6.6.6.3 is deleted.

6.6.7 is deleted.

6.8.8 Control valves are required to be zoned per floor.

6.11.2 Fire department connections (FDC) shall be 2½ in. inlets with female National Standard Hose threads; all inlets shall be equipped with individual check valves (e.g. clappers). The FDC inlets shall be located at a height of 30 to 36" aboveground.

6.16.4 Where a building fire alarm system is provided, the building sprinkler systems are required to be zoned by floor.

10.2.2.1 Systems shall be hydrostatically tested for leakage at 200 psi for a duration of 2 hours in accordance with NFPA 13.

10.2.2.2 is deleted. (Ord. 31258.)