1705.3 Concrete Construction.

San Jose Municipal Code · 2026-09 edition · updated 2026-09-29 · San Jose

The special inspections and tests of concrete construction shall be

performed in accordance with this section and Table 1705.3.

Exceptions: Special inspections and tests shall not be required for:

Isolated spread concrete footings of buildings three stories or less above grade plane that are fully supported on earth or rock, where the structural design of the footing is based on a specified compressive strength, f'c, no greater than two thousand five hundred pounds per square inch (psi) (17.2 MPa).

Continuous concrete footings supporting walls of buildings three stories or less above grade plane that are fully supported on earth or rock where:

2.1.

The footings support walls of light-frame construction;

2.2.

The footings are designed in accordance with Table 1809.7; or

2.3.

The structural design of the footing is based on a specified compressive strength, f'c, no greater than two thousand five hundred pounds per square inch (psi) (17.2 Mpa), regardless of the compressive strength specified in the approved construction documents or used in the footing construction.

Nonstructural concrete slabs supported directly on the ground, including prestressed slabs on grade, where the effective prestress in the concrete is less than one hundred fifty psi (1.03 Mpa).

Concrete foundation walls constructed in accordance with table 1807.1.6.2.

Concrete patios, driveways and sidewalks, on grade.

(Ords. 28166, 28838, 29334, 29806, 30326.)