CBC · California Building Code

How do CBC/CalGreen direct designers to use the California Energy Code (Part 6) for compliance?

In plain terms: when CalGreen (the CBC green‑building volume) asks for energy compliance, designers must comply with the California Energy Code (Title 24 Part 6). That means using Part 6 prescriptive or performance methods, doing the Part 6 required acceptance testing and certificates, and integrating Part 6 procedures into CalGreen commissioning and documentation.

Last reviewed: July 5, 2026

What the code requires

CalGreen (the CBC Volume dedicated to green building) explicitly directs designers to follow the California Energy Code (Title 24, Part 6) as the mandatory energy standard for energy-related design and verification for projects subject to CalGreen mandatory measures, summarized in § 5.201.1. Designers must therefore use Part 6 compliance paths (prescriptive, performance, or other Part‑6‑approved methods) and submit the Part 6 required documentation and certificates when demonstrating compliance with the energy elements that CalGreen delegates to the Energy Code. The CBC/App. A cross‑reference that points users to the Energy Code is identified in the CBC materials, but the exact Appendix cross‑reference text § [A]101.4.6 was not located in the retrieved files.

Requirements in detail

1) Which standard controls energy design

  • Rule: For mandatory CalGreen energy mandates, design and verification must conform to the California Energy Code (Title 24, Part 6). See § 5.201.1 for the CalGreen direction to use Part 6 as the mandatory energy standard.
  • Practical effect: When CalGreen asks for energy performance, documentation and testing, the designer uses Part 6 compliance procedures, definitions, and referenced test/certification sources in Part 6.

2) Compliance approaches designers must be prepared to use

  • Part 6 offers prescriptive packages, performance (software) compliance and various reference appendices; CalGreen energy measures are met by meeting the applicable provisions in Part 6. Designers must pick the performance or prescriptive method required or allowed by Part 6 for their occupancy and scope.

3) Documentation, verification and commissioning

  • CalGreen requires commissioning and functional performance testing where noted; those tests and the acceptance criteria that demonstrate correct installation and operation must be performed in accordance with the California Energy Code when the systems fall under Part 6 coverage (informational note and commissioning sections).
  • Part 6 requires Certificates of Compliance and Certificates of Acceptance (and acceptance testing for lighting, controls, etc.) as part of demonstrating compliance — those submission and installation cert rules live in Part 6 and Title 24 Part 1 administrative sections referenced by Part 6.

Decision table (key dimensions designers use to decide how to apply Part 6)

Decision dimension When it matters Designer action Code reference
Project type (new, addition, alteration) All projects covered by CalGreen mandatory measures Determine Part 6 applicability for the occupancy and use the applicable Part 6 compliance path § 5.201.1
Compliance method Chosen by designer or required by occupancy (prescriptive vs. performance) Select Part 6 prescriptive package or run certified compliance software for performance approach Part 6 definitions/compliance methods § 100.1 and related in Part 6
Commissioning / functional testing When CalGreen Chapter 5 mandates commissioning or where Part 6 requires acceptance testing Prepare commissioning plan and perform functional tests to Part 6 / CalGreen criteria; submit required certificates § 5.410.2 (CalGreen) and Part 6 acceptance testing rules § 130.4 / § 10‑103 references
Renewable energy / PV sizing When Part 6 PV triggers apply (new building types, thresholds) Calculate required PV capacity using Part 6 equations and include in energy compliance documentation Equation for PV capacity in Part 6 (e.g., Equation 140.10‑A / 170.2‑D in Part 6)
Appliance/equipment certification Installation of regulated appliances or systems Use Energy Commission certified appliance directories or manufacturer certification routes specified by Part 6 Part 6 §§ 110.0–110.2 (appliance / equipment certification)

(Use the table above as a checklist in pre‑design: identify the occupancy, select method, assemble Part 6 documentation, and integrate required CalGreen commissioning and records.)

4) How CalGreen and Part 6 interact on specific items

  • Commissioning and functional testing called for by CalGreen reference Part 6 for test procedures and verification requirements where the systems are energy‑code systems (lighting, HVAC, controls, etc.). Designers must follow Part 6 acceptance test procedures and submit Part 6 installation/acceptance certificates when applicable.
  • Voluntary CalGreen tiers may ask designers to “meet or exceed” Part 6 performance (or use Part 6 modeling software for LSC) — appendix provisions of CalGreen explicitly reference Part 6 metrics and software.

Exceptions & special cases

  • Local amendments: jurisdictions may adopt energy standards but must obtain California Energy Commission approval if they are energy‑related and more stringent than Part 6; local rules that are permitted are described in the CBC/CalGreen administrative sections (local adoption/approval language). Designers must confirm whether a local jurisdiction has adopted Part 6 as‑published or adopted a local amendment approved by the Energy Commission.
  • Mixed occupancies: Part 6 contains exceptions allowing the design of the whole building to follow the rules for the predominant occupancy under certain floor‑area percentages — verify the Part 6 occupancy thresholds and lighting/HVAC caveats before choosing that path.
  • Small scope alterations: Part 6 allows alternative modeling/limits for alterations and repairs (e.g., “whole building” elective compliance for additions/alterations is allowed in certain circumstances) — check Part 6 sections on additions/alterations.

If you need a jurisdictional check: ask whether the enforcing agency has adopted local amendments or an earlier effective edition of the codes; that changes which Part 6 edition and which CalGreen effective date apply.

Common mistakes

  • Treating CalGreen’s energy phrases as separate “new” energy rules rather than as a referral: designers sometimes try to satisfy CalGreen energy language with non‑Part‑6 methods — but CalGreen defers to Part 6 for mandatory energy standards, so design must use Part 6 compliance methods. Always map each energy item in a CalGreen checklist back to the controlling Part 6 requirement. § 5.201.1 reiterates that Part 6 is the mandatory energy yardstick.
  • Missing Part 6 certificates: failing to submit the Part 6 Certificate of Compliance or Certificate of Acceptance (for lighting controls, etc.) expecting CalGreen forms alone to suffice. Part 6 administrative and acceptance sections govern those submittals.
  • Overlooking acceptance testing standards: when Part 6 requires acceptance testing (lighting controls, demand responsive controls, etc.), designers must specify these tests in the commissioning plan and arrange for the required certified testers per Part 6.
  • Using incorrect PV area factors or applying PV exceptions incorrectly — use the Part 6 equations and SARA rules when sizing PV for compliance shown in Part 6 (the Part 6 PV equations and exceptions apply).

Worked example — small commercial addition (numbers)

Scenario: 2,000 ft² conditioned addition to an existing small office (same occupancy), climate zone where Part 6 prescriptive packages apply. Designer must show CalGreen mandatory energy items are met by following Part 6.

Step 1 — Determine whether the addition can be treated under Part 6 alteration rules or whether whole‑building compliance is required. Part 6 permits whole‑building compliance in certain alteration/addition cases; otherwise, apply specific alteration provisions.

Step 2 — Pick a compliance approach. If using Part 6 performance method, run the certified compliance software and produce the Certificate of Compliance (CF1R/CF2R outputs or the nonresidential equivalents). If using prescriptive, apply the climate‑zone specific component U‑/R‑values, HVAC minimum efficiency, lighting power densities, etc., per Part 6 prescriptive tables.

Step 3 — PV calculation (if Part 6 requires PV for this occupancy and area): use Part 6 PV equation (kW PVdc = (CFA × A)/1000) where CFA is conditioned floor area and A is the capacity factor per table in Part 6. For a 2,000 ft² addition, if A = 4 W/ft² (example climate/building type factor), required kW = (2,000 × 4)/1000 = 8 kW PVdc (subject to Part 6 exceptions for available SARA, minimum kW thresholds, or contiguous SARA thresholds). Use the Part 6 equation and exceptions when making the final determination.

Step 4 — Commissioning and testing: if CalGreen Chapter 5 mandates commissioning for the project size/systems, include OPR/BOD and a commissioning plan and perform functional performance tests. Any Part 6 required acceptance testing (lighting controls) must be scheduled and recorded per Part 6 acceptance procedures; submit the Part 6 Certificate of Acceptance where required.

Related provisions (CBC / CalGreen / Part 6 sections to review)

  • CalGreen mandatory measures and administration: § 5.201.1 (CalGreen direction to use Part 6 for energy)
  • CalGreen commissioning and functional testing requirements: § 5.410.2 (Owner’s Project Requirements, Basis of Design, Functional performance testing)
  • CalGreen voluntary tiers referencing Part 6 performance: A5.601.2.2 / A5.601.3.2 (CalGreen tiers and statement that the California Energy Commission adopts mandatory energy standards)
  • California Energy Code (Part 6) compliance methods and definitions: Part 6 § 100.1 and related compliance sections (defines compliance approaches, climate zones, etc.)
  • Part 6 acceptance testing and certificate requirements: Part 6 § 130.4 and Part 1 § 10‑103 referenced by Part 6 for certificates of acceptance and installation certification procedures
  • Part 6 photovoltaic sizing and equations: Part 6 Equation 140.10‑A / 170.2‑D and SARA exceptions (PV sizing and exceptions)

Note about § [A]101.4.6: the user asked specifically about § [A]101.4.6 as the CBC cross‑reference to the California Energy Code. I did not find the text of § [A]101.4.6 in the files returned by the search; therefore I cannot quote or cite that particular subsection from the retrieved documents. If you can upload or point me to the CBC Appendix text that contains § [A]101.4.6 I will incorporate it directly and update the guidance.

Code references

Grounded in the retrieved California Building Code — click a citation to read the verbatim passage:

  • CBC § 405.4 High relevance — show source text
    1. From Division A5.4,

    a. Comply with recycled content of 15 percent of materials based on estimated total cost, or use two products from Table A5.405.4 for at least 75 percent by cost in Section A5.405.4.1. b. Comply with the 80-percent reduction in construction and demolition waste in Section A5.408.3.1. c. Comply with three elective measures selected from this division.

    1. From Division A5.5,

    a. Comply with resilient flooring systems for 100 percent of resilient flooring in Section A5.504.4.7.1. Exception: Allowance may be permitted in Tier 2 for up to 5-percent specialty purpose flooring. b. Comply with thermal insulation meeting 2009 CHPS low-emitting materials list and no added formaldehyde in Section A5.504.4.8.1.

    c. Comply with three elective measures selected from this division. 6. Comply with three additional elective measures selected from any division.

    1 Cool roof is required for compliance with Tiers 1 and 2 and may be used to meet energy standards in Part 6, exceed energy standards and to mitigate heat island effect.

    A5.601.4 Compliance verification. Compliance with Section A5.601.2 or A5.601.3 shall be as required in Chapter 7 of this code. Compliance documentation shall be made part of the project record as required in Section 5.410.2 or 5.410.3.

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-43

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    A5.602

    CALGreen VERIFICATION GUIDELINES MANDATORY MEASURES CHECKLIST

    Application: This checklist shall be used for nonresidential projects that meet one of the following: new construction, building additions of 1,000 square feet or greater, or building alterations with a permit valuation of $200,000 or more pursuant to Section 301.3 AND do not trigger a Tier 1 or Tier 2 requirement:

    Y = Yes (section has been selected and/or included)

    N/A = Not Applicable (code section does not apply to the project mainly used for additions and alterations) O = Other (provide explanation)

    [N] = New construction pursuant to Section 301.3

    [A ] = Additions and/or Alterations pursuant to Section 301.3

    CHAPTER 5
    DIVISIONS
    Col2 SECTION TITLE CODE
    SECTION
    Y N/A O PLAN SHEET,
    SPEC OR
    ATTACH
    DIVISION 5.1
    Planning and
    Design
    Mandatory Deconstruction and reuse of existing structures,
    Scope with Exception
    5.105.1
    DIVISION 5.1
    Planning and
    Design
    Mandatory Reuse of existing building & Verification of compliance with
    note
    5.105.2 and
    5.105.2.1
    DIVISION 5.1
    Planning and
    Design
    Mandatory Storm water pollution prevention for projects that disturb less
    than 1 acre of land
    5.106.
  • CBC § 101.7.1. High relevance — show source text

    This code does not limit the authority of city, county, or city and county governments to make necessary changes to the provisions contained in this code pursuant to Section 101.7.1. The effective date of amendments, additions or deletions to this code for cities, counties, or cities and counties filed pursuant to Section 101.7.1 shall be the date on which it is filed. However, in no case shall the amendments, additions or deletions to this code be effective any sooner than the effective date of this code.

    Local modifications shall comply with Health and Safety Code Section 18941.5(b) for Building Standards Law, Health and Safety Code Section 17958.5 for State Housing Law or Health and Safety Code Section 13869.7 for Fire Protection Districts.

    101.7.1 Findings and filings.

    1. The city, county, or city and county shall make express findings for each amendment, addition or deletion based upon climatic, topographical or geological conditions. For the purpose of this section, climatic, topographical or geological conditions include local environmental conditions as established by the city, county, or city and county.

    2. The city, county, or city and county shall file the amendments, additions or deletions expressly marked and identified as to the applicable findings. Cities, counties, cities and counties, and fire departments shall file the amendments, additions or deletions and the findings with the California Building Standards Commission at 2525 Natomas Park Drive, Suite 130, Sacramento, CA 95833.

    3. Findings prepared by fire protection districts shall be ratified by the local city, county, or city and county and filed with the California Department of Housing and Community Development at 9342 Tech Center Drive, Suite 500, Sacramento, CA 95826.

    4. The city, county, or city and county shall obtain California Energy Commission approval for any energy- related ordinances consistent with Public Resources Code Section 25402.1(h)(2) and Title 24, Part 1, Section 10-106. Local governmental agencies may adopt and enforce energy standards for newly constructed buildings, additions, alterations and repairs, provided the California Energy Commission finds that the standards will require buildings to be designed to consume no more energy than permitted by Part 6. Such local standards include, but are not limited to, adopting the requirements of Part 6 before their effective date, requiring additional energy conservation measures, or setting more stringent energy budgets.

    101.8 Alternate materials, designs and methods of construction. The provisions of this code are not intended to prevent the use of any alternate material, appliance, installation, device, arrangement, method, design or method of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternate shall be approved on a case-by-case basis where the enforcing agency finds that the proposed alternate is satisfactory and complies with the intent of the provisions of this code and is at least the equivalent of that prescribed in this code in planning and design, energy, water, material conservation and resource efficiency, environmental air quality, performance, safety and the protection of life and health. Consideration and compliance provisions for occupancies regulated by adopting state agencies are found in the sections listed below.

    1. Section 1.2.3 in the California Building Code (CBC) for the California Building Standards Commission.
    2. Section 104.2.3 in the California Building Code (CBC) for the Division of the State Architect.
  • CBC § 25402.1 High relevance — show source text
    1. The city, county, or city and county shall obtain California Energy Commission approval for any energy- related ordinances consistent with Public Resources Code Section 25402.1(h)(2) and Title 24, Part 1, Section 10-106. Local governmental agencies may adopt and enforce energy standards for newly constructed buildings, additions, alterations and repairs, provided the California Energy Commission finds that the standards will require buildings to be designed to consume no more energy than permitted by Part 6. Such local standards include, but are not limited to, adopting the requirements of Part 6 before their effective date, requiring additional energy conservation measures, or setting more stringent energy budgets.

    101.8 Alternate materials, designs and methods of construction. The provisions of this code are not intended to prevent the use of any alternate material, appliance, installation, device, arrangement, method, design or method of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternate shall be approved on a case-by-case basis where the enforcing agency finds that the proposed alternate is satisfactory and complies with the intent of the provisions of this code and is at least the equivalent of that prescribed in this code in planning and design, energy, water, material conservation and resource efficiency, environmental air quality, performance, safety and the protection of life and health. Consideration and compliance provisions for occupancies regulated by adopting state agencies are found in the sections listed below.

    1. Section 1.2.3 in the California Building Code (CBC) for the California Building Standards Commission.
    2. Section 104.2.3 in the California Building Code (CBC) for the Division of the State Architect.
    3. Section 1.8.7 in the California Building Code (CBC); and Section 1.8.7 in the California Residential Code (CRC) for the Department of Housing and Community Development.
    4. Section 7-104 in the California Administrative Code for the Office of the Statewide Health Planning and Development.

    1-4 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    ADMINISTRATION

    101.9 Effective date of this code. Only those standards approved by the California Building Standards Commission that are effective at the time an application for a building permit is submitted shall apply to the plans and specifications for, and to the construction performed under, that permit. For the effective dates of the provisions contained in this code, see the appropriate application checklist and the History Note page of this code.

    101.10 Mandatory requirements. This code contains both mandatory and voluntary green building measures. Mandatory and voluntary measures are identified in the appropriate application checklist contained in this code.

    101.11 Effective use of this code. The following steps shall be used to establish which provisions of this code are applicable to a specific occupancy:

    1. Establish the type of occupancy.
    2. Verify which state agency has authority for the established occupancy by reviewing the authorities list in Sections 103 through 106.
    3. Once the appropriate agency has been identified, find the chapter which covers the established occupancy.
    4. The Matrix Adoption Tables at the beginning of Chapters 4 and 5 identify the mandatory green building measures necessary to meet the minimum requirements of this code for the established occupancy.
    5. Voluntary tier measures are contained in Appendix Chapters A4 and A5. A checklist containing each green building measure, both required and voluntary, is provided at the end of each appendix chapter.
  • CBC § 4.3 High relevance — show source text

    For each phase of the work, define the roles and responsibilities for each member of the Cx team. iii. List the required Cx deliverables, reports, forms and verifications expected at each stage of the commissioning effort.

    iv. Include the confirmation process for the O&M manual, systems manual and the facility operator and maintenance staff training.

    4.3 Enforcement:

    At their discretion, the inspector confirms demonstrated compliance at Plan Intake by: a) Receipt of a copy of the commissioning plan, or b) Receipt of a form signed by the owner or owner’s representative attesting that the Cx Plan has been completed.

    Reference: 5 Functional performance testing

    CALGreen Section 5.410.2.4, Functional performance testing.

    5.1 Intent:

    Develop and implement the functional performance tests to document, as set forth in the commissioning plan, that all components, equipment, systems and system-to-system interfaces were installed as specified, and operate according to the Owner’s Project Requirements, Basis of Design, and plans and specifications.

    The following systems to be functionally tested are listed in the Basis of Design (Section 5.410.2.2 of the code):

    1. Renewable energy systems

    2. Landscape irrigation systems

    3. Water reuse systems

    5.2 Compliance Method:

    Compliance is demonstrated by developing and implementing test procedures for each piece of commissioned equipment and interfaces between equipment and systems according to the building-specific commissioning plan. Tests should include verification of proper operation of all equipment features, each part of the sequence of operation, overrides, lockouts, safeties, alarms, occupied and unoccupied modes, loss of normal power, exercising a shutdown, startup, low load through full load (as much as is possible) and back, staging and standby functions, scheduling, energy efficiency strategies and loop tuning.

    Elements of acceptable test procedures include:

    1. Date and party—Identification of the date of the test and the party conducting the test.

    2. Signature block—Signature of the designated commissioning lead and the equipment installing contractor attesting that the recorded test results are accurate.

    3. Prerequisites—Any conditions or related equipment checkout or testing that needs to be completed before conducting this test.

    4. Precautions—Identification of the risks involved to the test team members and the equipment and how to mitigate them.

    5. Instrumentation—Listing of the instrumentation and tools necessary to complete the test.

    6. Reference—In each procedure item, identify the source for what is being confirmed (e.g., sequence of operation ID, operating feature, specification requirement, etc.).

    8-18 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    COMPLIANCE FORMS, WORKSHEETS AND REFERENCE MATERIAL

    1. Test instructions—Step-by-step instructions of how to complete the test, including functions to test and the conditions under which the tests should performed.

    2. Acceptance criteria—Measurable pass / fail criteria for each step of the test, as applicable.

    3. Results—Expected system response and space to document the actual response, readings, results and adjustments.

    4. Return to normal—Instructions that all systems and equipment are to be returned to their as-found state at the conclusion of the tests.

    5. Deficiencies—A list of deficiencies and how they were mitigated.

    5.3 Enforcement:

  • CBC § 409.4 Medium relevance — show source text

    Solar access is the ratio of solar insolation including shade to the
    solar insolation without shade. Shading from obstructions located on the roof or any other part of the building shall not be included in the determination of annual solar access.
    3.
    Life cycle assessment compliant with Section A5.409.4 in this code may be substituted for prescriptive measures from Division A5.4.|

    A5.601.1 Scope. The measures contained in this appendix are not mandatory unless adopted by local government as specified in Section 101.7. The provisions of this section outline means of achieving enhanced construction or reach levels by incorporating addi

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A5-41

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    tional green building measures for newly constructed nonresidential buildings as well as additions and alterations. In order to meet one of the tier levels designers, builders or property owners are required to incorporate additional green building measures necessary to meet the threshold of each level. Refer to the provisions in Section 301.3 for nonresidential additions and alterations scope and application.

    A5.601.2 CALGreen Tier 1

    A5.601.2.1 Prerequisites. To achieve CALGreen tier status, a project must meet all of the mandatory measures in Chapter 5 and, in addition, meet the provisions of this section.

    A5.601.2.2 Energy performance. For the purposes of mandatory energy efficiency standards in this code, the California Energy Commission will continue to adopt mandatory standards.

    A5.601.2.3 Tier 1. Comply with the energy efficiency requirements in Section A5.203.1.1 and Section A5.203.1.2.1.

    A5.601.2.4 Voluntary measures for Tier 1. In addition to the provisions of Sections A5.601.2.1 and A5.601.2.3 above, compliance with the following voluntary measures from Appendix A5 is required for Tier 1:

    1. From Division A5.1, a. Comply with the designated parking requirements for high-efficiency vehicles for a minimum of 35 percent of parking capacity per Section A5.106.5.1. b. Electric vehicle (EV) charging [N] and Table A5.106.5.3.1 w/ footnotes. c. Comply with thermal emittance, solar reflectance or SRI values for cool roofs in Section A5.106.11.2 and Table A5.106.11.2.2. [1]

    d. Comply with one elective measure selected from this division. 2. From Division A5.2 comply with ONE of the following:

    1. Outdoor lighting as described in A5.203.1.1.1.

    2. Service water heating in restaurants as described in A5.203.1.1.2.

    3. Warehouse Dock Seal Doors A5.203.1.1.3.

    4. Daylight Design Power Adjustments 5.203.1.1.4.

    5. Exhaust Air Heat Recovery A5.203.1.1.5.

    6. From Division A5.3,

    a. Comply with the 12-percent reduction for indoor potable water use in Section A5.303.2.3.1. b. Comply with one elective measure selected from this division.

    1. From Division A5.4,
  • CBC § 503.1.4. Medium relevance — show source text

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MULTIFAMILY BUILDINGS—PERFORMANCE AND PRESCRIPTIVE COMPLIANCE APPROACHES

    and obstructions that are part of the building design and elevation features, may be considered for the annual solar access calculations.

    B. Occupied roofs as specified by CBC Section 503.1.4. C. Roof area that is otherwise not available due to compliance with: i. Other state building code requirements, or ii. Local building code requirements if the local building code requirements are confirmed by the Executive Director.

    EQUATION 170.2-D—PHOTOVOLTAIC DIRECT CURRENT CAPACITY

    kW PVdc = (CFA × A)/1000

    where:

    kW PVdc = Minimum rated PV system capacity in kW.

    CFA = Conditioned floor area in square feet.

    A = PV capacity factor in W/square foot as specified in Table 170.2-U for the building type.

    Exception 1 to Section 170.2(g): No PV system is required where the total of all available SARA is less than 3 percent of the conditioned floor area.

    Exception 2 to Section 170.2(g): No PV system is required where the required PV system capacity is less than 4 kW dc .

    Exception 3 to Section 170.2(g): No PV system is required if the SARA contains less than 80 contiguous square feet.

    Exception 4 to Section 170.2(g): Buildings with enforcement-authority-approved roof designs, where the enforcement authority determines it is not possible for the PV system, including panels, modules, components, supports and attachments to the roof structure, to meet ASCE 7-16, Chapter 7, Snow Loads.

    Exception 5 to Section 170.2(g): Multifamily buildings with more than three habitable stories in areas where a load-serving entity does not provide a program where PV generation is compensated through virtual energy bill credits. This exception does not apply where the Commission has approved a community solar program for showing compliance as specified in Title 24, Part 1, Section 10-115, or where a load-serving entity provides a program where PV generation is compensated through virtual energy bill credits for occupants of nonresidential and hotel/motel tenant spaces to receive energy bill benefits from netting of energy generation and consumption.

    TABLE 170.2-U – PV CAPACITY FACTORS (W/ft2 of conditioned floor area) Col2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 Col10 Col11 Col12 Col13 Col14 Col15 Col16 Col17
    BUILDING TYPE CZ 1 CZ 2 CZ 3 CZ 4 CZ 5 CZ 6 CZ 7 CZ 8 CZ 9 CZ 10 CZ 11 CZ 12 CZ 13 CZ 14 CZ 15 CZ 16
    Event & Exhibit 3.48 4.28 3.66 4.32 3.77 4.05 4.28 4.83 4.63 4.
  • CBC § 100.0 Medium relevance — show source text

    Exception 1 to Section 100.0(f): If one occupancy constitutes at least 80 percent of the conditioned floor area of the building, the entire building envelope, HVAC and water heating may be designed to comply with the provisions of Part 6 applicable to that occupancy, provided that the applicable lighting requirements in Sections 140.6 through 140.8, 150.0(k), or 160.5 and 170.2(e) are met for each occupancy and space, and mandatory measures in Sections 110.0 through 130.5, 150.0, and 160.0 through 160.9 are met for each occupancy and space.

    Exception 2 to Section 100.0(f): If one occupancy constitutes at least 90 percent of the combined conditioned plus unconditioned floor area of the building, the entire building indoor lighting may be designed to comply with only the lighting provisions of Part 6 applicable to that occupancy.

    (g) Administrative requirements. Administrative requirements relating to permit requirements, enforcement by the Commission, locally adopted energy standards, interpretations, claims of exemption, approved calculation methods, rights of appeal, and certification and labeling requirements of fenestration products and roofing products are specified in California Code of Regulations, Title 24, Part 1, Sections 10-101 to 10-114.

    (h) Certification requirements for manufactured equipment, products and devices. Part 6 limits the installation of manufactured equipment, products and devices to those that have been certified as specified by Sections 110.0 and 110.1. Requirements for manufactured equipment, products, and devices, when not specified in Title 24 Part 6, are specified in California Code of Regulations, Title 20, Sections 1601–1609.

    Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code .

    SECTION 100.1 DEFINITIONS AND RULES OF CONSTRUCTION

    (a) Rules of Construction.

    1. Where the context requires, the singular includes the plural and the plural includes the singular.
    2. The use of “and” in a conjunctive provision means that all elements in the provision must be complied with or must exist to make the provision applicable. Where compliance with one or more elements suffices, or where existence of one or more elements makes the provision applicable, “or” (rather than “and/or”) is used.
    3. “Shall” is mandatory and “may” is permissive.

    (b) Definitions. Terms, phrases, words and their derivatives in Part 6 shall be defined as specified in Section 100.1. Terms, phrases, words and their derivatives not found in Section 100.1 shall be defined as specified in the “Definitions” chapters of Title 24, Parts 1 through 5 of the California Code of Regulations. Where terms, phrases, words and their derivatives are not defined in any of the references above, they shall be defined as specified in Webster’s Third New International Dictionary of the English Language, Unabridged (1961 edition, through the 2002 addenda), unless the context requires otherwise.

  • CBC § 110.1 Medium relevance — show source text

    SECTION 110.1—MANDATORY REQUIREMENTS FOR APPLIANCES

    (a) Any appliance regulated by the Appliance Efficiency Regulations, Title 20 California Code of Regulations, Section 1601 et seq., may be installed only if the appliance fully complies with Section 1608(a) of those regulations.

    (b) Except for those circumstances described in Section 110.1(c), conformance with efficiency levels required to comply with Part 6 mandatory, prescriptive and performance standards shall be verified utilizing data from either:

    1. The Energy Commission’s database of certified appliances maintained pursuant to Title 20 California Code of Regulations Section 1606, and which is available at: www.energy.ca.gov/appliances/database/ ; or
    2. An equivalent directory published by a federal agency; or
    3. An approved trade association directory as defined in Title 20 California Code of Regulations Section 1606(h).

    (c) Conformance with efficiency levels required to comply with Part 6 mandatory, prescriptive and performance standards shall be demonstrated either by default to the mandatory efficiency levels specified in Part 6 or by following procedures approved by the Commission pursuant to Section 10-109 of Title 24, Part 1, when:

    1. Data to verify conformance with efficiency levels required to comply with Part 6 mandatory, prescriptive and performance standards is not available pursuant to subdivision (b); or
    2. Field verification and diagnostic testing is required for compliance with Part 6 and the Energy Commission has not approved a field verification and diagnostic test protocol that is applicable to the appliance; or
    3. The appliance meets the requirements of Section 110.1(a) but has been site-modified in a way that affects its performance; or

    2025 CALIFORNIA ENERGY CODE 39

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    ALL OCCUPANCIES—MANDATORY REQUIREMENTS FOR THE MANUFACTURE, CONSTRUCTION AND INSTALLATION OF SYSTEMS, EQUIPMENT AND BUILDING COMPONENTS

    1. The U.S. Department of Energy has approved a waiver from federal test procedures, pursuant to 10 CFR Section 430.27 or Section 431.401 and that waiver fails to specify how the efficiency of the system shall be determined.

    Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5 , 2 5402.8, and 25943, Public Resources Code.

    SECTION 110.2—MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

    Certification by manufacturers. Any space-conditioning equipment listed in this section may be installed only if the manufacturer has certified to the Commission that the equipment complies with all the applicable requirements of this section.

    (a) Efficiency. Equipment shall meet the applicable efficiency requirements in Tables 110.2-A through 110.2-L, subject to the following:

    1. If more than one efficiency standard is listed for any equipment in Tables 110.2-A through 110.2-L, the equipment shall meet all the applicable standards that are listed; and
    2. If more than one test method is listed in Tables 110.2-A through 110.2-L, the equipment shall comply with the applicable efficiency standard when tested with each listed test method; and
  • CBC § 405.4 Medium relevance — show source text
    1. From Division A5.4,

    a. Comply with recycled content of 10 percent of materials based on estimated total cost, or use two products from Table A5.405.4 for at least 75 percent by cost in Section A5.405.4. b. Comply with the 65-percent reduction in construction and demolition waste in Section A5.408.3.1. c. Comply with one elective measure selected from this division.

    1. From Division A5.5,

    a. Comply with resilient flooring systems for 90 percent of resilient flooring in Section A5.504.4.7. b. Comply with thermal insulation meeting 2009 CHPS low-emitting materials list in Section A5.504.4.8. c. Comply with one elective measure selected from this division. 6. Comply with one additional elective measure selected from any division.

    1 Cool roof is required for compliance with Tiers 1 and 2 and may be used to meet energy standards in Part 6, exceed energy standards and to mitigate heat island effect.

    A5.601.3 CALGreen Tier 2.

    A5.601.3.1 Prerequisites. To achieve CALGreen tier status, a project must meet all of the mandatory measures in Chapter 5 and, in addition, meet the provisions of this section.

    A5.601.3.2 Energy performance. For the purposes of mandatory energy efficiency standards in this code, the California Energy Commission will continue to adopt mandatory standards.

    A5.601.3.3 Tier 2. Comply with the energy efficiency requirements in Section A5.203.1.1 and Section A5.203.1.2.2.

    A5.601.3.4 Voluntary measures for Tier 2. In addition to the provisions of Sections A5.601.3.1 and A5.601.3.3 above, compliance with the following voluntary measures from Appendix A5 is required for Tier 2:

    1. From Division A5.1, a. Comply with the designated parking requirements for fuel efficient vehicles for a minimum of 50 percent of parking capacity per Section A5.106.5.1. b. Electric vehicle (EV) charging [N] and Table A5.106.5.3.2 with footnotes. c. Comply with thermal emittance, solar reflectance or SRI values for cool roofs in Section A5.106.11.2 and Table A5.106.11.2.3. [1]

    d. Comply with three elective measures selected from this division.

    APPENDIX A5-42 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A5NONRESIDENTIAL VOLUNTARY MEASURES

    1. From Division A5.2 comply with TWO of the following:

    2. Outdoor lighting as described in A5.203.1.1.1.

    3. Service water heating in restaurants as described in A5.203.1.1.2.

    4. Warehouse Dock Seal Doors A5.203.1.1.3.

    5. Daylight Design Power Adjustments 5.203.1.1.4.

    6. Exhaust Air Heat Recovery A5.203.1.1.5.

    7. From Division A5.3,

  • CBC § 9-2 Medium relevance — show source text
    1. The current transformer mounting base must include termination bolts, Belleville washers, and nuts on the line and load sides necessary to connect the PG&E current transformers. See Section 9, for details about these internal components.

    2. The applicant’s service entrance conductors must be terminated on the top (line side) of the current-transformer mounting base or termination enclosure busing.

    3. The applicant’s load conductors must be terminated on the bottom (load side) of the current-transformer mounting base or termination enclosure busing.

    4. Applicant conduit must not be installed within 2 inches of any corner of the cabinet.

    5. Applicant’s conductors must be routed properly, ensuring they do not obstruct the PG&E current transformers or test switch areas.

    Service Conduit (in the Center Position)

    Transformer-Mounting Base Furnished and Installed by Applicant

    Sealable Studs (Four Places)

    Test Switch Locations (For Mounting Base Detail, See Figure 9-2 on Page 9-3.)

    duit er Position) Col2
    Line Side Line Side
    Load Side Load Side

    Front View 3-1/2” Max.

    W Dimensions: 3-Wire 1 ∅ = 24” Min. 4-Wire 3 ∅ = 36” Min.

    Side View

    Figure 6-7 Overhead-Fed Combination Meter and Current-Transformer Cabinet (201 Amps−400 Amps, 1or 3)

    6-11 2022 – 2023

    Section 6, Electric Metering: Residential

    6.4.2. (continued)

    CL of

    Lower Bolt

    See Subsection 5.3

    See Section 9, Figure 9-11 on Page 9-8

    Transformer Rated Meter Box

    Figure 6-8 Overhead-Fed, Separate-Bused, Current-Transformer Cabinet and Meter Box (201 Amps−400 Amps, 1or 3)

    6.4.3. Single Meter: Combination Overhead and Underground Service Equipment

    Enclosures designed for a combination of either overhead or underground service entrance conductors must meet all of the requirements for both types of conductor entries.

    A. See the requirements in Subsection 6.4.1., “Single Meter: Underground Service,” on Page 6-4, and Subsection 6.4.2., “Single Meter: Overhead Service,” on Page 6-8.

    B. For overhead services, applicants must ensure the service entrance conductors are long enough to provide a bending radius that is equal to or greater than 10 times the diameter of the conductors.

    C. Overhead service panels must have a manufactured raceway built for the panel to isolate the service entrance conductors.

    2022 – 2023 6-12

    Section 6, Electric Metering: Residential

    6.4.3. (continued)

  • CBC § 11.2 Medium relevance — show source text

    Table R905.11.2

    D6223/D6223M—2021: Specification for Atactic Polypropylene (APP) Modified Bituminous Sheet Materials Using a Combination of Polyester and Glass Fiber Reinforcements

    Table R905.11.2

    D6298—2016: Specification for Fiberglass Reinforced Styrene-Butadiene-Styrene (SBS) Modified Bituminous Sheets with a Factory Applied Metal Surface

    Table R905.11.2

    D6305—21: Practice for Calculating Bending Strength Design Adjustment Factors for Fire-Retardant-Treated Plywood Roof Sheathing

    R302.15.6

    D6380/D6380M—2003(2018): Standard Specification for Asphalt Roll Roofing (Organic Felt) R905.1.1, Table R905.1.1(1), R905.2.8.2, R905.5.4

    D6464—2003A(2017): Standard Specification for Expandable Foam Adhesives for Fastening Gypsum Wallboard to Wood Framing

    R702.3.1.1

    2025 CALIFORNIA RESIDENTIAL CODE 44-11

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    REFERENCED STANDARDS

    D6694/D6694M—08(2013)E1: Standard Specification for Liquid-Applied Silicone Coating Used in Spray Polyurethane Foam Roofing Systems Table R905.13.3, R905.14.2, Table R909.2

    D6754/D6754M—2015: Standard Specification for Ketone Ethylene Ester Based Sheet Roofing

    Table R905.12

    D6757/D6757M—2018: Specification for Underlayment Felt Containing Inorganic Fibers Used in Steep-Slope Roofing R905.1.1, Table R905.1.1(1)

    D6841—21: Standard Practice for Calculating Design Value Treatment Adjustment Factors for Fire-Retardant-Treated Lumber

    R302.15.7

    D6878/D6878M—2021: Standard Specification for Thermoplastic Polyolefin-Based Sheet Roofing

    Table R905.12

    D6947/D6947M—2016: Standard Specification for Liquid Applied Moisture Cured Polyurethane Coating Used in Spray Polyurethane Foam Roofing System Table R905.13.3, R905.14.2, Table R909.2

    D7032—2021: Standard Specification for Establishing Performance Ratings for Wood-Plastic Composite and Plastic Lumber Deck Boards, Stair Treads, Guards, and Handrails

    R507.2.2, R507.2.2.1, R507.2.2.3, R507.2.2.4

    D7158—D7158M—20: Standard Test Method for Wind Resistance of Asphalt Shingles (Uplift Force/Uplift Resistance Method) R905.2.4.1, Table R905.2.4.1

    D7254—21: Standard Specification for Polypropylene (PP) Siding Table R703.3(1), R703.14

    D7425/D7425M—13(2019): Standard Specification for Spray Polyurethane Foam Used for Roofing Applications

    R905.13.2

  • CBC § 1.75 Medium relevance — show source text

    250|1.75|0.65|3.25|9.25|6.00|303844|303844| |1/0|2|SAPT-1/0-26|YE25R-60|0.250|1.75|0.65|3.25|9.25|6.00|303845|303845| |4/0|2/0|SAPT-4/0-206|YE28R-60|0.375|1.54|0.91|3.50|10.9|6.00|303846|W249
    U249
    U2492| |350|4/0|PTB-350-6|YE31AG3|0.460|2.25|1.12|4.70|10.7|6.00|303554|−
    U31ART
    U31ART2| |500/60
    0|500|PTM-500-346|YE34AP-
    GE|0.750|2.56|1.57|6.30|12.3|6.00|300013|−
    U34ART3
    U34ART2,3| |700|500|PTL-750|YE39AGB|0.750|2.56|1.60|6.30|12.3|6.00|303555|−

    P39ART| |1,000|700|PTF-1000-34
    6|YE44AG7|0.750|2.56|1.60|6.30|12.3|6.00|033757|−

    P44ART|

    1 Within this column, the first entry corresponds to a 6-ton press tool, the second entry corresponds to a 12-ton press tool, and the third entry corresponds to a 15-ton press tool. 2 A U-die adapter must be used when utilizing U-dies in 15-ton press tool. 3 Homac equivalent of this die is 106A.

    Notes

    1. The material for the pin terminals is on Table 41. Copper Rod-Soft Drawn, Tinned, Aluminum Connector EC Grade, Untinned

    2. Connector is supplied pre-filled with inhibitor and sealed.

    3. Connector is supplied pre-filled with inhibitor and sealed.

    4. Pin terminals connected to copper secondary conductors use a copper connector. Pin terminals connected to aluminum secondary conductors use a fired wedge or h-tap.

    Application

    1. To make straight connections of insulated aluminum secondary neutral to bare copper neutral, see Note 10 Page 7.
    2. To connect aluminum primary stress cone termination to terminal tap connector or cutout.
    3. To make watertight termination for secondary risers.

    015251 Page 38 of 39 Rev. #07: 03-25-22

    UG-1: Connectors Greenbook Connectors for Insulated Cables Underground Distribution Systems

    Pin Terminals (continued)

    Table 42 Color Coding Col2
    Color Coding Requirements for Plastic End Plugs in Pin Terminals Color Coding Requirements for Plastic End Plugs in Pin Terminals
    Conductor Size Plug Color
    #6 Blue
    #2 Red
    1/0 Yellow
    4/0 Pink
    350 Brown
    700 Purple

    Table 43 Specifications and Ordering Information for Copper Pin Terminal

  • CBC § 25218.5 High relevance — show source text

    (b) Certification Requirements for Manufactured Systems, Equipment, Appliances and Building Components.

    1. Appliances that are within the scope of Section 1601 of the Appliance Efficiency Regulations shall only be installed if they have been certified to the Energy Commission by the manufacturer, pursuant to the provisions of Title 20 California Code of Regulations, Section 1606; or
    2. Systems, equipment, appliances and building components that are required by Part 6 or the Reference Appendices to be certified to the Energy Commission, which are not appliances that are within the scope of Section 1601 of the Appliance Efficiency Regulations, shall only be installed if they are certified by the manufacturer in a declaration, executed under penalty of perjury under the laws of the State of California, that: A. All the information provided pursuant to the certification is true, complete, accurate and in compliance with all applicable requirements of Part 6; and B. The equipment, product, or device was tested using the test procedure specified in Part 6 if applicable
    3. The certification status of any system, equipment, appliance or building component shall be confirmed only by reference to: A. A directory published or approved by the Commission; or B. A copy of the application for certification from the manufacturer and the letter of acceptance from the Commission staff; or C. Written confirmation from the publisher of a Commission-approved directory that a device has been certified; or D. A Commission-approved label on the device.

    Note: Part 6 does not require a builder, designer, owner, operator, or enforcing agency to test any certified device to determine its compliance with minimum specifications or efficiencies adopted by the Commission.

    Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5 , 2 5402.8, and 25943, Public Resources Code.

    SECTION 110.1—MANDATORY REQUIREMENTS FOR APPLIANCES

    (a) Any appliance regulated by the Appliance Efficiency Regulations, Title 20 California Code of Regulations, Section 1601 et seq., may be installed only if the appliance fully complies with Section 1608(a) of those regulations.

    (b) Except for those circumstances described in Section 110.1(c), conformance with efficiency levels required to comply with Part 6 mandatory, prescriptive and performance standards shall be verified utilizing data from either:

    1. The Energy Commission’s database of certified appliances maintained pursuant to Title 20 California Code of Regulations Section 1606, and which is available at: www.energy.ca.gov/appliances/database/ ; or
    2. An equivalent directory published by a federal agency; or
    3. An approved trade association directory as defined in Title 20 California Code of Regulations Section 1606(h).

    (c) Conformance with efficiency levels required to comply with Part 6 mandatory, prescriptive and performance standards shall be demonstrated either by default to the mandatory efficiency levels specified in Part 6 or by following procedures approved by the Commission pursuant to Section 10-109 of Title 24, Part 1, when:

    1. Data to verify conformance with efficiency levels required to comply with Part 6 mandatory, prescriptive and performance standards is not available pursuant to subdivision (b); or
    2. Field verification and diagnostic testing is required for compliance with Part 6 and the Energy Commission has not approved a field verification and diagnostic test protocol that is applicable to the appliance; or
  • CBC § 13.3 Medium relevance — show source text

    CERTIFIED TO THE ENERGY COMMISSION means, when used in association with appliances, certified under Section 1606 of Title 20 of the California Code of Regulations; and otherwise means certified by the manufacturer in a declaration, executed under penalty of perjury under the laws of the State of California, that all the information provided pursuant to the certification is true, complete, accurate and in compliance with all applicable provisions of Part 6; and if applicable that the equipment, product or device was tested under the applicable test method specified in Part 6.

    CERTIFYING ORGANIZATION is an independent organization recognized by the Commission to certify manufactured devices for performance values in accordance with procedures adopted by the Commission.

    CIE 13.3 is the International Commission on Illumination (Commission Internationale de l’Eclairage) document titled “Method of Measuring and Specifying Colour Rendering Properties of Light Sources,” 1995 (CIE 13.3-1995).

    CIE 15 is the International Commission on Illumination (Commission Internationale de l’Eclairage) document titled “Technical Report: Colorimetry,” 2018 (CIE 15:2018).

    CIRCULATING FAN means a fan that is not a ceiling fan, but that is used to move air within a space that has no provision for connection to ducting or separation of the fan inlet from its outlet, and designed to be used for the general circulation of air.

    CLIMATE ZONES are the 16 geographic areas of California for which the commission has established typical weather data, prescriptive packages and energy budgets. Climate zones are defined by ZIP code and listed in Reference Joint Appendix JA2. FIGURE 100.1-A is an approximate map of the 16 climate zones.

    CLOSED-CIRCUIT COOLING TOWER is a cooling tower that utilizes indirect contact between a heated fluid, typically water or glycol, and the cooling atmosphere to transfer the source heat load through sensible heat, latent heat and mass transfer indirectly to the air, essentially combining a heat exchanger and cooling tower into an integrated and relatively compact device.

    CODES, CALIFORNIA HISTORICAL BUILDING CODE is the California Historical Building Code, California Code of Regulations, Title 24, Part 8 and Part 2 (Chapter 34).

    CODES, CBC is the 2025 California Building Code.

    CODES, CEC is the 2025 California Electrical Code.

    CODES, CFC is the 2025 California Fire Code.

    CODES, CMC is the 2025 California Mechanical Code.

    CODES, CPC is the 2025 California Plumbing Code.

    COEFFICIENT OF PERFORMANCE (COP), COOLING is the ratio of the rate of net heat removal to the rate of total energy input, calculated under designated operating conditions and expressed in consistent units, as determined using the applicable test method in the Appliance Efficiency Regulations or Section 110.2.

    COEFFICIENT OF PERFORMANCE (COP), HEATING is the ratio of the rate of net heat output to the rate of total energy input, calculated under designated operating conditions and expressed in consistent units, as determined using the applicable test method in the Appliance Efficiency Regulations or Section 110.2.

    COEFFICIENT OF PERFORMANCE (COP), HEAT PUMP is the ratio of the rate of useful heat output delivered by the complete heat pump unit (exclusive of supplementary heating) to the corresponding rate of energy input, in consistent units and as determined using the applicable test method in Appliance Efficiency Regulations or Section 110.2.

  • CBC § 6.4. Medium relevance — show source text
    1. Outdoor lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.8; and
    2. Lighting systems receiving the Institutional Tuning Power Adjustment Factor shall be tested in accordance with Reference Nonresidential Appendix NA7.6.4.
    3. Demand responsive controls required to control controlled receptacles shall be tested in accordance with Reference Nonresidential Appendix NA7.6.5.

    (b) Lighting control installation certificate requirements. To be recognized for compliance with Part 6 an installation certificate shall be submitted in accordance with Section 10-103(a) for any lighting control system, energy management control system, interlocked lighting system, lighting power adjustment factor, or additional wattage available for a videoconference studio, in accordance with the following requirements, as applicable:

    1. Certification that when a lighting control system is installed to comply with lighting control requirements in Part 6 it complies with the applicable requirements of Section 110.9; and complies with Reference Nonresidential Appendix NA7.7.1.

    2. Certification that when an energy management control system is installed to function as a lighting control required by Part 6 it functionally meets all applicable requirements for each application for which it is installed, in accordance with Sections 110.9, 130.0 through 130.5, 140.6 through 150.0, and 150.2; and complies with Reference Nonresidential Appendix NA7.7.2.

    3. Reserved.

    4. Reserved.

    5. Certification that interlocked lighting systems used to serve an approved area comply with Section 140.6(a)1; and comply with Reference Nonresidential Appendix NA7.7.4.

    6. Certification that lighting controls installed to earn a lighting power adjustment factor (PAF) comply with Section 140.6(a)2; and comply with Reference Nonresidential Appendix NA7.7.5.

    2025 CALIFORNIA ENERGY CODE 101

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—MANDATORY REQUIREMENTS FOR LIGHTING SYSTEMS AND EQUIPMENT, AND ELECTRICAL POWER DISTRIBUTION SYSTEMS

    1. Certification that additional lighting wattage installed for a videoconference studio complies with Section 140.6(c)2Gvii; and complies with Reference Nonresidential Appendix NA7.7.6.

    (c) When certification is required by Title 24, Part 1, Section 10-103.1, the acceptance testing specified by Section 130.4 shall be performed by a certified lighting controls acceptance test technician (CLCATT). If the CLCATT is operating as an employee, the CLCATT shall be employed by a certified lighting controls acceptance test employer. The CLCATT shall disclose on the Certificate of Acceptance a valid CLCATT certification identification number issued by an approved acceptance test technician certification provider. The CLCATT shall complete all certificate of acceptance documentation in accordance with the applicable requirements in Section 10-103(a)4.

    Note: Authority cited: Sections 25402, 25402.1 and 25213, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code .

    SECTION 130.5—ELECTRICAL POWER DISTRIBUTION SYSTEMS

  • CBC § 130.3 Medium relevance — show source text

    Exception to Section 130.3(a)2B: Outdoor signs in tunnels and large covered areas that are intended to be illuminated both day and night. 3. Demand responsive Electronic Message Center (EMC) control. See Section 110.12 for requirements for demand responsive EMC controls .

    Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.

    SECTION 130.4—LIGHTING CONTROL ACCEPTANCE AND INSTALLATION CERTIFICATE REQUIREMENTS

    Nonresidential buildings other than healthcare facilities and hotel/motel buildings shall comply with the applicable requirements of Sections 130.4(a) through 130.4(c). Healthcare facilities shall comply with the applicable acceptance and installation documentation requirements of OSHPD.

    (a) Lighting and receptacle control acceptance requirements. Before an occupancy permit is granted, indoor and outdoor lighting and receptacle controls serving the building, area or site and installed to comply with Section 110.12, 120.6(h)5B, 130.1, 130.2, 130.5 or 140.6 shall be certified as meeting the Acceptance Requirements for Code Compliance as specified by the Reference Nonresidential Appendix NA7.6 and NA7.8. A Certificate of Acceptance shall be submitted to the enforcement agency under Section 10-103(a) of Part 1, that the equipment and systems meet the acceptance requirements:

    1. Reserved.

    2. Reserved.

    3. Daylight responsive controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.1;

    4. Lighting shut-OFF controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.2;

    5. Demand responsive lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.6.3; and

    6. Outdoor lighting controls shall be tested in accordance with Reference Nonresidential Appendix NA7.8; and

    7. Lighting systems receiving the Institutional Tuning Power Adjustment Factor shall be tested in accordance with Reference Nonresidential Appendix NA7.6.4.

    8. Demand responsive controls required to control controlled receptacles shall be tested in accordance with Reference Nonresidential Appendix NA7.6.5.

    (b) Lighting control installation certificate requirements. To be recognized for compliance with Part 6 an installation certificate shall be submitted in accordance with Section 10-103(a) for any lighting control system, energy management control system, interlocked lighting system, lighting power adjustment factor, or additional wattage available for a videoconference studio, in accordance with the following requirements, as applicable:

    1. Certification that when a lighting control system is installed to comply with lighting control requirements in Part 6 it complies with the applicable requirements of Section 110.9; and complies with Reference Nonresidential Appendix NA7.7.1.

    2. Certification that when an energy management control system is installed to function as a lighting control required by Part 6 it functionally meets all applicable requirements for each application for which it is installed, in accordance with Sections 110.9, 130.0 through 130.5, 140.6 through 150.0, and 150.2; and complies with Reference Nonresidential Appendix NA7.7.2.

    3. Reserved.

    4. Reserved.

  • CBC § 601.2.4 Medium relevance — show source text

    A5.601.2.4 Voluntary measures for Tier 1. In addition to the provisions of Sections A5.601.2.1 and A5.601.2.3 above, compliance with the following voluntary measures from Appendix A5 is required for Tier 1:

    1. From Division A5.1, a. Comply with the designated parking requirements for high-efficiency vehicles for a minimum of 35 percent of parking capacity per Section A5.106.5.1. b. Electric vehicle (EV) charging [N] and Table A5.106.5.3.1 w/ footnotes. c. Comply with thermal emittance, solar reflectance or SRI values for cool roofs in Section A5.106.11.2 and Table A5.106.11.2.2. [1]

    d. Comply with one elective measure selected from this division. 2. From Division A5.2 comply with ONE of the following:

    1. Outdoor lighting as described in A5.203.1.1.1.

    2. Service water heating in restaurants as described in A5.203.1.1.2.

    3. Warehouse Dock Seal Doors A5.203.1.1.3.

    4. Daylight Design Power Adjustments 5.203.1.1.4.

    5. Exhaust Air Heat Recovery A5.203.1.1.5.

    6. From Division A5.3,

    a. Comply with the 12-percent reduction for indoor potable water use in Section A5.303.2.3.1. b. Comply with one elective measure selected from this division.

    1. From Division A5.4,

    a. Comply with recycled content of 10 percent of materials based on estimated total cost, or use two products from Table A5.405.4 for at least 75 percent by cost in Section A5.405.4. b. Comply with the 65-percent reduction in construction and demolition waste in Section A5.408.3.1. c. Comply with one elective measure selected from this division.

    1. From Division A5.5,

    a. Comply with resilient flooring systems for 90 percent of resilient flooring in Section A5.504.4.7. b. Comply with thermal insulation meeting 2009 CHPS low-emitting materials list in Section A5.504.4.8. c. Comply with one elective measure selected from this division. 6. Comply with one additional elective measure selected from any division.

    1 Cool roof is required for compliance with Tiers 1 and 2 and may be used to meet energy standards in Part 6, exceed energy standards and to mitigate heat island effect.

    A5.601.3 CALGreen Tier 2.

    A5.601.3.1 Prerequisites. To achieve CALGreen tier status, a project must meet all of the mandatory measures in Chapter 5 and, in addition, meet the provisions of this section.

    A5.601.3.2 Energy performance. For the purposes of mandatory energy efficiency standards in this code, the California Energy Commission will continue to adopt mandatory standards.

    A5.601.3.3 Tier 2. Comply with the energy efficiency requirements in Section A5.203.1.1 and Section A5.203.1.2.2.

  • CBC § 203.1.1 Medium relevance — show source text

    A4.203.1.1 Long-term system cost (LSC). LSC rating for the building’s Proposed Design shall be computed by Compliance Software certified by the Energy Commission as specified in Title 24, Part 6, Section 100.1 and 150.1(b), and shall reduce the LSC required in the Compliance Software for minimum performance-based compliance with the California Energy Code by the compliance margin specified in Table A4.203.1.1. The rating shall be included in the Certificate of Compliance documentation.

    TABLE A4.203.1.1—RECOMMENDED LSC MARGINS BY CLIMATE ZONES Col2
    CALIFORNIA ENERGY CODE CLIMATE ZONE TOTAL LSC COMPLIANCE MARGIN
    1 2.70
    2 1.62
    3 1.10
    4 1.11
    5 1.01
    6 0.24
    7 0.24
    8 0.21
    9 0.20
    10 0.18
    11 1.11
    12 1.05
    13 0.96
    14 1.21
    15 0.59
    16 1.68
    Note: Community shared options complying with Title 24, Part 1, Section 10-115 may be used to achieve LSC targets. Note: Community shared options complying with Title 24, Part 1, Section 10-115 may be used to achieve LSC targets.

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE APPENDIX A4-9

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    APPENDIX A4RESIDENTIAL VOLUNTARY MEASURES

    A4.203.1.2 Prerequisite options. In addition, a minimum of TWO of the efficiency measures specified in Sections A4.203.1.2.1 through A4.203.1.2.7 must be met.

    A4.203.1.2.1 Roof deck insulation, or ducts in conditioned space. Meet one of the three options for the location of ducts and air handlers as well as insulation R -values and installation of a radiant barrier as specified in Title 24, Part 6, Section 150.1(c)9A or B:

    1. Below roof deck insulation with a minimum R -value of 19; or,

    2. Continuous above deck insulation with a minimum R-8 and with an air space present between the roofing and the roof deck; or,

    3. All ducts and air handlers in conditioned space as specified in the Title 24, Part 6, Reference Appendix RA3.1.

    A4.203.1.2.2 High performance walls. Meet the climate zone dependent U -factor or insulation R -value for either 2x6 or 2x4 framing as specified in Title 24, Part 6, Section 150.1(c)1B: maximum U -factor of 0.048.

    A4.203.1.2.3 Compact hot water distribution system. Meet the requirements for installation of Compact Hot Water Distribution Systems specified in the Title 24, Part 6, Reference Appendix RA3.6.5.

  • CBC § 5.57 Medium relevance — show source text

    35|5.57|5.72|5.95|6.11|6.23| |42|75|33|5.27|5.49|5.64|5.85|6.00|6.11| |41|75|34|5.19|5.41|5.56|5.75|5.89|5.99| |46|80|34|5.19|5.41|5.56|5.75|5.89|5.99| |40|75|35|5.11|5.33|5.48|5.67|5.79|5.88| |45|80|35|5.11|5.33|5.48|5.67|5.79|5.88| |44|80|36|5.03|5.26|5.40|5.58|5.70|5.79| |43|80|37|4.94|5.18|5.32|5.50|5.62|5.70| |42|80|38|4.84|5.10|5.25|5.43|5.53|5.61| |41|80|39|4.73|5.01|5.17|5.35|5.46|5.53| |46|85|39|4.73|5.01|5.17|5.35|5.46|5.53| |40|80|40|4.62|4.92|5.09|5.27|5.38|5.45| |45|85|40|4.62|4.92|5.09|5.27|5.38|5.45| |44|85|41|4.49|4.82|5.00|5.20|5.30|5.38| |43|85|42|4.35|4.71|4.91|5.12|5.23|5.30| |42|85|43|4.19|4.59|4.81|5.03|5.15|5.22| |41|85|44|4.02|4.46|4.70|4.94|5.06|5.14| |40|85|45|3.84|4.32|4.58|4.84|4.98|5.06| |Condenser DT2|Condenser DT2|Condenser DT2|14.04|11.23|9.36|7.02|5.62|4.68| |1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2.

  • CBC § 7.47 Medium relevance — show source text

    15|7.47|7.72|8.10|8.37|8.58| |45|75|30|7.05|7.35|7.58|7.93|8.18|8.36| |44|75|31|6.95|7.23|7.45|7.77|8.00|8.16| |43|75|32|6.85|7.13|7.33|7.63|7.83|7.98| |42|75|33|6.75|7.03|7.22|7.49|7.68|7.82| |41|75|34|6.65|6.93|7.12|7.37|7.55|7.67| |46|80|34|6.65|6.93|7.12|7.37|7.55|7.67| |40|75|35|6.55|6.83|7.01|7.26|7.42|7.54| |45|80|35|6.55|6.83|7.01|7.26|7.42|7.54| |44|80|36|6.44|6.73|6.92|7.15|7.30|7.41| |43|80|37|6.32|6.63|6.82|7.05|7.19|7.30| |42|80|38|6.20|6.53|6.72|6.95|7.09|7.19| |41|80|39|6.06|6.42|6.62|6.85|6.99|7.08| |46|85|39|6.06|6.42|6.62|6.85|6.99|7.08| |40|80|40|5.91|6.30|6.52|6.76|6.89|6.98| |45|85|40|5.91|6.30|6.52|6.76|6.89|6.98| |44|85|41|5.75|6.17|6.403|6.66|6.79|6.89| |43|85|42|5.57|6.03|6.28|6.55|6.70|6.79| |42|85|43|5.37|5.88|6.16|6.44|6.59|6.69| |41|85|44|5.15|5.71|6.01|6.33|6.49|6.59| |40|85|45|4.91|5.53|5.86|6.20|6.37|6.48| |Condenser DT2|Condenser DT2|Condenser DT2|14.04|11.23|9.36|7.02|5.62|4.68| |1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2.

  • CBC § 6.44 Medium relevance — show source text

    17|6.44|6.66|6.99|7.23|7.40| |45|75|30|6.08|6.34|6.54|6.84|7.06|7.22| |44|75|31|6.00|6.24|6.43|6.71|6.90|7.05| |43|75|32|5.91|6.15|6.33|6.58|6.76|6.89| |42|75|33|5.83|6.07|6.23|6.47|6.63|6.75| |41|75|34|5.74|5.98|6.14|6.36|6.51|6.62| |46|80|34|5.74|5.98|6.14|6.36|6.51|6.62| |40|75|35|5.65|5.90|6.05|6.26|6.40|6.51| |45|80|35|5.65|5.90|6.05|6.26|6.40|6.51| |44|80|36|5.56|5.81|5.97|6.17|6.30|6.40| |43|80|37|5.46|5.73|5.89|6.08|6.21|6.30| |42|80|38|5.35|5.64|5.80|6.00|6.12|6.20| |41|80|39|5.23|5.54|5.71|5.91|6.03|6.11| |46|85|39|5.23|5.54|5.71|5.91|6.03|6.11| |40|80|40|5.10|5.44|5.62|5.83|5.95|6.03| |45|85|40|5.10|5.44|5.62|5.83|5.95|6.03| |44|85|41|4.96|5.33|5.55|5.74|5.86|5.94| |43|85|42|4.81|5.21|5.42|5.66|5.78|5.86| |42|85|43|4.63|5.08|5.31|5.56|5.69|5.77| |41|85|44|4.45|4.93|5.19|5.46|5.60|5.69| |40|85|45|4.24|4.77|5.06|5.35|5.50|5.59| |Condenser DT2|Condenser DT2|Condenser DT2|14.04|11.23|9.36|7.02|5.62|4.68| |1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2.

  • California Building Code Medium relevance — show source text


    5
    10
    15|64
    99
    126
    NA|613
    594
    565
    NA|336
    313
    296
    281|77
    118
    148
    171|779
    759
    727
    698|441
    416
    394
    375|92
    139
    173
    198|968
    946
    912
    880|562
    533
    567
    485|127
    186
    229
    259|1376
    1352
    1315
    1280|841
    828
    777
    742| |20|2
    5
    10
    15
    20|61
    95
    122
    NA
    NA|678
    658
    627
    NA
    NA|375
    350
    332
    314
    296|73
    113
    143
    165
    186|867
    845
    811
    780
    750|491
    463
    440
    418
    397|87
    133
    167
    191
    214|1083
    1059
    1022
    987
    955|627
    597
    566
    541
    513|121
    179
    221
    251
    277|1548
    1523
    1482
    1443
    1406|953
    933
    879
    840
    807| |30|2
    5
    10
    15
    20
    30|57
    90
    115
    NA
    NA
    NA|762
    741
    709
    NA
    NA
    NA|421
    393
    373
    353
    332
    288|68
    106
    135
    156
    176
    NA|985
    962
    927
    893
    860
    NA|558
    526
    500
    476
    450
    416|81
    125
    158
    181
    203
    249|1240
    1216
    1176
    1139
    1103
    1035|717
    683
    648
    621
    592
    555|111
    169
    210
    239
    264
    318|1793
    1766
    1721
    1679
    1638
    1560|1112
    1094
    1025
    981
    940
    877| |50|2
    5

  • CBC § 6-1 Medium relevance — show source text

    Figure 6-1 Typical Underground Service-Termination Enclosure, Combination Meter-Socket Panel (Residential, 0 Amps−225 Amps) . . . . . . . . . . . . . 6-5

    Figure 6-2 Typical Service-Termination Enclosure, Combination Meter-Socket Panel for a Class 320 Meter (Residential, 120/240-Volt, 226-Amp Through 320-Amp Service) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6

    Figure 6-3 Underground Combination Meter and Current-Transformer Cabinet (201 Amps−400 Amps, 1∅ or 3∅) . . . . . . . . . . . . . . . . . . . . . 6-7

    Figure 6-4 Typical Underground, Separate-Bused, Current-Transformer Cabinet and Safety-Socket Meter Box Assembly (201 Amps−400 Amps, 3∅ and 201 Amps−600 Amps, 1∅) . . . . . . . . 6-8

    Figure 6-5 Combination Meter Socket Load Center . . . . . . . . . . . . . . . . . . . . . . . . 6-9

    Figure 6-6 Typical Combination Meter and Service Termination Panel for a Class 320 Meter (Residential, 120/240-Volt, 226-Amp Through 320-Amp Service) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10

    Figure 6-7 Overhead-Fed Combination Meter and Current-Transformer Cabinet (201 Amps−400 Amps, 1∅ or 3∅) . . . . . . . . . . . . . . . . . . . . 6-11

    Figure 6-8 Overhead-Fed, Separate-Bused, Current-Transformer Cabinet and Meter Box (201 Amps−400 Amps, 1∅ or 3∅) . . . . . . . . . . . . . . . . . . 6-12

    Figure 6-9 Overhead- or Underground-Fed Combination Meter and Service-Termination Panel (100 Amps−225 Amps, 1∅) . . . . . . . . . . 6-13

    Figure 6-10 Overhead or Underground Service-Termination Meter Panel with Manual Bypass studs (320 Amps, 120/240-Volt, 1∅) . . . . . . . . . 6-14

    Figure 6-11 Overhead Service, Grouped-Meter Installation Without a Main Switch (400 Amps Max, 1∅ or 3∅) . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16

    Figure 6-12 Underground Service, Grouped-Meter Installation Without a Main Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-16

  • California Building Code Medium relevance — show source text


    5
    10
    15
    20|NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA|38
    35
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA|73
    67
    59
    NA
    NA|NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA|123
    115
    105
    95
    80|NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA|200
    183
    170
    156
    144|163
    NA
    NA
    NA
    NA|520
    NA
    NA
    NA
    NA|273
    252
    235
    217
    202| |30|2
    5
    10
    15
    20
    30|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|41
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|81
    75
    66
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|136
    127
    113
    105
    88
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|215
    196
    182
    168
    155
    NA|158
    NA
    NA
    NA
    NA
    NA|578
    NA
    NA
    NA
    NA
    NA|302
    279
    260
    240
    223
    182| |50|2
    5
    10
    15
    20
    30|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|91
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|160
    149
    136
    124
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|250
    228
    212
    195
    180
    NA|NA
    NA
    NA
    NA
    NA
    NA|NA
    NA
    NA
    NA
    NA
    NA|350
    321
    301
    278
    258
    NA| |Minimum
    internal area of
    chimney
    (square inches)|Minimum
    internal

  • CBC § 5-17 Medium relevance — show source text

    Figure 5-17 Multiple Remote Switchboard or Meter-Panel Locations . . . . . . . . . . 5-35

    Figure 5-18 Grounding Outside of the Sealed Section−Self-Contained Meter . . . . 5-37

    Figure 5-19 Grounding Outside of the Sealed Section–Transformer Rated Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-37

    Figure 5-20 Temporary-Service Metering Pedestal . . . . . . . . . . . . . . . . . . . . . . . . . 5-40

    Figure 5-21 Plug-In Temporary Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-41

    Figure 5-22 Typical Plug-In Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-41

    Figure 5-23 Transfer Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-45

    Figure 5-24 SLD Manual Transfer Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-46

    v 2022 – 2023

    List of Figures

    Contents Page

    Section 6 – Electric Metering: Residential

    Figure 6-1 Typical Underground Service-Termination Enclosure, Combination Meter-Socket Panel (Residential, 0 Amps−225 Amps) . . . . . . . . . . . . . 6-5

    Figure 6-2 Typical Service-Termination Enclosure, Combination Meter-Socket Panel for a Class 320 Meter (Residential, 120/240-Volt, 226-Amp Through 320-Amp Service) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6

    Figure 6-3 Underground Combination Meter and Current-Transformer Cabinet (201 Amps−400 Amps, 1∅ or 3∅) . . . . . . . . . . . . . . . . . . . . . 6-7

    Figure 6-4 Typical Underground, Separate-Bused, Current-Transformer Cabinet and Safety-Socket Meter Box Assembly (201 Amps−400 Amps, 3∅ and 201 Amps−600 Amps, 1∅) . . . . . . . . 6-8

    Figure 6-5 Combination Meter Socket Load Center . . . . . . . . . . . . . . . . . . . . . . . . 6-9

    Figure 6-6 Typical Combination Meter and Service Termination Panel for a Class 320 Meter (Residential, 120/240-Volt, 226-Amp Through 320-Amp Service) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10

  • CBC § 6.4 Medium relevance — show source text

    6.4_|||X|||||||||||||||||||||| |907.2.6.5|||X|||||||||||||||||||||| |907.2.9|||X|||||||||||||||||||||| |907.2.9.1|||X|||||||||||||||||||||| |907.2.9.3|||X|||||||||||||||||||||| |907.2.9.4|||X|||||||||||||||||||||| |907.2.9.4.1|||X|||||||||||||||||||||| |907.2.10|||X|||||||||||||||||||||| |907.2.11|||X|||||||||||||||||||||| |907.2.11.1|||X|||||||||||||||||||||| |907.2.11.2|||X|||||||||||||||||||||| |907.2.11.2.1 – 907.2.11.2.6|||X|||||||||||||||||||||| |907.2.11.3|||X|||||||||||||||||||||| |907.2.11.4|||X|||||||||||||||||||||| |907.2.11.6|||X|||||||||||||||||||||| |907.2.11.8|||X|||||||||||||||||||||| |907.2.11.9|||X|||||||||||||||||||||| |907.2.12|||X|||||||||||||||||||||| |907.2.13|||X|||||||||||||||||||||| |907.2.13.1|||X|||||||||||||||||||||| |907.2.13.1.2|||X|||||||||||||||||||||| |907.2.24 with subsections|||X|||||||||||||||||||||| |907.2.25 with subsections|||X|||||||||||||||||||||| |907.2.26 with subsections|||X|||||||||||||||||||||| |907.2.27|||X||||||||||||||||||||||

    2025 CALIFORNIA BUILDING CODE 9-3

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CALIFORNIA BUILDING CODE – MATRIX ADOPTION TABLE

    CHAPTER 9 – FIRE PROTECTION AND LIFE SAFETY SYSTEMS—continued

  • California Building Code Medium relevance — show source text


    2
    5
    10
    15
    20|190
    182
    224
    277
    325
    374|1053
    708
    692
    666
    640
    616|573
    468
    457
    437
    419
    400|238
    227
    279
    339
    393
    448|1379
    914
    896
    866
    838
    810|750
    611
    596
    570
    549
    526|326
    309
    381
    457
    526
    592|1751
    1146
    1126
    1092
    1060
    1028|927
    754
    734
    702
    677
    651|473
    443
    547
    646
    730
    808|2631
    1689
    1665
    1626
    1587
    1550|1346
    1098
    1074
    1037
    1005
    973| |30|0
    2
    5
    10
    15
    20
    30|184
    175
    215
    265
    312
    360
    461|1168
    823
    806
    777
    750
    723
    670|647
    533
    521
    501
    481
    461
    426|229
    219
    269
    327
    379
    433
    541|1542
    1069
    1049
    1017
    985
    955
    895|852
    698
    684
    662
    638
    615
    574|312
    296
    366
    440
    507
    570
    704|1971
    1346
    1324
    1287
    1251
    1216
    1147|1056
    863
    846
    821
    794
    768
    720|454
    424
    524
    620
    702
    780
    937|2996
    1999
    1971
    1927
    1884
    1841
    1759|1545
    1308
    1283
    1243
    1205
    1166
    1101| |50|0
    2
    5

  • CBC § 7-4 Medium relevance — show source text

    Figure 7-4 Separate-Bused Current-Transformer Cabinet and Meter Box with Underground Service-Termination Pull Box (201 Amps−400 Amps, 3∅ and 201 Amps−600 Amps, 1∅) . . . . . . . . 7-8

    Figure 7-5 Underground Service Combination Meter and Current-Transformer Cabinet (600 Amps, 1Ø or 3Ø, 800 Amps 3Ø) . . . . . . . . . . . . . . . . . . 7-10

    Figure 7-6 Switchboard Pull Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11

    Figure 7-7 Separate Pull Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11

    Figure 7-8 Bottom-Fed Service Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11

    Figure 7-9 Overhead-Fed Combination Meter and Current-Transformer Cabinet, (201 Amps−400 Amps, 1∅ or 3∅) . . . . . . . . . . . . . . . . . . . . 7-13

    Figure 7-10 Overhead-Fed, Separate-Bused, Current-Transformer Cabinet and Safety-Socket Meter Box (201 Amps−400 Amps, 1∅ or 3∅) . . . . . . 7-14

    Figure 7-11 Overhead, Service-Termination, Standard Switchboard Service Section (0 Volts−600 Volts) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-15

    Figure 7-12 Overhead Service, Grouped-Meter Installation Without a Main Switch (Max. 400 Amps, 1∅ or 3∅) . . . . . . . . . . . . . . . . . . . . . . . . . . 7-17

    Figure 7-13 Underground Service, Grouped-Meter Installation Without a Main Switch (Max. 400 Amps, 3∅, or 600 Amps, 1∅) . . . . . . . . . . . . . . . . 7-17

    Figure 7-14 Grouped-Meter Installation With a Main Switch (Max. 400 Amps, 3∅, 600 Amps, 1∅) . . . . . . . . . . . . . . . . . . . . . . . . 7-17

    Section 8 – Electric Metering: Pedestals

    Figure 8-1 Residential Electric Metering Pedestal . . . . . . . . . . . . . . . . . . . . . . . . . 8-2

    Figure 8-2 Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5

  • California Building Code Medium relevance — show source text


    2
    5
    10
    15|36
    38
    51
    NA
    NA|93
    69
    63
    NA
    NA|57
    47
    44
    39
    NA|56
    57
    75
    95
    NA|190
    136
    128
    116
    NA|111
    93
    86
    79
    72|80
    80
    102
    128
    158|325
    225
    216
    201
    186|186
    149
    140
    131
    124|116
    115
    144
    182
    220|499
    337
    326
    308
    290|283
    224
    217
    203
    192|153
    148
    182
    228
    272|713
    473
    459
    438
    418|388
    314
    298
    284
    269| |20|0
    2
    5
    10
    15
    20|35
    37
    50
    NA
    NA
    NA|96
    74
    68
    NA
    NA
    NA|60
    50
    47
    41
    NA
    NA|54
    56
    73
    93
    NA
    NA|200
    148
    140
    129
    NA
    NA|118
    99
    94
    86
    80
    NA|78
    78
    100
    125
    155
    186|346
    248
    239
    223
    208
    192|201
    165
    158
    146
    136
    126|114
    113
    141
    177
    216
    254|537
    375
    363
    344
    325
    306|306
    248
    239
    224
    210
    196|149
    144
    178
    222
    264
    309|772
    528
    514
    491
    469
    448|428
    344
    334
    316
    301
    285| |30|0
    2
    5

  • CBC § 140.6 Medium relevance — show source text

    To qualify for any of the power adjustment factors in this table, the installation shall comply with the applicable requirements in Section 140.6(a)2.
    b. Only one PAF may be used for each qualifying luminaire unless combined below.
    c. Lighting controls that are required for compliance with Part 6 shall not be eligible for a PAF.|a. To qualify for any of the power adjustment factors in this table, the installation shall comply with the applicable requirements in Section 140.6(a)2.
    b. Only one PAF may be used for each qualifying luminaire unless combined below.
    c. Lighting controls that are required for compliance with Part 6 shall not be eligible for a PAF.|a. To qualify for any of the power adjustment factors in this table, the installation shall comply with the applicable requirements in Section 140.6(a)2.
    b. Only one PAF may be used for each qualifying luminaire unless combined below.
    c. Lighting controls that are required for compliance with Part 6 shall not be eligible for a PAF.|

    2025 CALIFORNIA ENERGY CODE 131

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND PRESCRIPTIVE

    COMPLIANCE APPROACHES FOR ACHIEVING ENERGY EFFICIENCY

    1. Lighting wattage excluded. The watts of the following indoor lighting applications may be excluded from adjusted indoor lighting power. (Indoor lighting not listed below shall comply with all applicable nonresidential indoor lighting requirements in Part 6): A. In theme parks: lighting for themes and special effects; B. Studio lighting for film or photography, provided that these lighting systems are in addition to and separately switched from a general lighting system; C. Lighting for dance floors, lighting for theatrical and other live performances, and theatrical lighting used for religious worship, provided that these lighting systems are additions to a general lighting system and are separately controlled by a multiscene or theatrical cross-fade control station accessible only to authorized operators; Lighting intended for makeup, hair, and costume preparation in performing arts facility dressing rooms, provided that the lighting is separately switched from the general lighting system, switched independently at each dressing station, and is controlled with a vacancy sensor. D. In civic facilities, transportation facilities, convention centers and hotel function areas: lighting for temporary exhibits, if the lighting is in addition to a general lighting system, and is separately controlled from a panel accessible only to authorized operators; E. Lighting installed by the manufacturer in walk-in coolers or freezers, vending machines, food preparation equipment, and scientific and industrial equipment; F. Examination and surgical lights, low ambient night lights and lighting integral to medical equipment, provided that these lighting systems are additions to and separately switched from a general lighting system; G. Lighting for plant growth or maintenance in non-CEH spaces, if it is controlled by a multilevel astronomical timeswitch control that complies with the applicable provisions of Section 110.9; H. Lighting equipment that is for sale; I. Lighting demonstration equipment in lighting education facilities; J. Lighting that is required for exit signs subject to the CBC. Exit signs shall meet the requirements of the Appliance Efficiency Regulations; K. Exitway or egress illumination that is normally off and that is subject to the CBC; L. In hotel/motel buildings, lighting in guest rooms (lighting in hotel/motel guestrooms shall comply with Section 130.0(b).
  • CBC § 2.25 Medium relevance — show source text

    00|2.25|0.70|DR|3.70|1.05|DR|DR| |Minimum 33
    mil steel
    furring or
    minimum
    1x wood
    furringc|33 mil cold-
    formed steel
    stud|#10 screw|Steel thick-
    ness plus 3
    threads|16|3.85|1.45|DR|DR|3.40|DR|DR|DR| |Minimum 33
    mil steel
    furring or
    minimum
    1x wood
    furringc|33 mil cold-
    formed steel
    stud|#10 screw|Steel thick-
    ness plus 3
    threads|24|3.40|DR|DR|DR|2.70|DR|DR|DR| |Minimum 33
    mil steel
    furring or
    minimum
    1x wood
    furringc|43 mil or
    thicker cold-
    formed steel
    stud|#8 Screw|Steel thick-
    ness plus 3
    threads|12|3.00|1.80|DR|DR|3.00|0.65|DR|DR| |Minimum 33
    mil steel
    furring or
    minimum
    1x wood
    furringc|43 mil or
    thicker cold-
    formed steel
    stud|#8 Screw|Steel thick-
    ness plus 3
    threads|16|3.00|1.00|DR|DR|2.85|DR|DR|DR| |Minimum 33
    mil steel
    furring or
    minimum
    1x wood
    furringc|43 mil or
    thicker cold-
    formed steel
    stud|#8 Screw|Steel thick-
    ness plus 3
    threads|24|2.85|DR|DR|DR|2.20|DR|DR|DR| |Minimum 33
    mil steel
    furring or
    minimum
    1x wood
    furringc|43 mil or
    thicker cold-
    formed steel
    stud|#10 screw|Steel thick-
    ness plus 3
    threads|12|4.00|3.85|2.80|1.80|4.00|3.05|1.50|DR| |Minimum 33
    mil steel
    furring or
    minimum
    1x wood
    furringc|43 mil or
    thicker cold-
    formed steel
    stud|#10 screw|Steel thick-
    ness plus 3
    threads|16|4.00|3.30|1.95|0.60|4.00|2.25|DR|DR| |Minimum 33
    mil steel
    furring or
    minimum
    1x wood
    furringc|43 mil or
    thicker cold-
    formed steel
    stud|#10 screw|Steel thick-
    ness plus 3
    threads|24|4.00|2.25|DR|DR|4.00|0.65|DR|DR| |For SI: 1 inch = 25.4 mm, 1 pound per square foot (psf) = 0.0479 kPa, 1 pound per square inch = 0.00689 MPa.
    DR = Design Required, o.c. = on center.
    a. Wood furring shall be spruce-pine-fir or any softwood species with a specific gravity of 0.42 or greater.

  • CBC § 6.1507 Medium relevance — show source text

    LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|

    A6.207.1.2 Controls for heat pumps with supplementary electric resistance heaters. Heat pumps with supplementary electric resistance heaters shall have controls:

    A6.207.1.2.1 That prevent supplementary heater operation when the heating load can be met by the heat pump alone; and

  • CBC § 180.2 Medium relevance — show source text

    2025 CALIFORNIA ENERGY CODE 283

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    MULTIFAMILY BUILDINGS—ADDITIONS, ALTERATIONS AND REPAIRS TO EXISTING MULTIFAMILY BUILDINGS

    EXCEPTION 2 to Section 180.2(c): Where the space in the attic or rafter area is not large enough to accommodate the required R- value, the entire space shall be filled with insulation, provided such installation does not violate Section 1203.2 of Title 24, Part 2.

    NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8 and 25943, Public Resources Code .

    SECTION 180.3—REPAIRS

    Repairs shall not increase the preexisting energy consumption of the repaired component, system or equipment.

    NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8 and 25943, Public Resources Code .

    SECTION 180.4 —WHOLE BUILDING

    Any addition or alteration may comply with the requirements of Title 24, Part 6 by meeting the requirements for the entire building.

    NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8 and 25943, Public Resources Code .

    284 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    CALIFORNIA MECHANICAL CODE, CALIFORNIA CODE OF REGULATIONS, TITLE 24, PART 4, CHAPTER 6, DUCT SYSTEMS

    TABLE P4-A ADOPTION TABLE

    CODE SECTION Col2 AGENCY
    Adopt entire Chapter as amended
    (amended sections listed below)1
    CEC
    601.0 X
    602.0 X
    603.0 X
    604.0 X
    605.0 X
    1. Adopted by reference for Occupancies A, B, E, F, H, I, L, M, R, S and U; see Sections 110.8(d)3, 120.4 and 150.0(m).

    2025 CALIFORNIA ENERGY CODE 285

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    286 2025 CALIFORNIA ENERGY CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    1-A STANDARDS AND DOCUMENTS

    REFERENCED IN THE ENERGY CODE

  • CBC § 140.9 Medium relevance — show source text
    1. In a jurisdiction where gas heating is allowed.

    Exception 4 to Section 140.9(c)6: Buildings with an exhaust air heat recovery system and heat recovery chillers designed to provide at least 40 percent of the peak heating load from exhaust heat recovery.

    Exception 5 to Section 140.9(c)6: Exhaust systems requiring wash down systems such as exhaust systems dedicated to perchloric acid fume hoods.

    Exception to Section 140.9(c): Healthcare facilities.

    Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code . Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8 and 25943, Public Resources Code.

    SECTION 140.10—PRESCRIPTIVE REQUIREMENTS FOR PHOTOVOLTAIC AND BATTERY ENERGY STORAGE SYSTEMS

    (a) Photovoltaic requirements. All newly constructed building types specified in Table 140.10-A, or mixed occupancy buildings where at least 80 percent of the floor area of the building serves one or more of these building types, shall have a newly installed photovoltaic (PV) system meeting the minimum qualification requirements of Reference Joint Appendix JA11. The PV capacity in kW dc shall not be less than the smaller of the minimum rated PV system capacity determined by Equation 140.10-A, or the total of all available solar access roof areas (SARA) multiplied by 18 for steep-sloped roofs or multiplied by 14 for low-sloped roofs. In mixed occupancy buildings, the minimum rated PV system capacity for the building shall be determined by applying Equation 140.10-A to the conditioned floor area of each of the listed building types and summing the capacities determined for each.

    1. SARA includes the area of the building’s roof space capable of structurally supporting a PV system, and the area of all roof space on covered parking areas, carports and all other newly constructed structures on the site that are compatible with supporting a PV system per Title 24, Part 2, Section 1511.10.

    2. SARA does NOT include:

    A. Any area that has less than 70 percent annual solar access. Annual solar access is determined by dividing the total annual solar insolation (accounting for shading obstructions) by the total annual solar insolation if the same areas were unshaded by those obstructions. For all roofs, all obstructions, including those that are external to the building, and obstructions that are part of the building design and elevation features may be considered for the annual solar access calculations.

    B. Occupied roofs as specified by CBC Section 503.1.4. C. Roof area that is otherwise not available due to compliance with: i. Other state building code requirements; or ii. Local building code requirements if the local building code requirements are confirmed by the Executive Director.

    2025 CALIFORNIA ENERGY CODE 145

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL AND HOTEL/MOTEL OCCUPANCIES—PERFORMANCE AND PRESCRIPTIVE

    COMPLIANCE APPROACHES FOR ACHIEVING ENERGY EFFICIENCY

    EQUATION 140.10-A—PHOTOVOLTAIC DIRECT CURRENT CAPACITY

    kW PVdc = (CFA × A)/1000

    where:

    kW PVdc = Minimum rated PV system capacity in kW.

  • CBC § 25.4 Medium relevance — show source text

    joints broken in alternate courses;
    cement-sand grout; 13 SWG iron wire rein-
    forcement in alternate horizontal joints.|90 tons|2 hrs|||7|2–4|2| |C-10-SB-3|10″|10″ × 12″ block encased columns;
    8″ × 6″ × 35 lbs “H” beam; protection: 2″
    foamed slag concrete blocks; 13 SWG wire at
    each horizontal joint; mortar at each joint.|90 tons|2 hrs|||7|5|2| |C-10-SB-4|101/2″|101/2″ × 12″ block encased steel columns;
    8″ × 6″ × 35 lbs “H” beam; protection: gravel
    aggregate concrete fill (unconsolidated) 2″
    thick hollow clay tiles with mortar at edges.|86 tons|56 min|||7|1|3/4| |C-10-SB-5|101/2″|101/2″ × 12″ block encased steel columns;
    8″ × 6″ × 35 lbs “H” beam; protection: 2″
    hollow clay tiles with mortar at edges.|86 tons|22 min|||7|1|1/4|

    For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 ton = 8.896 kN.

    Notes:

    1. Failure mode—collapse.

    2. Passed 2-hour fire test (Grade “C,” British).

    3. Passed hose stream test.

    4. Passed reload test.

    5. Passed 2-hour fire exposure but collapsed immediately following hose stream test.

    TABLE 2.5.2.2
    STEEL COLUMNS—BRICK AND BLOCK ENCASEMENTS
    MINIMUM DIMENSION 12″ TO LESS THAN 14″
    Col2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 Col10
    ITEM
    CODE
    MINIMUM
    DIMENSION
    CONSTRUCTION DETAILS PERFORMANCE PERFORMANCE REFERENCE NUMBER REFERENCE NUMBER REFERENCE NUMBER NOTES REC.
    HOURS
    ITEM
    CODE
    MINIMUM
    DIMENSION
    CONSTRUCTION DETAILS LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92 POST-BMS-92 POST-BMS-92
    C-12-SB-1 12″ 12″ × 15″ brick encased steel columns;
    8″ × 6″ × 35 lbs “H” beam; protection:
    25/8″ thick brick; joints broken in alternate
    courses; cement-sand grout; fill of broken
    brick and mortar.
    90 tons 1 hr
    49 min
    7 1 13/4

    For SI: 1 inch = 25.4 mm, 1 pound = 0.004448 kN, 1 ton = 8.896 kN.

    Notes:

    1. Failure mode—collapse.

    2025 CALIFORNIA EXISTING BUILDING CODE RESOURCE A-87

  • California Building Code Medium relevance — show source text

    |100 psf|1 hr
    23 min|||7|1, 2|11/3| |F/C-4-RC-9|4″|4″ deep (4370 psi);1/4″ reinforcement bars
    at 6″ pitch with3/4″ cover;1/4″ main rein-
    forcement bars at 4″ pitch perpendicular
    with1/2″ cover; 13′1″ span restrained.|150 psf|2 hrs|||7|1, 3|2| |F/C-4-RC-10|4″|4″ thick (5140 psi) deck;1/4″ reinforce-
    ment bars at 71/2″ pitch with7/8″ cover;3/8″
    main reinforcement bars at 33/4″ pitch
    perpendicular with1/2″ cover; 13′1″ span
    restrained.|140 psf|1 hr
    16 min|||7|1, 5|11/4| |F/C-4-RC-11|4″|4″ thick (4000 psi) concrete deck;
    3″ × 11/2″ × 4 lbs R.S.J.; 2′6″ C.R.S.; flush
    with top surface; 4″ × 6″ x 13 SWG mesh
    reinforcement 1″ from bottom of slab; 6′6″
    span restrained.|150 psf|2 hrs|||7|1, 3|2| |F/C-4-RC-12|4″|4″ deep (2380 psi) concrete deck;
    3″ × 11/2″ × 4 lbs R.S.J.; 2′6″ C.R.S.; flush
    with top surface; 4″ × 6″ x 13 SWG mesh
    reinforcement 1″ from bottom surface;
    6′6″ span restrained.|150 psf|1 hr
    3 min|||7|1, 2|1| |F/C-4-RC-13|41/2″|41/2″ thick (5200 psi) deck;1/4″ reinforce-
    ment bars at 71/4″ pitch with7/8″ cover;3/8″
    main reinforcement bars at 33/4″ pitch
    perpendicular with1/2″ cover; 13′1″ span
    restrained.|140 psf|2 hrs|||7|1, 3|2| |F/C-4-RC-14|41/2″|41/2″ deep (2525 psi) concrete deck;1/4″
    reinforcement bars at 71/2″ pitch with7/8″
    cover;3/8″ main reinforcement bars at
    33/8″ pitch perpendicular with1/2″ cover;
    13′1″ span restrained.|150 psf|42 min|||7|1, 5|2/3| |F/C-4-RC-15|41/2″|41/2″ deep (4830 psi) concrete deck;
    11/2″ × No.

  • CBC § 1.1.2 Medium relevance — show source text

    35|35|35|35| ||||50|76|74|74|80|85|89|31|31|31|31|31|31|31| |||100|43|72|73|73|75|78|68|25|25|25|25|25|25|25| |||94|42|63|64|64|65|69|67|20|20|20|102|102|102|102| |||93|41|58|59|59|60|66|22|12|12|12|101|108|108|108| |||54|40|57|53|53|45|61|21|11|11|11|83|30|30|30| |||46|37|52|49|49|44|32|13|10|15|15|82|29|29|29| |||39|16|48|33|33|34|9|8|6|14|14|26|27|27|107| ||38|36|4|24|17|17|2|3|5|1|7|23|19|18|18|28| ||||||||||||||||||

    0 1 2 3 4

    FIRE-RESISTANCE RATING (HOURS)

    TABLE 1.1.2
    MASONRY WALLS
    4″ TO LESS THAN 6″ THICK
    Col2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 Col10
    ITEM
    CODE
    THICKNESS CONSTRUCTION DETAILS PERFORMANCE PERFORMANCE REFERENCE NUMBER REFERENCE NUMBER REFERENCE NUMBER NOTES REC.
    HOURS
    ITEM
    CODE
    THICKNESS CONSTRUCTION DETAILS LOAD TIME PRE-
    BMS-92
    BMS-92 POST-
    BMS-92
    POST-
    BMS-92
    POST-
    BMS-92
    W-4-M-1 4″ Solid 3″ thick, gypsum blocks laid in 1:3 sanded
    gypsum mortar; facings:1/2″ of 1:3 sanded gypsum
    plaster (both sides).
    N/A 2 hrs 1 1 2
    W-4-M-2 4″ Solid clay or shale brick. N/A 1 hr
    15 min
    1 1,
  • CBC § 4.1.1 Medium relevance — show source text
    1. Failure mode—thermal; back face temperature rise.

    2. Passed hose stream test.

    3. Failed hose stream test.

    4. Test stopped at 4 hours before any endpoints were reached.

    5. A generalized cross section of this floor type follows:

    6. Plaster: base coat—retarded hemihydrate gypsum-sand; second coat—neat gypsum.

    7. Concrete in Item 7 is Portland cement-based but with crushed brick aggregates, while in Item 8, river sand and river gravels are used with the Portland cement.

    8. Load—unspecified.

    9. The 12-inch by 12-inch fire-clay tiles were laid end to end in rows spaced 2 [1] / 2 inches or 4 inches apart. The reinforcing steel was placed between these rows and the concrete cast around them and over the tile to form the structural floor.

    RESOURCE A-106 2025 CALIFORNIA EXISTING BUILDING CODE

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    RESOURCE A—GUIDELINES ON FIRE RATINGS OF ARCHAIC MATERIALS AND ASSEMBLIES

    SECTION IV—BEAMS

    TABLE 4.1.1
    REINFORCED CONCRETE BEAMS
    DEPTH 10″ TO LESS THAN 12″
    Col2 Col3 Col4 Col5 Col6 Col7 Col8 Col9 Col10
    ITEM CODE DEPTH CONSTRUCTION DETAILS PERFORMANCE PERFORMANCE REFERENCE NUMBER REFERENCE NUMBER REFERENCE NUMBER NOTES REC.
    HOURS
    ITEM CODE DEPTH CONSTRUCTION DETAILS LOAD TIME PRE-BMS-92 BMS-92 POST-BMS-92 POST-BMS-92 POST-BMS-92
    B-11-RC-1 11″ 24″ wide × 11″ deep reinforced concrete “T”
    beam (3290 psi); details: see Note 5 figure.
    8.8 tons 4 hrs
    2 min
    7 1, 2, 14 4
    B-10-RC-2 10″ 24″ wide × 10″ deep reinforced concrete “T”
    beam (4370 psi); details: see Note 6 figure.
    8.8 tons 1 hr
    53
    min
    7 1, 3 13/4
    B-10-RC-3 101/2″ 24″ wide × 101/2″ deep reinforced concrete
    “T” beam (4450 psi); details: see Note 7
    figure.
    8.8 tons 2 hrs
    40
    min
    7 1, 3 22/3
    B-11-RC-4 11″ 24″ wide × 11″ deep reinforced concrete “T”
    beam (2400 psi); details: see Note 8 figure.
    8.8 tons 3 hrs
    32
    min
    7 1, 3, 14 31/2
    B-11-RC-5 11″ 24″ wide × 11″ deep reinforced concrete “T”
    beam (4250 psi); details: see Note 9 figure.
    8.
  • CBC § 6.85 Medium relevance — show source text

    71|6.85|6.94| |42|80|38|5.90|6.21|6.40|6.61|6.75|6.84| |41|80|39|5.77|6.11|6.30|6.52|6.65|6.74| |46|85|39|5.77|6.11|6.30|6.52|6.65|6.74| |40|80|40|5.63|6.00|6.20|6.43|6.56|6.65| |45|85|40|5.63|6.00|6.20|6.43|6.56|6.65| |44|85|41|5.47|5.87|6.10|6.33|6.47|6.55| |43|85|42|5.30|5.74|5.98|6.24|6.37|6.46| |42|85|43|5.11|5.60|5.86|6.13|6.28|6.37| |41|85|44|4.90|5.44|5.72|6.02|6.17|6.27| |40|85|45|4.68|5.26|5.58|5.90|6.07|6.17| |Condenser DT2|Condenser DT2|Condenser DT2|14.04|11.23|9.36|7.02|5.62|4.68| |1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2. Condenser DT = Leaving Condenser Water Temperature (°F) – Entering Condenser Water Temperature (°F)
    Kadj = 6.1507 – 0.30244(×) + 0.0062692(×)2 – 0.000045595(×)3
    where× = Condenser DT + LIFT
    COPadj = Kadj * COPstd|1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2.

  • CBC § 5.410.2.1 Medium relevance — show source text

    Informational Note:

    1. Functional performance testing for heating, ventilation, air conditioning systems and lighting controls must be performed in compliance with the California Energy Code.

    5.410.2.1 Owner’s or Owner representative’s Project Requirements (OPR). [N] The expectations and requirements of the building appropriate to its phase shall be documented before the design phase of the project begins. This documentation shall include the following:

    1. Environmental and sustainability goals.
    2. Building sustainable goals.
    3. Indoor environmental quality requirements.
    4. Project program, including facility functions and hours of operation, and need for after hours operation.
    5. Equipment and systems expectations.
    6. Building occupant and operation and maintenance (O&M) personnel expectations.

    5.410.2.2 Basis of Design (BOD). [N] A written explanation of how the design of the building systems meets the OPR shall be completed at the design phase of the building project. The Basis of Design document shall cover the following systems:

    1. Renewable energy systems.

    2. Landscape irrigation systems.

    3. Water reuse systems.

    5.410.2.3 Commissioning plan. [N] Prior to permit issuance a commissioning plan shall be completed to document how the project will be commissioned. The commissioning plan shall include the following:

    1. General project information.
    2. Commissioning goals.
    3. Systems to be commissioned. Plans to test systems and components shall include: a. An explanation of the original design intent. b. Equipment and systems to be tested, including the extent of tests.

    c. Functions to be tested.

    d. Conditions under which the test shall be performed. e. Measurable criteria for acceptable performance. 4. Commissioning team information. 5. Commissioning process activities, schedules and responsibilities. Plans for the completion of commissioning shall be included.

    5.410.2.4 Functional performance testing. [N] Functional performance tests shall demonstrate the correct installation and operation of each component, system and system- to-system interface in accordance with the approved plans and specifications.

    2025 CALIFORNIA GREEN BUILDING STANDARDS CODE 5-27

    on Jul 18, 2025 11:14 AM (CDT) THEREUNDER.

    NONRESIDENTIAL MANDATORY MEASURES

    Functional performance testing reports shall contain information addressing each of the building components tested, the testing methods utilized, and include any readings and adjustments made.

    5.410.2.5 Documentation and training. [N] A systems manual and systems operations training are required, including Occupational Safety and Health Act (OSHA) requirements in California Code of Regulations (CCR), Title 8, Section 5142, and other related regulations.

    5.410.2.5.1 Systems manual. [N] Documentation of the operational aspects of the building shall be completed within the systems manual and delivered to the building owner or representative. The systems manual shall include the following:

    1. Site information, including facility description, history and current requirements.

    2. Site contact information.

    3. Basic operations and maintenance, including general site operating procedures, basic troubleshooting, recommended maintenance requirements, site events log.

    4. Major systems.

    5. Site equipment inventory and maintenance notes.

    6. A copy of verifications required by the enforcing agency or this code.

    7. Other resources and documentation, if applicable.

  • CBC § 1-5 Medium relevance — show source text

    102 Construction Documents

    and Installation Verification . . . . . . . . . . . . . . . . . . . .1-5

    103 Building Standards Commission. . . . . . . . . . . . . . . . . . .1-5 104 Department of Housing and Community Development. . . . . . . . . . . . . . . . . .1-6 105 Division of the State Architect . . . . . . . . . . . . . . . . . . . . .1-6

    106 Office of Statewide Health Planning and Development . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-6

    CHAPTER 2 DEFINITIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3

    201 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3

    202 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3

    CHAPTER 3 GREEN BUILDING . . . . . . . . . . . . . . . . . . . . . . . . 3-3

    301 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-3

    302 Mixed Occupancy Buildings . . . . . . . . . . . . . . . . . . . . . . .3-4 303 Phased Projects. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4 304 Voluntary Tiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4 305 CALGreen Tier 1 and CALGreen Tier 2 . . . . . . . . . . . . . .3-4

    306 Voluntary Measures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4

    CHAPTER 4 RESIDENTIAL MANDATORY MEASURES . . . . . . 4-3

    4.1 Planning and Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-3 4.2 Energy Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-7 4.3 Water Efficiency and Conservation . . . . . . . . . . . . . . . . .4-9 4.4 Material Conservation and Resource Efficiency . . . . 4-11 4.5 Environmental Quality . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13

    CHAPTER 5 NONRESIDENTIAL MANDATORY MEASURES . . 5-3

  • CBC § 7.11 Medium relevance — show source text

    80|7.11|7.35|7.71|7.97|8.16| |45|75|30|6.71|6.99|7.21|7.55|7.78|7.96| |44|75|31|6.61|6.89|7.09|7.40|7.61|7.77| |43|75|32|6.52|6.79|6.98|7.26|7.45|7.60| |42|75|33|6.43|6.69|6.87|7.13|7.31|7.44| |41|75|34|6.33|6.60|6.77|7.02|7.18|7.30| |46|80|34|6.33|6.60|6.77|7.02|7.18|7.30| |40|75|35|6.23|6.50|6.68|6.91|7.06|7.17| |45|80|35|6.23|6.50|6.68|6.91|7.06|7.17| |44|80|36|6.13|6.41|6.58|6.81|6.95|7.05| |43|80|37|6.02|6.31|6.49|6.71|6.85|6.94| |42|80|38|5.90|6.21|6.40|6.61|6.75|6.84| |41|80|39|5.77|6.11|6.30|6.52|6.65|6.74| |46|85|39|5.77|6.11|6.30|6.52|6.65|6.74| |40|80|40|5.63|6.00|6.20|6.43|6.56|6.65| |45|85|40|5.63|6.00|6.20|6.43|6.56|6.65| |44|85|41|5.47|5.87|6.10|6.33|6.47|6.55| |43|85|42|5.30|5.74|5.98|6.24|6.37|6.46| |42|85|43|5.11|5.60|5.86|6.13|6.28|6.37| |41|85|44|4.90|5.44|5.72|6.02|6.17|6.27| |40|85|45|4.68|5.26|5.58|5.90|6.07|6.17| |Condenser DT2|Condenser DT2|Condenser DT2|14.04|11.23|9.36|7.02|5.62|4.68| |1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2.

  • CBC § 6.10 Medium relevance — show source text

    84|6.10|6.30|6.61|6.84|7.00| |45|75|30|5.75|6.00|6.19|6.47|6.68|6.83| |44|75|31|5.67|5.91|6.08|6.34|6.53|6.67| |43|75|32|5.59|5.82|5.99|6.23|6.39|6.52| |42|75|33|5.51|5.74|5.90|6.12|6.27|6.39| |41|75|34|5.43|5.66|5.81|6.02|6.16|6.26| |46|80|34|5.43|5.66|5.81|6.02|6.16|6.26| |40|75|35|5.35|5.58|5.73|5.93|6.06|6.15| |45|80|35|5.35|5.58|5.73|5.93|6.06|6.15| |44|80|36|5.26|5.50|5.65|5.84|5.96|6.05| |43|80|37|5.16|5.42|5.57|5.76|5.87|5.96| |42|80|38|5.06|5.33|5.49|5.67|5.79|5.87| |41|80|39|4.95|5.24|5.41|5.60|5.71|5.78| |46|85|39|4.95|5.24|5.41|5.60|5.71|5.78| |40|80|40|4.83|5.14|5.32|5.52|5.63|5.70| |45|85|40|4.83|5.14|5.32|5.52|5.63|5.70| |44|85|41|4.69|5.04|5.253|5.43|5.55|5.62| |43|85|42|4.55|4.93|5.13|5.35|5.47|5.54| |42|85|43|4.38|4.80|5.03|5.26|5.38|5.46| |41|85|44|4.21|4.67|4.91|5.17|5.30|5.38| |40|85|45|4.01|4.52|4.79|5.06|5.20|5.29| |Condenser DT2|Condenser DT2|Condenser DT2|14.04|11.23|9.36|7.02|5.62|4.68| |1. LIFT = Entering Condenser Water Temperature (°F) – Leaving Chilled Water Temperature (°F)
    2.

  • CBC § 20.0 Medium relevance — show source text

    2 gpm/hp|CTI ATC-105| |Propeller or axial fan
    open cooling towers|All|85°F leaving water|85°F leaving water|and| |Propeller or axial fan
    open cooling towers|All|75°F wb outdoor air|75°F wb outdoor air|CTI STD-201| |Centrifugal fan open
    cooling towers|All|95°F entering water|≥ 20.0 gpm/hp|CTI ATC-105| |Centrifugal fan open
    cooling towers|All|85°F leaving water|85°F leaving water|and| |Centrifugal fan open
    cooling towers|All|75°F wb outdoor air|75°F wb outdoor air|CTI STD-201| |Air cooled condensers|All|125°F condensing
    temperature|≥ 176,000 Btu/h·hp|ARI 460| |Air cooled condensers|All|R22 test fluid|R22 test fluid|R22 test fluid| |Air cooled condensers|All|190°F entering gas
    temperature|190°F entering gas
    temperature|190°F entering gas
    temperature| |Air cooled condensers|All|15°F subcooling|15°F subcooling|15°F subcooling| |Air cooled condensers|All|95°F entering drybulb|95°F entering drybulb|95°F entering drybulb| |1. For purposes of this table, open cooling tower performance is defined as the maximum flow rating of the tower divided by the fan nameplate rated motor power.
    2. For purposes of this table air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the fan nameplate rated motor power.
    3. Open cooling towers shall be tested using the test procedures in CTI ATC-105. Performance of factory assembled open cooling towers shall be either certified as base models
    as specified in CTI STD-201 or verified by testing in the field by a CTI approved testing agency. Open factory assembled cooling towers with custom options added to a CTI
    certified base model for the purpose of safe maintenance or to reduce environmental or noise impact shall be rated at 90 percent of the CTI certified performance of the asso-
    ciated base model or at the manufacturer’s stated performance, whichever is less. Base models of open factory assembled cooling towers are open cooling towers configured
    in exact accordance with the Data of Record submitted to CTI as specified by CTI STD-201. There are no certification requirements for field erected cooling towers.
    4. The efficiencies for open cooling towers listed in Table A6.207.1-G are not applicable for closed-circuit cooling towers.|1. For purposes of this table, open cooling tower performance is defined as the maximum flow rating of the tower divided by the fan nameplate rated motor power.
    2. For purposes of this table air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the fan nameplate rated motor power.
    3. Open cooling towers shall be tested using the test procedures in CTI ATC-105. Performance of factory assembled open cooling towers shall be either certified as base models
    as specified in CTI STD-201 or verified by testing in the field by a CTI approved testing agency. Open factory assembled cooling towers with custom options added to a CTI
    certified base model for the purpose of safe maintenance or to reduce environmental or noise impact shall be rated at 90 percent of the CTI certified performance of the asso-
    ciated base model or at the manufacturer’s stated performance, whichever is less.

Frequently asked questions

Must every CalGreen energy item be proven via a Part 6 submittal?

Yes — where CalGreen’s mandatory measures refer to energy performance or testing, they are satisfied by complying with the California Energy Code (Part 6) and by submitting the Part 6 required Certificates of Compliance / Acceptance as applicable. § 5.201.1 directs users to Part 6.

If a jurisdiction has a local energy ordinance, which controls?

Local energy ordinances may be enforced only if they have Energy Commission approval or are found by the Energy Commission to require no more energy than Part 6; verify local adoption under the CBC/CalGreen administrative provisions before assuming the local ordinance controls.

Do CalGreen commissioning requirements replace Part 6 acceptance testing?

No — they are complementary. CalGreen requires commissioning and functional testing for systems; when those systems are regulated by Part 6 (lighting, HVAC, controls), the Part 6 acceptance test procedures and certificate requirements apply and must be used in the commissioning program.

Where do I find the Part 6 equations for PV sizing and exceptions?

Part 6 contains the PV sizing equations and the SARA rules — use the Part 6 PV equation and check the Part 6 exceptions for minimum kW thresholds and available SARA conditions. See the Part 6 PV sizing equations.

I don’t see § [A]101.4.6 in the files you searched — can you check it?

I was not able to retrieve the text of § [A]101.4.6 in the provided files. If you upload a copy of the CBC Appendix or provide the specific file containing § [A]101.4.6 I will extract the exact wording and update the guidance.

More in California Building Code

Ask about the CBC

Get cited, plain-English answers on the California Building Code for your project — any code section, any scenario.

Start Free Trial

Related in the CBC