.4.1 and 602.4.2 of the California Building Code . Such construction shall be visually inspected by the owner annually and properly repaired, restored or replaced where damaged, altered, breached or penetrated. Where concealed, such elements shall not be required to be visually inspected by the owner unless the concealed space is accessible by the removal or movement of a panel, access door, ceiling tile or similar movable entry to the space.

  • CBC § 701.2 High relevance — show source text

    701.2 Fire-resistance-rated construction. The fire-resistance rating of the following fire-resistance-rated construction shall be maintained:

    1. Structural members.

    2. Exterior walls.

    3. Fire walls, fire barriers, fire partitions.

    4. Horizontal assemblies.

    5. Shaft enclosures.

    701.2.1 Hanging displays. The hanging and displaying of salable goods and other decorative materials from acoustical ceiling systems that are part of a fire-resistance-rated horizontal assembly shall be prohibited.

    701.3 Smoke barriers. The fire-resistance rating and smoke-resistant characteristics of smoke barriers shall be maintained.

    701.4 Smoke partitions. The smoke-resistant characteristics of smoke partitions shall be maintained.

    701.5 Maintaining protection. Materials, systems and devices used to repair or protect breaches and openings in fire-resistance-rated construction and construction installed to resist the passage of smoke shall be maintained in accordance with Sections 703 through 707.

    701.6 Owner’s responsibility. The owner shall maintain an inventory of all required fire-resistance-rated construction, construction installed to resist the passage of smoke and the construction included in Sections 703 through 707 and Sections 602.4.1 and 602.4.2 of the California Building Code . Such construction shall be visually inspected by the owner annually and properly repaired, restored or replaced where damaged, altered, breached or penetrated. Where concealed, such elements shall not be required to be visually inspected by the owner unless the concealed space is accessible by the removal or movement of a panel, access door, ceiling tile or similar movable entry to the space.

    701.6.1 Recordkeeping. Records of all required system inspections, testing, repairs and maintenance shall be maintained in accordance with Section 110.3.

    701.7 Unsafe conditions. Where any components in this chapter are not maintained and do not function as intended or do not have the fire resistance or the resistance to the passage of smoke required by the code under which the building was constructed, remodeled or altered, such component(s) or portion thereof shall be deemed an unsafe condition, in accordance with Section 115.1.1. Components or portions thereof determined to be unsafe shall be repaired or replaced to conform to that code under which the building was constructed, remodeled or altered or this chapter, as deemed appropriate by the fire code official.

    Where the condition of components is such that any building, structure or portion thereof presents an imminent danger to the occupants of the building, structure or portion thereof, the fire code official shall act in accordance with Section 115.2.

    SECTION 702—DEFINITIONS

    702.1 Definitions. The following terms are defined in Chapter 2:

    DRAFTSTOP.

    FIREBLOCKING.

    MEMBRANE-PENETRATION FIRESTOP SYSTEM.

    OPENING PROTECTIVE.

    SMOKE BARRIER.

    SMOKE PARTITION.

    THROUGH-PENETRATION FIRESTOP SYSTEM.

    2025 CALIFORNIA FIRE CODE 7-3

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE AND SMOKE PROTECTION FEATURES

    SECTION 703—PENETRATIONS

  • CFC § 701 High relevance — show source text

    Chapter 7 Fire and Smoke Protection Features

    The maintenance of assemblies required to be fire-resistance rated is a key component in a passive fire protection philosophy. Chapter 7 sets forth requirements to maintain required fire-resistance ratings of building elements and limit fire spread. Section 701 addresses the basics of what construction elements such as fire barriers and smoke barriers need to be maintained as well as defining the owner’s responsibility. Sections 703 through 708, deals with various fire and smoke protection features that must also be maintained.

    xiv 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    Chapter 8 Interior Finish, Decorative Materials and Furnishings

    The overall purpose of Chapter 8 is to regulate interior finishes, decorative materials and furnishings in new and existing buildings so that they do not significantly add to or create fire hazards within buildings. This chapter is consistent with Chapter 8 of the CBC, which regulates the interior finishes of new buildings.

    Chapter 9 Fire Protection and Life Safety Systems

    Chapter 9 prescribes the minimum requirements for active systems of fire protection equipment to perform the following functions: detect a fire, alert the occupants or fire department of a fire emergency, and control smoke and control or extinguish the fire. Generally, the requirements are based on the occupancy, the height and the area of the building because these are the factors that most affect firefighting capabilities and the relative hazard of a specific building or portion thereof. This chapter parallels and is substantially duplicated in Chapter 9 of the CBC; however, this chapter also contains periodic testing criteria that are not contained in the CBC. In addition, the special fire protection system requirements based on use and occupancy found in CBC Chapter 4 are duplicated in CFC Chapter 9 as a user convenience.

    Chapter 10 Means of Egress

    The criteria in Chapter 10 regulating the design of the means of egress system are established as the primary method for protection of occupants by allowing timely relocation or evacuation. Both prescriptive and performance language is utilized for determination of a safe exiting system. It addresses all portions of the means of egress system (i.e., exit access, exits and exit discharge) and includes design requirements as well as provisions regulating individual components. The requirements detail the size, arrangement, number and protection of means of egress components. The means of egress protection requirements work in coordination with other sections of the code, such as protection of vertical openings (see Chapter 7 of the CBC), interior finish (see Chapter 8 of the CBC), fire suppression and detection systems (see Chapter 9) and numerous others, all having an impact on life safety. Chapter 10 of the CBC is duplicated in Chapter 10 of the CFC; however, the CFC contains one additional section on the maintenance of the means of egress system in existing buildings.

    Chapter 11 Construction Requirements for Existing Buildings

    Chapter 11 applies to existing buildings constructed prior to the adoption of the code and intends to provide a minimum degree of fire and life safety to persons occupying existing buildings by providing for retroactive requirements to install or upgrade fire safety features to such buildings that do not comply with the minimum requirements of the CBC. Prior to the 2009 edition, its content existed in the CFC but in a random manner that was neither efficient nor user-friendly. In the 2007/2008 International Code Council (ICC) code development cycle, a code change (F294-07/ 08) was approved that consolidated the retroactive elements of CFC into a single chapter for easier and more efficient reference and application to existing buildings.

    Chapter 12 Energy Systems

  • CFC § 701 High relevance — show source text

    PART I—ADMINISTRATIVE

    Chapter 1 Scope and Administration.

    Chapter 1 establishes the limits of applicability of the code and describes how the code is to be applied and enforced. The provisions of Chapter 1 establish the authority and duties of the code official appointed by the authority having jurisdiction and also establish the rights and privileges of the design professional, contractor and property owner.

    Chapter 2 Definitions.

    Chapter 2 is the repository of the definitions of terms used in the body of the code. The user of the code should be familiar with and consult this chapter because the definitions are essential to the correct interpretation of the code and because the user may not be aware that a term is defined.

    PART II—GENERAL SAFETY PROVISIONS

    Chapter 3 General Requirements

    General regulations contained in Chapter 3, are intended to improve premises safety for everyone, including construction workers, tenants, operations and maintenance personnel, and emergency response personnel.

    Chapter 4 Emergency Planning and Preparedness

    Chapter 4 addresses the human contribution to life safety during emergencies. Continuous training and scheduled fire, evacuation and lockdown drills can be as important as the required periodic inspections and maintenance of built-in fire protection features. The level of preparation by the occupants also improves the emergency responders’ abilities during an emergency.

    PART III—BUILDING AND EQUIPMENT DESIGN FEATURES

    Chapter 5 Fire Service Features

    The requirements of Chapter 5 apply to all buildings and occupancies and pertain to access roads, access to building openings and roofs, premises identification, key boxes, fire protection water supplies, fire command centers, fire department access to equipment, and in-building emergency responder communication system coverage.

    Chapter 6 Building Services and Systems

    Chapter 6 provides a more systematic view of building systems and services as they relate to potential safety hazards and when and how they should be installed.

    Chapter 7 Fire and Smoke Protection Features

    The maintenance of assemblies required to be fire-resistance rated is a key component in a passive fire protection philosophy. Chapter 7 sets forth requirements to maintain required fire-resistance ratings of building elements and limit fire spread. Section 701 addresses the basics of what construction elements such as fire barriers and smoke barriers need to be maintained as well as defining the owner’s responsibility. Sections 703 through 708, deals with various fire and smoke protection features that must also be maintained.

    xiv 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    Chapter 8 Interior Finish, Decorative Materials and Furnishings

    The overall purpose of Chapter 8 is to regulate interior finishes, decorative materials and furnishings in new and existing buildings so that they do not significantly add to or create fire hazards within buildings. This chapter is consistent with Chapter 8 of the CBC, which regulates the interior finishes of new buildings.

    Chapter 9 Fire Protection and Life Safety Systems

    Chapter 9 prescribes the minimum requirements for active systems of fire protection equipment to perform the following functions: detect a fire, alert the occupants or fire department of a fire emergency, and control smoke and control or extinguish the fire. Generally, the requirements are based on the occupancy, the height and the area of the building because these are the factors that most affect firefighting capabilities and the relative hazard of a specific building or portion thereof. This chapter parallels and is substantially duplicated in Chapter 9 of the CBC; however, this chapter also contains periodic testing criteria that are not contained in the CBC. In addition, the special fire protection system requirements based on use and occupancy found in CBC

  • CBC § 1.11. High relevance — show source text

    CHAPTER 7 – FIRE AND SMOKE PROTECTION FEATURES

    (Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)

    Adopting Agency BSC BSC-
    CG
    SFM Col5 HCD Col7 Col8 DSA Col10 OSHPD Col12 Col13 Col14 Col15 Col16 BSCC DPH AGR DWR CEC CA SL SLC
    Adopting Agency BSC BSC-
    CG
    T-24 T-19* 1 2 1/AC AC SS 1 1R 2 3 4 5 5 5 5 5 5 5 5 5
    Adopt Entire Chapter
    Adopt Entire Chapter as
    amended (amended sections
    listed below)
    X
    Adopt only those sections that
    are listed below
    [California Code of Regulations,
    Title 19, Division 1]
    Chapter / Section
    709 X
    • The California Code of Regulations (CCR), Title 19, Division 1 provisions that are found in the California Fire Code are a reprint from the current CCR, Title 19, Division 1 text for the code user’s convenience only. The scope, applicability and appeals procedures of CCR, Title 19, Division I remain the same. The state agency does not adopt sections identified by the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.

    2025 CALIFORNIA FIRE CODE 7-1

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    7-2 2025 CALIFORNIA FIRE CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    7 FIRE AND SMOKE PROTECTION FEATURES

    User notes:

    About this chapter: Chapter 7 provides requirements to maintain the fire-resistance ratings of building elements and to limit fire spread. Section 701 addresses the maintenance of and owner’s responsibility for construction elements such as fire barriers and smoke barriers. The rest of the chapter deals with various aspects that also must be maintained to achieve overall fire resistance of the main fire- and smoke-resistive features. These include penetrations, joint protection, door and window openings, and duct and air transfer opening protection.

    SECTION 701—GENERAL

  • CBC § 0.0187 High relevance — show source text

    Exception: In occupancies other than Groups I-2 and I-3, a duct is permitted to penetrate three floors or less without a fire damper at each floor, provided that such duct meets all of the following requirements:

    1. The duct shall be contained and located within the cavity of a wall and shall be constructed of steel having a minimum wall thickness of 0.0187 inches (0.4712 mm) (No. 26 gage).
    2. The duct shall open into only one dwelling unit or sleeping unit and the duct system shall be continuous from the unit to the exterior of the building.
    3. The duct shall not exceed 4-inch (102 mm) nominal diameter and the total area of such ducts shall not exceed 100 square inches (0.065 m [2] ) in any 100 square feet (9.3 m [2] ) of floor area.
    4. The annular space around the duct is protected with materials that prevent the passage of flame and hot gases sufficient to ignite cotton waste where subjected to ASTM E119 or UL 263 time-temperature conditions under a minimum positive pressure differential of 0.01 inch of water (2.49 Pa) at the location of the penetration for the time period equivalent to the fire-resistance rating of the construction penetrated.
    5. Grille openings located in a ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly shall be protected with a listed ceiling radiation damper installed in accordance with Section 717.6.2.1.

    717.6.2 Membrane penetrations. Ducts and air transfer openings constructed of approved materials in accordance with the Cali- fornia Mechanical Code that penetrate the ceiling membrane of a fire-resistance-rated floor/ceiling or roof/ceiling assembly shall be protected with one of the following:

    1. A shaft enclosure in accordance with Section 713.

    2. A listed ceiling radiation damper installed at the ceiling line where a duct penetrates the ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly. Exceptions:

    3. A fire-resistance-rated assembly tested in accordance with ASTM E119 or UL 263 showing that ceiling radiation dampers are not required in order to maintain the fire-resistance rating of the assembly.

    4. Where exhaust duct or outdoor air duct penetrations protected in accordance with Section 714.5.2 are located within the cavity of a wall and do not pass through another dwelling unit or tenant space.

    5. Where duct and air transfer openings are protected with a duct outlet penetration system tested as part of a fire-resistance-rated assembly in accordance with ASTM E119 or UL 263.

    6. A listed ceiling radiation damper installed at the ceiling line where a diffuser with no duct attached penetrates the ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly. Exceptions:

    7. A fire-resistance-rated assembly tested in accordance with ASTM E119 or UL 263 showing that ceiling radiation dampers are not required in order to maintain the fire-resistance rating of the assembly.

    8. Where duct and air transfer openings are protected with a duct outlet penetration system tested as part of a fire-resistance-rated assembly in accordance with ASTM E119 or UL 263.

    717.6.2.1 Ceiling radiation dampers testing and installation. Ceiling radiation dampers shall be tested in accordance with Section 717.3.1. Ceiling radiation dampers shall be installed in accordance with the details specified in the fire-resistance-rated assembly and the manufacturer’s instructions and the listing.

  • CBC § 501A.3 High relevance — show source text

    501 A .2 Fire-resistance ratings. Fire-resistance ratings shall comply with the California Building Standards Code.

    501A.3 Prescriptive compliance provisions. Alterations, additions and changes of occupancy to the following categories of existing buildings and structures shall comply with the provisions of this section.

    501A.3.1 Prescriptive compliance provisions for SPC-4D using the California Building Code, 1980 (CBC 1980). Nonconforming buildings shall satisfy the following requirements: 1. The California Building Code, 1980 (CBC 1980), as used in this chapter, consists of the Uniform Building Code, 1979 (UBC 1979) along with requirements contained in: a) California Code of Regulations, Title 24- Building Standards, dated February 2, 1980 (Revision record for Register 80, No. 5). b) California Code of Regulations, Title 22 – Social Security, dated October 13, 1979 (Revision Record for Register 79, No 41). c) California Code of Regulations, Title 17 – Public Health, dated October 13, 1979 (Revision Record for Register 79, No 41-B). 2. All existing structural elements of Seismic Force Resisting System (SFRS) shall satisfy the detailing requirements in the CBC 1980 or demonstrate that the level of seismic performance is equivalent to that given in the CBC 1980, as determined by the building official. 3. A continuous load path or paths with adequate strength and stiffness to transfer all the forces from the point of origin to final point of resistance shall be justified by analysis. 4. Site data report in accordance with the CBC 1980 shall establish that seismically induced differential settlement does not exceed 1in 40.

    5. Adjacent buildings shall satisfy the SPC building separation requirements in accordance with the California Administrative Code, Chapter 6 Section 3.4. 6. The addition of new structural elements or strengthening of existing structural elements for retrofit of nonconforming build- ings to SPC-4D shall comply with the following: a) The seismic demand (forces or displacements) shall be in accordance with the CBC 1980; b) Capacity, detailing and connections for new structural elements shall satisfy the requirements in the CBC 2025 for new construction; and c) The strengthening of existing structural elements shall use capacities determined in accordance with the CBC 2025 for new construction consistent with the detailing and connections used in the strengthened member. 7. All construction, quality assurance and quality control shall be in accordance with the new construction provisions of CBC 2025.

    8. Elements not part of the Seismic Force-Resisting System (SFRS), including those identified in the California Administrative Code Chapter 6, Article 10, shall be evaluated using seismic forces and the requirements of the CBC 1980. 9. Any column or wall that forms part of two or more intersecting SFRS and is subjected to axial load due to seismic forces acting along either principal plan axis equaling or exceeding 20 percent of the axial design strength of the column or wall shall be _evaluated for the most critical load effect due to application of seismic force in any direction.

  • CBC § 703.2 High relevance — show source text

    703.2 Repair of penetrations. Where damaged, materials used to protect membrane- and through-penetrations shall be replaced or restored with materials or systems that meet or exceed the code requirements applicable at the time when the assembly was constructed, remodeled or altered.

    SECTION 704—JOINTS AND VOIDS

    704.1 Maintaining protection. Where required when the building was originally constructed, materials and systems used to protect joints and voids in the following locations shall be maintained. The materials and systems shall be securely attached to or bonded to the adjacent construction, without openings visible through the construction.

    1. Joints in or between fire-resistance-rated walls, floors or floor/ceiling assemblies and roof or roof/ceiling assemblies.

    2. Joints in smoke barriers.

    3. Voids at the intersection of a horizontal floor assembly and an exterior curtain wall.

    4. Voids at the intersection of a horizontal smoke barrier and an exterior curtain wall.

    5. Voids at the intersection of a nonfire-resistance-rated floor assembly and an exterior curtain wall.

    6. Voids at the intersection of a vertical fire barrier and an exterior curtain wall.

    7. Voids at the intersection of a vertical fire barrier and a nonfire-resistance-rated roof assembly.

    Unprotected joints and voids do not need to be protected where such joints and voids were not required to be protected when the building was originally constructed. Where the system design number is known, the system shall be inspected to the listing criteria and manufacturer’s installation instructions.

    704.2 Repair of joints and voids. Where damaged, materials used to protect joints and voids shall be replaced or restored with materials or systems that meet or exceed the code requirements applicable at the time when the assembly was constructed, remodeled or altered.

    704.3 Opening protectives. Where openings are required to be protected, opening protectives shall be maintained self-closing or automatic-closing by smoke detection. Existing fusible-link-type automatic door-closing devices are permitted if the fusible link rating does not exceed 135°F (57°C).

    SECTION 705—DOOR AND WINDOW OPENINGS

    705.1 General. Where required when the building was originally constructed, opening protectives installed in fire-resistance-rated assemblies, smoke barriers and smoke partitions shall be inspected and maintained in accordance with this section.

    705.2 Inspection and maintenance. Opening protectives in fire-resistance-rated assemblies shall be inspected and maintained in accordance with NFPA 80. Opening protectives in smoke barriers shall be inspected and maintained in accordance with NFPA 80 and NFPA 105. Openings in smoke partitions shall be inspected and maintained in accordance with NFPA 105. Fire doors and smoke and draft control doors shall not be blocked, obstructed, or otherwise made inoperable. Fusible links shall be replaced promptly whenever fused or damaged. Opening protectives and smoke and draft control doors shall not be modified.

    705.2.1 Labeling requirements. Where approved by the fire code official, the application of field-applied labels associated with the maintenance of opening protectives shall follow the requirements of the approved third-party certification organization accredited for listing the opening protective.

    705.2.2 Signs. Where required by the fire code official, a sign shall be permanently displayed on or near each fire door in letters not less than 1 inch (25 mm) high to read as follows:

    1. For doors designed to be kept normally open: “FIRE DOOR—DO NOT BLOCK.”
    2. For doors designed to be kept normally closed: “FIRE DOOR—KEEP CLOSED.”
  • CBC § 714.5.2 Medium relevance — show source text
    1. A shaft enclosure in accordance with Section 713.

    2. A listed ceiling radiation damper installed at the ceiling line where a duct penetrates the ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly. Exceptions:

    3. A fire-resistance-rated assembly tested in accordance with ASTM E119 or UL 263 showing that ceiling radiation dampers are not required in order to maintain the fire-resistance rating of the assembly.

    4. Where exhaust duct or outdoor air duct penetrations protected in accordance with Section 714.5.2 are located within the cavity of a wall and do not pass through another dwelling unit or tenant space.

    5. Where duct and air transfer openings are protected with a duct outlet penetration system tested as part of a fire-resistance-rated assembly in accordance with ASTM E119 or UL 263.

    6. A listed ceiling radiation damper installed at the ceiling line where a diffuser with no duct attached penetrates the ceiling of a fire-resistance-rated floor/ceiling or roof/ceiling assembly. Exceptions:

    7. A fire-resistance-rated assembly tested in accordance with ASTM E119 or UL 263 showing that ceiling radiation dampers are not required in order to maintain the fire-resistance rating of the assembly.

    8. Where duct and air transfer openings are protected with a duct outlet penetration system tested as part of a fire-resistance-rated assembly in accordance with ASTM E119 or UL 263.

    717.6.2.1 Ceiling radiation dampers testing and installation. Ceiling radiation dampers shall be tested in accordance with Section 717.3.1. Ceiling radiation dampers shall be installed in accordance with the details specified in the fire-resistance-rated assembly and the manufacturer’s instructions and the listing.

    717.6.2.1.1 Dynamic systems. Only ceiling radiation dampers labeled for use in dynamic systems shall be installed in heating, ventilation and air-conditioning systems designed to operate with fans on during a fire.

    717.6.2.1.2 Static systems. Static ceiling radiation dampers shall be provided with systems that are not designed to operate during a fire.

    Exceptions:

    1. Where a static ceiling radiation damper is installed at the opening of a duct, a smoke detector shall be installed inside the duct or outside the duct with sampling tubes protruding into the duct. The detector or tubes in the duct shall be within 5 feet (1524 mm) of the damper. Air outlets and inlets shall not be located between the detector or tubes and the damper. The detector shall be listed for the air velocity, temperature and humidity

    2025 CALIFORNIA BUILDING CODE 7-39

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    FIRE AND SMOKE PROTECTION FEATURES

    anticipated at the point where it is installed. Other than in mechanical smoke control systems, dampers shall be closed upon fan shutdown where local smoke detectors require a minimum velocity to operate. 2. Where a static ceiling radiation damper is installed in a ceiling, the ceiling radiation damper shall be permitted to be controlled by a smoke detection system installed in the same room or area as the ceiling radiation damper. 3. A static ceiling radiation damper shall be permitted to be installed in a room where an occupant sensor is provided within the room that will shut down the system.

    717.6.3 Nonfire-resistance-rated floor assemblies. Duct systems constructed of approved materials in accordance with the California Mechanical Code that penetrate nonfire-resistance-rated floor assemblies shall be protected by any of the following methods:

  • CBC § 3302.1.1 Medium relevance — show source text

    3302.1.1 Components of site safety plans. Site safety plans shall include the following, as applicable:

    1. Name and contact information of site safety director.

    2. Documentation of the training of the site safety director and fire watch personnel.

    3. Procedures for reporting emergencies.

    4. Fire department vehicle access routes.

    5. Location of fire protection equipment, including portable fire extinguishers, standpipes, fire department connections and fire hydrants.

    6. Smoking and cooking policies, designated areas to be used where approved, and signage locations in accordance with the California Fire Code.

    7. Location and safety considerations for temporary heating equipment.

    8. Hot-work permit plan.

    9. Plans for control of combustible waste material.

    10. Locations and methods for storage and use of flammable and combustible liquids and other hazardous materials.

    11. Provisions for site security and, where required, for a fire watch.

    12. Changes that affect this plan.

    13. Other site-specific information required by the California Fire Code .

    2025 CALIFORNIA BUILDING CODE 33-3

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    SAFEGUARDS DURING CONSTRUCTION

    3302.2 Site safety director. The owner shall designate a person to be the site safety director. The site safety director shall be responsible for ensuring compliance with the site safety plan. The site safety director shall have the authority to enforce the provisions of this chapter and other provisions as necessary to secure the intent of this chapter. Where guard service is provided in accordance with the California Fire Code, the site safety director shall be responsible for the guard service.

    3302.3 Daily fire safety inspection. The site safety director shall be responsible for the completion of a daily fire safety inspection at the project site. Each day, all building and outdoor areas shall be inspected to ensure compliance with the inspection list in this section. The results of each inspection shall be documented and maintained on-site until a certificate of occupancy has been issued. Documentation shall be immediately available for on-site inspection and review.

    1. Any contractors entering the site to perform hot work each day have been instructed in the hot work safety requirements in the California Fire Code, and hot work is performed only in areas approved by the site safety director.

    2. Temporary heating equipment is maintained away from combustible materials in accordance with the equipment manufacturer’s instructions.

    3. Combustible debris, rubbish and waste material is removed from the building in areas where work is not being performed.

    4. Temporary wiring does not have exposed conductors.

    5. Flammable liquids and other hazardous materials are stored in locations that have been approved by the site safety director when not involved in work that is being performed.

    6. Fire apparatus access roads required by the California Fire Code are maintained clear of obstructions that reduce the width of the usable roadway to less than 20 feet (6096 mm).

    7. Fire hydrants are clearly visible from access roads and are not obstructed.

    8. The location of fire department connections to standpipe and in-service sprinkler systems are clearly identifiable from the access road and such connections are not obstructed.

    9. Standpipe systems are in service and continuous to the highest work floor, as specified in Section 3311.

    10. Portable fire extinguishers are available in locations required by Section 3309 and for roofing operations in accordance with the California Fire Code .

    11. Where a fire watch is required, fire watch records complying with the California Fire Code are up-to-date.

  • CBC § 1023.7 Medium relevance — show source text

    In each case, openings into the fire-resistance-rated construction shall be limited to those needed for maintenance and operation and shall be protected by opening protectives in accordance with Section 716 of the California Building Code for shaft enclosures.

    The interior exit stairway and ramp ventilation systems shall be independent of other building ventilation systems.

    [BE] 1023.7 Interior exit stairway and ramp exterior walls. Exterior walls of the interior exit stairway or ramp shall comply with the requirements of Section 705 of the California Building Code for exterior walls. Where nonrated walls or unprotected openings enclose the exterior of the stairway or ramps and the walls or openings are exposed by other parts of the building at an angle of less than 180 degrees (3.14 rad), building construction within 10 feet (3048 mm) of the exterior walls of the interior exit stairway or ramp shall comply with Sections 1023.7.1 and 1023.7.2.

    2025 CALIFORNIA FIRE CODE 10-47

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MEANS OF EGRESS

    [BE] 1023.7.1 Building exterior walls. Building exterior walls within 10 feet (3048 mm) horizontally of a nonrated wall or unprotected opening in an interior exit stairway or ramp shall have a fire-resistance rating of not less than 1 hour. Openings within such exterior walls shall be protected by opening protectives having a fire protection rating of not less than [3] / 4 hour. This construction shall extend vertically from the ground to a point 10 feet (3048 mm) above the topmost landing of the stairway or ramp, or to the roof line, whichever is lower.

    [BE] 1023.7.2 Roof assemblies. Where the interior exit stairway or ramp extends above an adjacent roof of the same building, the adjacent roof assembly shall have a fire-resistance rating of not less than 1 hour and openings shall be protected by opening protectives having a fire protection rating of not less than [3] / 4 hour. The fire-resistance rating and opening protection shall extend horizontally not less than 10 feet (3048 mm) from the exterior wall of the stairway or ramp, or to the perimeter of the adjacent roof, whichever is less.

    Exceptions:

    1. The roof assembly need not be rated and openings in the roof need not be protected where they are adjacent to the penthouse of the stairway or ramp, unless otherwise required by this code.
    2. The adjacent roof assembly need not be rated and adjacent openings in the roof need not be protected where the exterior wall of the stairway or ramp has a fire-resistance rating of 1 hour and openings are protected by opening protectives having a fire protection rating of not less than [3] / 4 hour, extending not less than 10 feet (3048 mm) above the roof.

    [BE] 1023.8 Barriers at level of exit discharge. An interior exit stairway and ramp shall not continue below its level of exit discharge unless an approved barrier is provided at the level of exit discharge to prevent persons from unintentionally continuing into levels below. Directional exit signs shall be provided as specified in Section 1013.

  • CBC § 2.1 Medium relevance — show source text

    2.1_||||X|X||||||||||||||||||||

    The state agency does not adopt sections identified with the following symbol: The Office of the State Fire Marshal’s adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.

    2025 CALIFORNIA BUILDING CODE 7-1

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    7-2 2025 CALIFORNIA BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    7 FIRE AND SMOKE PROTECTION FEATURES

    User notes:

    About this chapter: Chapter 7 provides detailed requirements for fire-resistance-rated construction, including structural members, walls, partitions and horizontal assemblies. Other portions of the code describe where certain fire-resistance-rated elements are required. This chapter specifies how these elements are constructed, how openings in walls and partitions are protected and how penetrations of such elements are protected.

    SECTION 701—GENERAL

    701.1 Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated construction separation of adjacent spaces to safeguard against the spread of fire and smoke within a building and the spread of fire to or from buildings.

    SECTION 702—MULTIPLE-USE FIRE ASSEMBLIES

    702.1 Multiple-use fire assemblies. Fire assemblies that serve multiple purposes in a building shall comply with all of the requirements that are applicable for each of the individual fire assemblies.

    SECTION 703—FIRE-RESISTANCE RATINGS AND FIRE TESTS

    703.1 Scope. Materials prescribed herein for fire resistance shall conform to the requirements of this chapter.

    703.2 Fire resistance. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with Section 703.2.1 or 703.2.2 without the use of automatic sprinklers or any other fire suppression system being incorporated, or in accordance with Section 703.2.3.

    703.2.1 Tested assemblies. A fire-resistance rating of building elements, components or assemblies shall be determined by the test procedures set forth in ASTM E119 or UL 263. The fire-resistance rating of penetrations and fire-resistant joint systems shall be determined in accordance with Sections 714 and 715, respectively.

    703.2.1.1 Nonsymmetrical wall construction. Interior walls and partitions of nonsymmetrical construction shall be tested with both faces exposed to the furnace, and the assigned fire-resistance rating shall be the shortest duration obtained from the two tests conducted in compliance with ASTM E119 or UL 263. Where evidence is furnished to show that the wall was tested with the least fire-resistant side exposed to the furnace, subject to acceptance of the building official, the wall need not be subjected to tests from the opposite side (see Section 705.5 for exterior walls).

    703.2.1.2 Combustible components. Combustible aggregates are permitted in gypsum and Portland cement concrete mixtures for fire-resistance-rated construction. Any component material or admixture is permitted in assemblies if the resulting tested assembly meets the fire-resistance test requirements of this code.

Frequently asked questions

Who exactly is "the owner" for purposes of these duties?

"The owner" is the person or entity that holds legal ownership of the building; ownership responsibilities may be carried out by agents or property managers, but the duty and accountability to maintain the inventory, inspections and records remain the owner’s under § 701.6.

How often must rated assemblies be inspected?

The code requires the owner to visually inspect required rated construction annually. § 701.6.

If I find a small penetration, can I patch it with any fire‑resistant material?

No — repairs must restore the fire‑resistance and be performed with materials/systems that meet the applicable requirements (see Chapters 703–707) and the repair standard in § 701.5; use a listed firestop or other approved system that restores the assembly’s rating.

Must concealed rated elements be opened for inspection?

No — concealed elements need not be visually inspected unless the concealed space is accessible by removal or movement of a panel, access door, ceiling tile or similar movable entry. § 701.6.

How long do I have to keep inspection/repair records?

Records must be maintained in accordance with Section 110.3 as required by § 701.6.1 — keep inspection, testing and repair records as directed by § 110.3.

More in California Building Code

Ask about the CBC

Get cited, plain-English answers on the California Building Code for your project — any code section, any scenario.

Start Free Trial

Related in the CBC