Earlier editions: 2026-09
Title 15 — BUILDINGS AND CONSTRUCTION
Whittier Municipal Code Ch. 15.02 Building Code
Whittier Municipal Code · 2026-10 edition · updated 2026-10-04 · Whittier
Cite as: Whittier Municipal Code Chapter 15.02 · Text as of 2026-10-04
15.02.010 - Documents—Adopted by reference.¶
(a) The City Council of the City of Whittier hereby adopts the California Building Code specified in Chapter 15.01.010 as Chapter 15.02.010 of Title 15 of the Codes, except such portions as are deleted, modified, or amended as set forth in this chapter. Said Code is adopted and incorporated as if fully set forth herein.
(b) The purpose of these Codes is to prescribe regulations for the erection, construction, enlargement, alteration, repair, improving, removal, conversion, demolition, occupancy, equipment, use, height, area and maintenance of all buildings and structures.
((Ord. No. 3173, § 4, 12-9-25)
State Law reference— Authority to regulate construction, Government Code § 38660; California Building Standards Law, Government Code § 18901 et seq.
15.02.020 - Chapter 1, Division II Scope and Administration amended.¶
The text within Chapter 1 Division II is deleted and replaced with the following:
Division II Administrative Provisions
Section 101. For administrative provisions for this Code, see Sec. 15.01.040.
(Ord. No. 3173, § 4, 12-9-25)
Amendments to Building Code (15.02)¶
15.02.030 - Section 312.1 amended.¶
Section 312.1 is amended to add "swimming pools" to the list of Group U occupancies such that the section reads as follows:
312.1 General. Buildings and structures of an accessory character and miscellaneous structures not classified in any specific occupancy will be constructed, equipped, and maintained to conform to the requirements of the Codes commensurate with the fire and life hazard incidental to their occupancy. Group U will include, but not be limited to, the following:
Agricultural buildings
Aircraft hangars, accessory to a one-or two-family residence (see Section 412.3)
Barns
Carports
Fences more than 6 feet (1,829 mm) high
Grain silos, accessory to a residential occupancy
Greenhouses
Livestock shelters
Private garages
Retaining walls
Sheds
Stables
Tanks
Towers
Swimming pools
(Ord. No. 3173, § 4, 12-9-25)
15.02.040 - Sections 705.2.3 amended.¶
Section 705.2.3 is amended by adding an additional exception to read as follows:
Type VB construction shall be allowed for combustible projections for additions to existing R-3 occupancies provided the fire separation distance is greater than or equal to 2 feet and the floor area of the addition does not exceed 50 percent of the existing floor area of the R-3 occupancy.
(Ord. No. 3173, § 4, 12-9-25)
15.02.050 - Sections 718.3 amended.¶
Section 718.3 is amended by deletion of the Exception.
(Ord. No. 3173, § 4, 12-9-25)
15.02.060 - Sections 718.4 amended.¶
Section 718.4 is amended by deletion of the Exception:
(Ord. No. 3173, § 4, 12-9-25)
15.02.070 - Table 1505.1 amended.¶
Table 1505.1 is amended, by the deletion of Table 1505.1 and the addition of a new Table 1505.1 thereto, to read as follows:
TABLE 1505.1 a MINIMUM ROOF COVERING CLASSIFICATIONS TYPES OF CONSTRUCTION
| IA | IB | IIA | IIB | IIIA | IIIB | IV | VA | VB |
|---|---|---|---|---|---|---|---|---|
| A | A | A | A | A | A | A | A | A |
(Ord. No. 3173, § 4, 12-9-25)
15.02.080 - Section 1505.1.2 amended.¶
Section 1505.1.2 is amended, by the deletion of the entire section and the addition of a new section thereto, to read as follows:
1505.1.2 Roof coverings within all other areas. The entire roof covering of every existing structure where more than 50 percent of the total roof area is replaced within any one-year period, the entire roof covering of every new structure, and any roof covering applied in the alteration, repair or replacement of the roof of every existing structure, shall be a fire-retardant roof covering that is at least Class A.
(Ord. No. 3173, § 4, 12-9-25)
15.02.090 - Section 1618 added.¶
Section 1618 is added to Chapter 16 to read as follows:
1618.1 Seismic Design Provisions for Hillside Buildings.
1618.1.1 Purpose. The purpose of this section is to establish minimum regulations for the design and construction of new buildings and additions to existing buildings when constructing such buildings on or into slopes steeper than one unit vertical in three units horizontal (33.3%). These regulations establish minimum standards for seismic force resistance to reduce the risk of injury or loss of life in the event of earthquakes.
1618.1.2 Scope. The provisions of this section shall apply to the design of the lateral-force-resisting system for hillside buildings at and below the base level diaphragm. The design of the lateral-force resisting system above the base level diaphragm shall be in accordance with the provisions for seismic and wind design as required elsewhere in this division.
Exception: Non-habitable accessory buildings and decks not supporting or supported from the main building are exempt from these regulations.
1618.2 Definitions. For the purposes of this section certain terms are defined as follows:
BASE LEVEL DIAPHRAGM is the floor at, or closest to, the top of the highest level of the foundation.
DIAPHRAGM ANCHORS are assemblies that connect a diaphragm to the adjacent foundation at the uphill diaphragm edge.
DOWNHILL DIRECTION is the descending direction of the slope approximately perpendicular to the slope contours.
FOUNDATION is concrete or masonry which supports a building, including footings, stem walls, retaining walls, and grade beams.
FOUNDATION EXTENDING IN THE DOWNHILL DIRECTION is a foundation running downhill and approximately perpendicular to the uphill foundation.
HILLSIDE BUILDING is any building or portion thereof constructed on or into a slope steeper than one unit vertical in three units horizontal (33.3%). If only a portion of the building is supported on or into the slope, these regulations apply to the entire building.
PRIMARY ANCHORS are diaphragm anchors designed for and providing a direct connection as described in Sections 1618.4 and 1618.7 between the diaphragm and the uphill foundation.
SECONDARY ANCHORS are diaphragm anchors designed for and providing a redundant diaphragm to foundation connection, as described in Sections 1618.5 and 1618.6.3.1.
UPHILL DIAPHRAGM EDGE is the edge of the diaphragm adjacent and closest to the highest ground level at the perimeter of the diaphragm.
UPHILL FOUNDATION is the foundation parallel and closest to the uphill diaphragm edge.
1618.3 Analysis and Design.
1618.3.1 General. Every hillside building within the scope of this section shall be analyzed, designed, and constructed in accordance with the provisions of this division. When the code prescribed wind design produces greater effects, the wind design shall govern, but detailing requirements and limitations prescribed in this and referenced sections shall be followed.
1618.3.2 Base Level Diaphragm-Downhill Direction. The following provisions shall apply to the seismic analysis and design of the connections for the base level diaphragm in the downhill direction.
1618.3.2.1 Base for Lateral Force Design Defined. For seismic forces acting in the downhill direction, the base of the building shall be the floor at or closest to the top of the highest level of the foundation.
1618.3.2.2 Base Shear. In developing the base shear for seismic design, the response modification coefficient (R) shall not exceed 5 for bearing wall and building frame systems. The total base shear shall include the forces tributary to the base level diaphragm including forces from the base level diaphragm.
1618.4 Base Shear Resistance-Primary Anchors.
1618.4.1 General. The base shear in the downhill direction shall be resisted through primary anchors from diaphragm struts provided in the base level diaphragm to the foundation.
1618.4.2 Location of Primary Anchors. A primary anchor and diaphragm strut shall be provided in line with each foundation extending in the downhill direction. Primary anchors and diaphragm struts shall also be provided where interior vertical lateral-force-resisting elements occur above and in contact with the base level diaphragm. The spacing of primary anchors and diaphragm struts or collectors shall in no case exceed 30 feet (9144 mm).
1618.4.3 Design of Primary Anchors and Diaphragm Struts. Primary anchors and diaphragm struts shall be designed in accordance with the requirements of Section 1613.7.8.
1618.4.4 Limitations. The following lateral-force-resisting elements shall not be designed to resist seismic forces below the base level diaphragm in the downhill direction:
Wood structural panel wall sheathing,
Cement plaster and lath,
Gypsum wallboard, and
Tension only braced frames.
Braced frames designed in accordance with the requirements of AISC 341 may be used to transfer forces from the primary anchors and diaphragm struts to the foundation provided lateral forces do not induce flexural stresses in any member of the frame or in the diaphragm struts. Deflections of frames shall account for the variation in slope of diagonal members when the frame is not rectangular.
1618.5 Base Shear Resistance-Secondary Anchors.
1618.5.1 General. In addition to the primary anchors required by Section 1618.4, the base shear in the downhill direction shall be resisted through secondary anchors in the uphill foundation connected to diaphragm struts in the base level diaphragm.
Exception: Secondary anchors are not required where foundations extending in the downhill direction spaced at not more than 30 feet (9144 mm) on center extend up to and are directly connected to the base level diaphragm for at least 70% of the diaphragm depth.
1618.5.2 Secondary Anchor Capacity and Spacing. Secondary anchors at the base level diaphragm shall be designed for a minimum force equal to the base shear, including forces based on Allowable Stress Design (ASD) levels. The secondary anchors shall be uniformly distributed along the uphill diaphragm edge and shall be spaced a maximum of 4 feet (1219 mm) on center.
1618.5.3 Design. Secondary anchors and diaphragm struts shall be designed in accordance with Section 1618.7.
1618.6 Diaphragms Below the Base Level-Downhill Direction. The following provisions shall apply to the lateral analysis and design of the connections for all diaphragms below the base level diaphragm in the downhill direction.
1618.6.1 Diaphragm Defined. Every floor level below the base level diaphragm shall be designed as a diaphragm.
1618.6.2 Design Force. Each diaphragm below the base level diaphragm shall be designed for all tributary loads at that level using a minimum seismic force factor not less than the base shear coefficient.
1618.6.3 Design Force Resistance-Primary Anchors. The design force described in Section 1618.6.2 shall be resisted through primary anchors from diaphragm struts provided in each diaphragm to the foundation. Primary anchors shall be provided and designed in accordance with the requirements and limitations of Section 1618.4.
1618.6.3.1 Design Force Resistance-Secondary Anchors.
1618.6.3.1.1 General. In addition to the primary anchors required in Section 1618.4, the design force in the downhill direction shall be resisted through secondary anchors in the uphill foundation connected to diaphragm struts in each diaphragm below the base level.
Exception: Secondary anchors are not required where foundations extending in the downhill direction, spaced at not more than 30 feet (9144 mm) on center, extend up to and are directly connected to each diaphragm below the base level for at least 70% of the diaphragm depth.
1618.6.3.1.2 Secondary Anchor Capacity. Secondary anchors at each diaphragm below the base level diaphragm shall be designed for a minimum force equal to the design force but not less than 300 pounds per lineal foot (4.38 kN/m) based on Allowable Stress Design (ASD) levels. The secondary anchors shall be uniformly distributed along the uphill diaphragm edge and shall be spaced a maximum of 4 feet (1219 mm) on center.
1618.6.3.1.3 Design. Secondary anchors and diaphragm struts shall be designed in accordance with Section 1618.7.
1618.7 Primary and Secondary Anchorage and Diaphragm Strut Design. Primary and secondary anchors and diaphragm struts shall be designed in accordance with the following provisions:
Fasteners. All bolted fasteners used to develop connections to wood members shall be provided with square plate washers at all bolt heads and nuts. Washers shall be minimum 0.229 inch by 3 inches by 3 inches (5.82 mm by 76 mm by 76 mm) in size. Nuts shall be tightened to finger tight plus one half (1/2) wrench turn prior to covering the framing.
Fastening. The diaphragm to foundation anchorage shall not be accomplished by the use of toenailing, nails subject to withdrawal, or wood in cross-grain bending or cross-grain tension.
Size of Wood Members. Wood diaphragm struts collectors, and other wood members connected to primary anchors shall not be less than 3 inches (76 mm) in nominal width. The effects of eccentricity on wood members shall be evaluated as required per Item 9.
Design. Primary and secondary anchorage, including diaphragm struts, splices, and collectors shall be designed for 125% of the tributary force.
Allowable Stress Increase. The one-third allowable stress increase permitted under Section 1605.3.2 shall not be taken when the working (allowable) stress design method is used.
Steel Element of Structural Wall Anchorage System. The strength design forces for steel elements of the structural wall anchorage system, with the exception of anchor bolts and reinforcing steel, shall be increased by 1.4 times the forces otherwise required.
Primary Anchors. The load path for primary anchors and diaphragm struts shall be fully developed into the diaphragm and into the foundation. The foundation must be shown to be adequate to resist the concentrated loads from the primary anchors.
Secondary Anchors. The load path for secondary anchors and diaphragm struts shall be fully developed in the diaphragm but need not be developed beyond the connection to the foundation.
Symmetry. All lateral force foundation anchorage and diaphragm strut connections shall be symmetrical. Eccentric connections may be permitted when demonstrated by calculation or tests that all components of force have been provided for in the structural analysis or tests.
Wood Ledgers. Wood ledgers shall not be used to resist cross-grain bending or cross-grain tension.
1618.8 Lateral-Force-Resisting Elements Normal to the Downhill Direction.
1618.8.1 General. In the direction normal to the downhill direction, lateral-force-resisting elements shall be designed in accordance with the requirements of this section.
1618.8.2 Base Shear. In developing the base shear for seismic design, the response modification coefficient (R) shall not exceed 5 for bearing wall and building frame systems.
1618.8.3 Vertical Distribution of Seismic Forces. For seismic forces acting normal to the downhill direction the distribution of seismic forces over the height of the building using Section 12.8.3 of ASCE 7 shall be determined using the height measured from the top of the lowest level of the building foundation.
1618.8.4 Drift Limitations. The story drift below the base level diaphragm shall not exceed 0.007 times the story height at strength design force level. The total drift from the base level diaphragm to the top of the foundation shall not exceed 3/4 inch (19 mm). Where the story height or the height from the base level diaphragm to the top of the foundation varies because of a stepped footing or story offset, the height shall be measured from the average height of the top of the foundation. The story drift shall not be reduced by the effect of the horizontal diaphragm stiffness.
1618.8.5 Distribution of Lateral Forces.
1618.8.5.1 General. The design lateral force shall be distributed to lateral-force-resisting elements of varying heights in accordance with the stiffness of each individual element.
1618.8.5.2 Wood Structural Panel Sheathed Walls. The stiffness of a stepped wood structural panel shear wall may be determined by dividing the wall into an adjacent rectangular estimated by AWC SDPWS Section 4.3.2. Sheathing and fastening requirements for the stiffest section shall be used for the entire wall. Each section of wall shall be anchored for shear and uplift at each step. The minimum horizontal length of a step shall be 8 feet (2438 mm) and the maximum vertical height of a step shall be 2 feet 8 inches (813 mm).
1618.8.5.3 Reinforced Concrete or Masonry Shear Walls. Reinforced concrete or masonry shear walls shall have forces distributed in proportion to the rigidity of each section of the wall.
1618.8.5.4 Limitations. The following lateral force-resisting-elements shall not be designed to resist lateral forces below the base level diaphragm in the direction normal to the downhill direction:
Cement plaster and lath,
Gypsum wallboard, and
Tension-only braced frames.
Braced frames designed in accordance with the requirements of Section 2205A of this Code may be designed as lateral-force-resisting elements in the direction normal to the downhill direction, provided lateral forces do not induce flexural stresses in any member of the frame. Deflections of frames shall account for the variation in slope of diagonal members when the frame is not rectangular.
1618.9 Specific Design Provisions.
1618.9.1 Footings and Grade Beams. All footings and grade beams shall comply with the following:
Grade beams shall extend at least 12 inches (305 mm) below the lowest adjacent grade and provide a minimum 24-inch (610 mm) distance horizontally from the bottom outside face of the grade beam to the face of the descending slope.
Continuous footings shall be reinforced with at least two No. 4 reinforcing bars at the top and two No. 4 reinforcing bars at the bottom.
All main footing and grade beam reinforcement steel shall be bent into the intersecting footing and fully developed around each corner and intersection.
All concrete stem walls shall extend from the foundation and reinforced as required for concrete or masonry walls.
1618.9.2 Protection Against Decay and Termites. All wood to earth separation shall comply with the following:
- Where a footing or grade beam extends across a descending slope, the stem wall, grade beam, or footing shall extend up to a minimum 18 inches (457 mm) above the highest adjacent grade.
Exception: At paved garage and doorway entrances to the building, the stem wall need only extend to the finished concrete slab, provided the wood framing is protected with a moisture proof barrier.
- Wood ledgers supporting a vertical load of more than 100 pounds per lineal foot (1.46 kN/m) based on Allowable Stress Design (ASD) levels and located within 48 inches (1219 mm) of adjacent grade are prohibited. Galvanized steel ledgers and anchor bolts, with or without wood nailers, or treated or decay resistant sill plates supported on a concrete or masonry seat, may be used.
1618.9.3 Sill Plates. All sill plates and anchorage shall comply with the following:
All wood framed walls, including nonbearing walls, when resting on a footing, foundation, or grade beam stem wall, shall be supported on wood sill plates bearing on a level surface.
Power-driven fasteners shall not be used to anchor sill plates except at interior nonbearing walls not designed as shear walls.
1618.9.4 Column Base Plate Anchorage. The base of isolated wood posts (not framed into a stud wall) supporting a vertical load of 4,000 pounds (17.8 kN) based on Allowable Stress Design (ASD) levels or more and the base plate for a steel column shall comply with the following:
When the post or column is supported on a pedestal extending above the top of a footing or grade beam, the pedestal shall be designed and reinforced as required for concrete or masonry columns. The pedestal shall be reinforced with a minimum of four No. 4 bars extending to the bottom of the footing or grade beam. The top of exterior pedestals shall be sloped for positive drainage.
The base plate anchor bolts or the embedded portion of the post base, and the vertical reinforcing bars for the pedestal, shall be confined with two No. 4 or three No. 3 ties within the top 5 inches (127 mm) of the concrete or masonry pedestal. The base plate anchor bolts shall be embedded a minimum of 20 bolt diameters into the concrete or masonry pedestal. The base plate anchor bolts and post bases shall be galvanized, and each anchor bolt shall have at least 2 galvanized nuts above the base plate.
1618.9.5 Steel Beam to Column Supports. All steel beam to column supports shall be positively braced in each direction. Steel beams shall have stiffener plates installed on each side of the beam web at the column. The stiffener plates shall be welded to each beam flange and the beam web. Each brace connection or structural member shall consist of at least two 5/8-inch (15.9 mm) diameter machine bolts.
(Ord. No. 3173, § 4, 12-9-25)
15.02.100 - Section 1807.1.4 amended.¶
Section 1807.1.4 amended to read as follows:
1807.1.4 Permanent wood foundation systems. Permanent wood foundation systems shall be designed and installed in accordance with AWC PWF. Lumber and plywood shall be treated in accordance with AWPA U1 (Commodity Specification A, Special Requirement 4.2) and shall be identified in accordance with Section 2303.1.9.1. Permanent wood foundation systems shall not be used for structures assigned to Seismic Design Category D, E or F.
(Ord. No. 3173, § 4, 12-9-25)
15.02.110 - Section 1807.1.6 amended.¶
Section 1807.1.6 amended to read as follows:
1807.1.6 Prescriptive design of concrete and masonry foundation walls. Concrete and masonry foundation walls that are laterally supported at the top and bottom shall be permitted to be designed and constructed in accordance with this section. Prescriptive design of foundation walls shall not be used for structures assigned to Seismic Design Category D, E or F.
(Ord. No. 3173, § 4, 12-9-25)
15.02.120 - Section 1809.3 amended.¶
Section 1809.3 amended to read as follows:
1809.3 Stepped footings. The top surface of footings shall be level. The bottom surface of footings shall be permitted to have a slope not exceeding one unit vertical in 10 units horizontal (10-percent slope). Footings shall be stepped where it is necessary to change the elevation of the top surface of the footing or where the surface of the ground slopes more than one unit vertical in 10 units horizontal (10-percent slope).
For structures assigned to Seismic Design Category D, E or F, the stepping requirement shall also apply to the top surface of grade beams supporting walls. Footings shall be reinforced with four No. 4 bars. Two bars shall be place at the top and bottom of the footings as shown in Figure 1809.3.
[Figure: FIGURE 1809.3 STEPPED FOOTING]
FIGURE 1809.3 STEPPED FOOTING
15.02.130 - Section 1809.4 amended.¶
Section 1809.4 amended the first sentence to read as follows:
1809.4 Depth and Width of Footings. The minimum depth of footings below undisturbed ground surface shall be 18 inches (305 mm).
(Ord. No. 3173, § 4, 12-9-25)
15.02.140 - Section 1809.7 and Table 1809.7 amended.¶
Section 1809.7 and Table 1809.7 amended to read as follows:
1809.7 Prescriptive footings for light-frame construction. Where a specific design is not provided, concrete or masonry-unit footings supporting walls of light-frame construction shall be permitted to be designed in accordance with Table 1809.7. Prescriptive footings in Table 1809.7 shall not exceed one story above grade plane for structures assigned to Seismic Design Category D, E or F.
TABLE 1809.7 PRESCRIPTIVE FOOTINGS SUPPORTING WALLS OF LIGHT-FRAME CONSTRUCTION a,b,c,d,e
| NUMBER OF FLOORS SUPPORTED BY FOOTING f | WIDTH OF FOOTING (inches) | THICKNESS OF FOOTING (inches) |
|---|---|---|
| 1 | 12 | 6 |
| 2 | 15 | 6 |
| 3 | 18 | 8 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm
a Depth of footings shall be in accordance with Section 1809.4.
b The ground under the floor shall be permitted to be excavated to the elevation of the top of the footing.
c Interior stud bearing walls shall be permitted to be supported by isolated footings. The footing width and length shall be twice the width shown in this table, and footings shall be spaced not more than 6 feet on center.
d See Section 1908 for additional requirements for concrete footings of structures assigned to Seismic Design Category C, D, E or F.
e For thickness of foundation walls, see Section 1807.1.6.
f Footings shall be permitted to support a roof addition to the stipulated number of floors. Footings supporting roof only shall be as required for supporting one floor.
(Ord. No. 3173, § 4, 12-9-25)
15.02.150 - Section 1809.12 amended.¶
Section 1809.12 amended to read as follows:
1809.12 Timber footings. Timber footings shall be permitted for buildings of Type V construction and as otherwise approved by the building official. Such footings shall be treated in accordance with AWPA U1 (Commodity Specification A, Use Category 4B). Treated timbers are not required where placed entirely below permanent water level, or where used as capping for wood piles that project above the water level over submerged or marsh lands. The compressive stresses perpendicular to grain in untreated timber footing supported upon treated piles shall not exceed 70 percent of the allowable stresses for the species and grade of timber as specified in the ANSI/AWC NDS. Timber footings shall not be used in structures assigned to Seismic Design Category D, E or F.
(Ord. No. 3173, § 4, 12-9-25)
15.02.160 - Section 1810.3.2.4 amended.¶
Section 1810.3.2.4 amended to read as follows:
1810.3.2.4 Timber. Timber deep foundation elements shall be designed as piles or poles in accordance with ANSI/AWC NDS. Round timber elements shall conform to ASTM D 25. Sawn timber elements shall conform to DOC PS-20. Timber shall not be used in structures assigned to Seismic Design Category D, E or F.
(Ord. No. 3173, § 4, 12-9-25)
15.02.170 - Section 2304.10.1 amended.¶
Section 2304.10.1 amended to read as follows:
2304.10.1 Fastener requirements. Connections for wood members shall be designed in accordance with the appropriate methodology in Section 2302.2. The number and size of fasteners connecting wood members shall not be less than that set forth in Table 2304.10.2. Staple fasteners in Table 2304.10.1 shall not be used to resist or transfer seismic forces in structures assigned to Seismic Design Category D, E or F.
Exception: Staples may be used to resist or transfer seismic forces when the allowable shear values are substantiated by cyclic testing and approved by the building official.
(Ord. No. 3173, § 4, 12-9-25)
15.02.180 - Section 2304.12.2.8 amended.¶
Section 2304.12.2.8 amended to read as follows:
2304.12.2.8 Wood used in retaining walls and cribs. Wood installed in retaining or crib walls shall be preservative treated in accordance with AWPA U1 for soil and freshwater use. Wood shall not be used in retaining or crib walls for structures assigned to Seismic Design Category D, E or F.
(Ord. No. 3173, § 4, 12-9-25)
15.02.190 - Section 2305.4 added.¶
Section 2305.4 added to Chapter 23 to read as follows:
2305.4 Quality of Nails. In Seismic Design Category D, E or F, mechanically driven nails used in wood structural panel shear walls shall meet the same dimensions as that required for hand-driven nails, including diameter, minimum length, and minimum head diameter. Clipped head or box nails are not permitted in new construction. The allowable design value for clipped head nails in existing construction may be taken at no more than the nail-head-area ratio of that of the same size hand-driven nails.
15.02.200 - Section 2305.5 added.¶
Section 2305.5 added to Chapter 23 to read as follows:
2305.5 Hold-down connectors. In Seismic Design Category D, E or F, hold-down connectors shall be designed to resist shear wall overturning moments using approved cyclic load values or 75 percent of the allowable seismic load values that do not consider cyclic loading of the product. Connector bolts into wood framing shall require steel plate washers on the post on the opposite side of the anchorage device. Plate size shall be a minimum of 0.229 inch by 3 inches by 3 inches (5.82 mm by 76 mm by 76 mm) in size. Hold-down connectors shall be tightened to finger tight plus one half (1/2) wrench turn prior to covering the wall framing.
(Ord. No. 3173, § 4, 12-9-25)
15.02.210 - Section 2306.2 amended.¶
Section 2306.2 amended to read as follows:
2306.2 Wood-frame diaphragms. Wood-frame diaphragms shall be designed and constructed in accordance with AWC SDPWS. Where panels are fastened to framing members with staples, requirements and limitations of AWC SDPWS shall be met and the allowable shear values set forth in Table 2306.2(1) or 2306.2(2) shall only be permitted for structures assigned to Seismic Design Category A, B, or C.
Exception: Allowable shear values where panels are fastened to framing members with staples may be used if such values are substantiated by cyclic testing and approved by the building official.
The allowable shear values in Tables 2306.2(1) and 2306.2(2) are permitted to be increased 40 percent for wind design.
Wood structural panel diaphragms used to resist seismic forces in structures assigned to Seismic Design Category D, E or F shall be applied directly to the framing members.
Exception: Wood structural panel diaphragms are permitted to be fastened over solid lumber planking or laminated decking, provided the panel joints and lumber planking or laminated decking joints do not coincide.
(Ord. No. 3173, § 4, 12-9-25)
5.02.220 - Section 2306.3 amended.¶
Section 2306.3 amended to read as follows:
2306.3 Wood-frame shear walls. Wood-frame shear walls shall be designed and constructed in accordance with AWC SDPWS. For structures assigned to Seismic Design Category D, E, or F, application of Tables 4.3A and 4.3B of AWC SDPWS shall include the following:
Wood structural panel thickness for shear walls shall not be less than 3/8 inch thick and studs shall not be spaced at more than 16 inches on center.
The maximum nominal unit shear capacities for 3/8-inch wood structural panels resisting seismic forces in structures assigned to Seismic Design Category D, E or F is 400 pounds per linear foot
Exception: Other nominal unit shear capacities may be permitted if such values are substantiated by cyclic testing and approved by the building official.
Nails shall be placed not less than 1/2 inch in from the panel edges and not less than 3/8 inch from the edge of the connecting members for shear greater than 350 plf using ASD or 500 plf using LRFD. Nails shall be placed not less than 3/8 inch from panel edges and not less than 1/4 inch from the edge of the connecting members for shears of 350 plf or less using ASD or 500 plf or less using LRFD.
Table 4.3B application is not allowed for structures assigned to Seismic Design Category D, E, or F.
For structures assigned to Seismic Design Category D, application of Table 4.3C of AWC SDPWS shall not be used below the top level in a multi-level building.
Where panels are fastened to framing members with staples, requirements, and limitations of AWC SDPWS shall be met and the allowable shear values set forth in Table 2306.3(1), 2306.3(2) or 2306.3(3) shall only be permitted for structures assigned to Seismic Design Category A, B, or C.
Exception: Allowable shear values where panels are fastened to framing members with staples may be used if such values are substantiated by cyclic testing and approved by the building official.
The allowable shear values in Tables 2306.3(1) and 2306.3(2) are permitted to be increased 40 percent for wind design. Panels complying with ANSI/APA PRP-210 shall be permitted to use design values for Plywood Siding in the AWC SDPWS.
(Ord. No. 3173, § 4, 12-9-25)
15.02.230 - Section 2307.2 added.¶
Section 2307.2 added to read as follows:
2307.2 Wood-frame shear walls. Wood-frame shear walls shall be designed and constructed in accordance with Section 2306.3 as applicable.
(Ord. No. 3173, § 4, 12-9-25)
Get a plain-English answer with a citation back to this text.
Ask AI about this code