Skip to content

Chapter 15.20 — CALIFORNIA FIRE CODE

2810.7 Footprint of Pallet Stacks.

Patterson Municipal Code · 2026-07 edition · updated 2026-09-27 · Patterson

  1. The maximum dimensions of a pile shall not exceed twenty (20) feet by seventy (70) feet.

  2. There shall be ten (10) feet of aisle ways between piles.

  3. Piles shall be placed in grids not to exceed one hundred forty (140) feet by one hundred fifty (150) feet.

  4. Each grid shall be separated by an approved fire apparatus access road.

(Image not reproduced in this text.)

  • MM. Alternative Approach. Section 2810.11 of the 2025 California Fire Code is hereby amended to read as follows: